Cooper Power Systems Kyle GV, Kyle GW Installation Instructions Manual

Page 1
Figure 1. Kyle®Type GW Sectionalizer.
84574KMA
Contents
Safety Information .................................................. 2
Hazard Statement Definitions ............................. 2
Safety Instructions .............................................. 2
Product Information ............................................... 3
Introduction ......................................................... 3
Acceptance and Initial Inspection ........................ 3
Handling and Storage .......................................... 3
Standards ........................................................... 3
Description........................................................... 3
Ratings .................................................................... 4
Operating Controls and Settings .......................... 6
Manual Operating Controls ................................. 6
Auxiliary Power .................................................... 6
Indicating Devices................................................ 6
Settings ............................................................... 7
Inrush-Current Restraint ...................................... 8
Response Time.................................................... 8
Installation............................................................... 9
Oil Level and Dielectric Strength ......................... 9
Lifting the Sectionalizer........................................ 9
Mounting the Sectionalizer .................................. 9
Grounding the Sectionalizer ................................ 9
High-Voltage Connections ................................... 11
120 Vac Wiring.....................................................11
Internal Wiring...................................................... 12
Auxiliary Switch......................................................13
Operating Instructions ...........................................15
Initial Operation.................................................... 15
Routine Operation................................................ 15
Automatic Return to Zero Count ..........................15
One-Count-to-Open ............................................. 15
CT Protector Board ................................................15
Testing .....................................................................16
Test Circuit and Equipment..................................16
Pre-Test Procedure..............................................16
Test Procedures...................................................16
Post-Test Procedures ..........................................19
March 2002 • Supersedes 12/92
Printed in USA
Service Information
Sectionalizers
Type GV and GW Installation Instructions
S270-20-3
Applicable to serial numbers above 2265 for Type GV and 4803 for Type GW
NOTICE: This bulletin is also applicable to Kyle product serial numbers beginning with the prefix CP57.
Page 2
Type GV and GW Installation Instructions
2
The instructions in this manual are not intended as a substitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians, who are familiar with this equip­ment should install, operate, and service it.
A competent technician has these qualifications:
• Is thoroughly familiar with these instructions.
• Is trained in industry-accepted high- and low-voltage safe operating practices and procedures.
• Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment.
• Is trained in the care and use of protective equip­ment such as flash clothing, safety glasses, face shield, hard hat, rubber gloves, hotstick, etc.
Following is important safety information. For safe instal­lation and operation of this equipment, be sure to read and understand all cautions and warnings.
Safety Instructions
Following are general caution and warning statements that apply to this equipment. Additional statements, relat­ed to specific tasks and procedures, are located through­out the manual.
SAFETY INFORMATION
WARNING: This equipment is not intended to
protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply may result in death, severe personal injury and equipment damage.
G102.1
!
DANGER: Hazardous voltage. Contact with
hazardous voltage will cause death or severe
personal injury. Follow all locally approved safety pro­cedures when working around high- and low- voltage lines and equipment. G103.3
!
WARNING: Before installing, operating, main-
taining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage.
G101.0
!
SAFETY FOR LIFE
Cooper Power Systems products meet or exceed all applicable industry standards relating to product safety. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Cooper Power Systems employees involved in product design, manufacture, marketing, and service.
We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high voltage lines and equipment and support our “Safety For Life” mission.
This manual may contain four types of hazard statements:
DANGER: Indicates an imminently haz-
ardous situation which, if not avoided, will
result in death or serious injury.
WARNING: Indicates a potentially haz-
ardous situation which, if not avoided, could
result in death or serious injury.
CAUTION: Indicates a potentially haz-
ardous situation which, if not avoided, may
result in minor or moderate injury.
CAUTION: Indicates a potentially hazardous situ­ation which, if not avoided, may result in equip­ment damage only.
Hazard Statement Definitions
WARNING: Power distribution equipment must
be properly selected for the intended application. It must be installed and serviced by competent per­sonnel who have been trained and understand proper safety procedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Failure to properly select, install, or maintain power distribu­tion equipment can result in death, severe personal injury, and equipment damage.
G122.2
!
!
SAFETY
FOR LIFE
!
SAFETY
FOR LIFE
!
!
!
Page 3
3
!
Introduction
Service Information S270-20-3 provides installation and operation instructions for the Kyle Type GV and GW Sectionalizers. Before installing and operating this sec­tionalizer, carefully read and understand the contents of this manual.
Read this Manual First
Read and understand the contents of this manual and follow all locally approved procedures and safety prac­tices before installing or operating this equipment.
Additional Information
These instructions can not cover all details or variations in the equipment, procedures, or processes described nor provide directions for meeting every possible contin­gency during installation, operation, or maintenance. For additional information, please contact your Cooper Power Systems representative.
Acceptance and Initial Inspection
Each sectionalizer is completely assembled, tested, inspected, adjusted, and filled to the correct level with insulating oil at the factory. It is in good condition when accepted by the carrier for shipment.
Upon receipt, inspect the shipping container for signs of damage. Unpack the sectionalizer and inspect it thor­oughly for damage incurred during shipment. If damage is discovered, file a claim with the carrier immediately.
Check for oil leakage, and tighten all bolts that may have been loosened during shipment, especially the bolts attaching the head to the tank.
Handling and Storage
Be careful during handling and storage of the sectional­izer to minimize the possibility of damage. If the section­alizer is to be stored for any length of time prior to instal­lation, provide a clean, dry storage area. Locate the sec­tionalizer so as to minimize the possibility of mechanical damage. In particular, protect the bushings and keep the operator cabinet closed to protect the electronic control components.
Standards
Kyle sectionalizers are designed and tested in accor­dance with ANSI standard C37.63 where applicable.
Quality Standards
ISO 9001:2000 Certified Quality Management System
Description
The sectionalizer is a self-contained, circuit-opening device used in conjunction with source-side protective devices such as reclosers or circuit breakers, to auto­matically isolate faulted sections of electrical distribution systems. The sectionalizer senses current flow above a preset level, and, when the source-side protective device opens to de-energize the circuit, the sectionalizer counts the overcurrent interruption. Depending upon the coordination scheme, the sectionalizer will open during the first, second, and third open interval of the fault inter­rupting device to isolate permanent faults and confine outages to smaller sections of line.
The sectionalizer does not interrupt fault current but can be closed into a faulted line. It opens during the open interval of the backup device. For this reason, it must always be used in series with a fault-interrupting backup protective reclosing device. Also, it will reset counts that do not reach the counts-to-open setting within the selected reset time due to clearing of temporary faults.
A minimum of 0.5 A of load current flowing through the sectionalizer will block the generation of a count pulse. This count-restraint feature prevents the sectionalizer from counting overcurrents interrupted by down-line devices.
The sectionalizers are also equipped with an inrush-current restraint feature which distinguishes between inrush cur­rents and fault currents. If it is determined that the over­current through the sectionalizer is inrush current, the phase and ground current levels of the sectionalizer are blocked for a duration of 3 seconds upon current detection.
3
S270-20-3
PRODUCT INFORMATION
SAFETY
FOR LIFE
Page 4
Tables 1 and 2 show rating information for the Types GV and GW sectionalizers.
Type GV and GW Installation Instructions
4
Table 1 Basic Sectionalizer Ratings
Type GV Type GW
Nominal Voltage (kV) . . . . . . . . . . . . . . . . . . . . . 14.4 34.5
Rated Maximum Voltage (kV) . . . . . . . . . . . . . . . 15.5 38.0
Impulse Withstand
1.2 x 5.0 microsecond wave
BIL (kV) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110 150
60 Hz withstand
Dry, 1 minute (kV) . . . . . . . . . . . . . . . . . . . . 50 70
Wet, 10 seconds (kV) . . . . . . . . . . . . . . . . . 45 60
Continuous Current Rating (A) . . . . . . . . . . . . . . 400 400
Rated symmetrical
interrupting current (A rms) . . . . . . . . . . . . . 880 880
Rated making current,
asymmetrical (A rms) . . . . . . . . . . . . . . . . . 20000 15000
Short-time ratings (A rms)
10-seconds symmetrical . . . . . . . . . . . . . . . 4000 3500
1-second symmetrical . . . . . . . . . . . . . . . . . 12500 10000
Momentary maximum,
asymmetrical (A rms) . . . . . . . . . . . . . . . . . 20000 15000
Creepage distance,
standard bushing mm (in) . . . . . . . . . . . . . . 280 (11) 431 (17)
Table 2 Operating Data
Phase-minimum-
actuating current (A) . . . . . . . . 16, 24, 40, 56, 80, 112, 160, 224, 256, 296, 320, 448, 480, 640
Ground-minimum-
actuating current (A) . . . . . . . . 3.5, 7, 16, 20, 28, 40, 56, 80, 112, 160, 224, 320, 448, BLOCK
Number of counts to open . . . . . . . 1, 2, 3
Count reset (seconds) . . . . . . . . . . 15, 30, 60, 90, 120, 180
RATINGS
Page 5
5
!
Figures 2 and 3 show essential dimensional information for Types GV and GW sectionalizers, along with their weights and oil capacities.
Note: All dimensions are approximate and are given in mm
(inches).
5
S270-20-3
Figure 2. Type GW Sectionalizer.
Figure 3. Type GV Sectionalizer.
Weight with oil 350 kg (770 lb)
Oil Capacity 160 L (42 gal)
Weight with oil 213 kg (470 lb)
Oil Capacity 72 L (19 gal)
DIMENSIONS AND WEIGHT
SAFETY
FOR LIFE
1051 (41.5)
292
(11.5)
38 (1.5)
292
(11.5)
Vented dipstick
Tapped Holes (12) for 1/2–13 Bolts
Ground Connector
No. 8–No.2
233
(9.25)
89 (3.5)
435 (17)
Terminal Connectors
No. 6 solid–350 MCM
305 (12)
562 (22)
Lifting
lug
838 (33)
Ground
Connector
No. 8–No. 2
641
(25.25)
203
(8)
365 (14.5)
32 (1.25)
254 (10)
254
(10)
648 (25.5)
657 (25.75)
1016 (40)
929 (36.5)
254
(10)
1372 (54)
Vented dipstick
Terminal Connectors No. 6 solid–350 MCM
197
(7.75)
70
(2.75)
197
(7.75)
Hole for bolt 16 mm (5/8")
448
(17.5)
448
(17.5)
(2.5)
1203
(47.25)
329
(13)
435 (17)
64
260
324
362
(2.5)
473
(18.75)
365 (14.5)
152 (6)
244
(9.75)
311
64
(12.25)
(10.25)
(12.75)
(14.25)
Page 6
Manual Operating Controls
The operating controls for the sectionalizer are located on the underside of the operator mechanism housing, as shown in Figure 4.
Manual Opening
The hookstick-operated, manual opening pullring trips open the sectionalizer with one pull of the yellow pullring.
One-Count-To-Open Lever
The one-count-to-open lever provides the capability of opening the sectionalizer on the first overcurrent interrup­tion count. It provides for added safety during downline hot-line work without disturbing the normal counts-to­open setting of the sectionalizer. The hookstick-operated lever locks into position when pulled down, and must be manually reset to restore normal counts-to-lockout.
Manual Closing
The hookstick-operated, manual closing pullring closes the sectionalizer when the gray pullring is pulled down approximately 10 to 12 times. The pullring manually charges the closing springs and overtoggles the springs to initiate the closing. (When the sectionalizer closes, the resistance on the pullring is eliminated.) This is the only means of closing the sectionalizer.
Auxiliary Power
Auxiliary power (120 Vac, 25 VA, min.) is required for the cabinet heater and/or potential charging of the trip capacitor. The input receptacle is located on the underside of the operator cabinet (Figure 4). A mating connector plug is also provided with the unit.
Indicating Devices
A contact position indicator and an operations counter are located under the sleet hood of the operator cabinet.
The yellow contact position indicator is pinned to the main operating shaft of the sectionalizer to indicate the OPEN and CLOSED condition of the main contacts.
The operations counter gives a visual indication of the cumulative number of openings of the unit.
Type GV and GW Installation Instructions
6
Figure 4. Operating controls on the underside of the operator cabinet.
84575KMA
Provision for installing auxiliary switch wiring receptacles
Manual Opening Pullring
120 Vac input receptacle
(mating plug also furnished)
Manual closing
pullring
One-count-to-
open Lever
OPERATING CONTROLS AND SETTINGS
IMPORTANT: The potential charging board also includes a voltage restraint feature which prevents the unit from counting overcurrent interruptions unless the auxiliary voltage is also interrupted. Therefore, the auxiliary power must be obtained from the load side of the backup protective device so that the board is energized only when the backup is closed. Failure to follow this pre­caution will prevent proper operation of the sectionalizer.
WARNING: Do not rely on the open position of
the yellow operating handle; it does not ensure that the line has been de-energized. Always establish a visible disconnect. Failure to follow proper safety practices can result in contact with high voltage, which will cause death or severe personal injury. G116.0
WARNING: Always use a hotstick when work-
ing with this equipment. Failure to do so could result in contact with high voltage, which will cause death or severe personal injury. G108.1
!
!
Page 7
7
!
Settings
The operating characteristics are preset to customer specifications and tested prior to shipment from the fac­tory. However, if the sectionalizer is relocated or the coordination scheme is modified, the operating charac­teristics can be changed by the user. The settings should be checked before the unit is put into service. All settings are located on the printed circuit board in the operator mechanism cabinet and are accessible when the cabinet cover is removed. See Figure 6. To access the settings on an in-service sectionalizer, follow this procedure to remove the sectionalizer from service.
1. Close all three bypass switches (see Figure 5).
2. Pull down the yellow operating handle with a hot-
stick. The yellow operating handle is located under the sleet hood (see Figures 3 and 4).
3. Open the source and load disconnect switches (see Figure 5).
4. Remove the cabinet cover.
Minimum Actuating Current
The minimum actuating current levels for both phase and ground are determined by the selection of the prop­er plug-in resistors. (Normally, these settings are approx­imately 80% of the minimum trip settings of the backup protective device.)
NOTE: If the backup device is not equipped for ground fault
sensing and tripping, the ground current sensing cir­cuits of the sectionalizer can be deactivated by using a shorting resistor labeled BLOCK.
Phase current resistors are identified with the phase symbol (ø) and the actuating current value in amperes. Catalog numbers for the available phase current resis­tors are listed in Table 3.
Ground current resistors are identified with the ground sym­bol ( ) and the actuating current value in amperes. Catalog numbers for the available ground current resis­tors are listed in Table 4.
The minimum actuating current of the sectionalizer for both phase and ground can be changed by merely changing the appropriate plug-in resistor.
Label Value Resistance () Catalog
(A) Minimum Maximum Number
16 264 270 KA176GV16 24 172 176 KA176GV24 40 94.3 96.3 KA176GV40 56 66.3 67.7 KA176GV56 80 47 48 KA176GV80
112 32.6 33.4 KA176GV112
60 22.9 23.5 KA176GV160 224 16.3 16.7 KA176GV224 256 13.8 14.2 KA176GV256 296 11.9 12.3 KA176GV296 320 11.1 11.5 KA176GV320 448 8.1 8.3 KA176GV448 480 7.4 7.6 KA176GV480 640 5.5 5.7 KA176GV640
TABLE 3 Minimum Actuating Resistor (Phase)
Table 4 Minimum Actuating Resistor (Ground)
Label Value Resistance () Catalog
(A) Minimum Maximum Number
3.5 6.91 k 7.05 k KA177GV3.5 7 1.168 k 1.192 k KA177GV7
16 379.0 387.0 KA177GV16 20 298.0 304.0 KA177GV20 28 200.0 204.0 KA177GV28 40 135.6 138.4 KA177GV40 56 94.3 96.3 KA177GV56
80 66.3 67.7 KA177GV80 112 47.0 48.0 KA177GV112 160 32.6 33.4 KA177GV160 224 22.9 23.5 KA177GV224 320 15.8 16.2 KA177GV320 448 11.2 11.4 KA177GV448
BLOCK 0 0.1 KA177GVBLO
7
S270-20-3
CAUTION: Equipment Damage. The sectional-
izer must be bypassed and disconnected prior to changing minimum actuating resistor settings. Failure to comply will cause circuit board damage and may cause misoperation (unintentional operation) of the sectionalizer.
T277.0
Figure 5. Main Wiring Connections.
SAFETY
FOR LIFE
!
Bypass Switches
Disconnect
Switches
Surge
Arrestor
120 Vac Input
Disconnect
Switches
SECTIONALIZER
Operator
Cabinet
Surge
Arrester
Page 8
Counts-to-Open
The counts-to-open setting is determined by the position of the COUNTS-TO-OPEN SELECTOR switch. Switch positions 1, 2, and 3 correspond to 1, 2, or 3 counts to open. Normally, this setting is one less than the number of operations to lockout of the backup protective device. To change the number of counts-to-open setting, merely change the position of the rotary switch.
Count Reset
The reset setting is determined by the position of the COUNT RESET switch. Reset times of 15, 30, 60, 90, 120, and 180 seconds are available. This feature resets to zero any accumulated counts whenever current through the sectionalizer flows without interruption for longer than the time programmed.
The reset feature will operate with any current flow from minimum load (0.5 A) to values below phase or ground pickup levels.
Inrush-Current Restraint
The inrush-current restraint feature blocks the phase and ground actuating levels for three seconds after cur­rent flow through the sectionalizer is restored and the overcurrent has been determined to be inrush current.
The three second time interval allows for system inrush parameters to stabilize prior to allowing the sensitivity of the sectionalizer to return to its programmed state.
Response Time
For backfed motor contribution and unsymmetrical clear­ing of upline faults, a response time is built into the sec­tionalizer control to eliminate unwanted counting of these situations. Upon detection of any current above the phase or ground actuating setting, the current must exceed the response-time characteristics as illustrated in Figure 7. Total clearing time of reclosers and breakers must exceed the response-time characteristic of the sec­tionalizer.
Type GV and GW Installation Instructions
8
Figure 7. Maximum Response-Time Characteristics.
Figure 6. Operating characteristics of the sectionalizer are pro­grammed on the printed circuit board in the operator cabinet.
020061KMA
Counts­to-open selector
Count reset selector
Test Point
C
Test Point
D
0.1
.08
.06
.05
.04
.03
TIME (sec)
.02
.01
50
80
60
100
CURRENT (percent of minimum actuating current)
200
500
400
600
800
1000
2000
300
Page 9
9
!
Oil Level and Dielectric Strength
Make sure the oil in the tank is at the proper level by checking the vented dipstick in the head casting. Replenish any loss with new, dry transformer oil. Refer to Figures 2 and 3.
If the switch has been stored for any length of time or is being relocated, check the dielectric strength of the oil in accordance with ASTM-approved testing procedures. Physical properties of the oil used in Kyle®distribution switchgear is found in Reference Data R280-90-1.
1. In new equipment, the oil must have a minimum
dielectric strength of 26 kV. If less than 26 kV, filter the oil to restore its dielectric strength to an accept­able level.
2. If the equipment has been in service and is being
relocated, the minimum dielectric strength of the oil must be at least 22 kV. If less than 22 kV, or if the oil is contaminated with carbon or sludge, replace the oil.
3. Check that the actual settings agree with the section-
alizer nameplate and are correct for the planned installation.
Lifting the Sectionalizer
Follow all approved safety practices when making hitch­es and lifting the equipment. Lift the load smoothly, and do not allow the load to shift.
This unit has two lifting lugs. Both lugs must be used when lifting. Maximum strength is attained with a verti­cal lift attached to the lugs. Use a spreader bar with a fixed attachment point for the hook at the load center.
If a sling is used, it must have a fixed attachment point at the load center. Rig the load so that the sling height is equal to or greater than the distance between lifting lugs. See Figure 8.
Mounting the Sectionalizer
Figures 9 and 10 show installation using Kyle mounting frames. If other mounting means are used, support the GV sectionalizer at the four 5/8 inch bolt holes in the mounting rails on the tank. The GW sectionalizer is sup­ported at the twelve 1/2-13 threaded holes tapped into the sides of the head casting.
Grounding the Sectionalizer
Make ground connections to the sectionalizer. Refer to Figures 2 and 3.
9
S270-20-3
Figure 8. Lifting the sectionalizer.
INSTALLATION
WARNING: Do not operate this equipment out
of oil. Oil is the electrical insulating medium with­in this equipment; operating out of oil will result in internal flashovers that will damage the equipment and can cause death or severe personal injury.
G104.2
CAUTION: This equipment relies on oil to pro-
vide electrical insulation between components.
The dielectric strength of the oil must be checked on a regular basis, as part of the routine maintenance inspection, to ensure that it is at or above minimum dielectric requirements. Use of this equipment with insulating oil that does not meet minimum require­ments can result in internal flashovers that will dam­age the equipment and can cause personal injury. G107.2
CAUTION: Follow all locally approved safety prac­tices when lifting and mounting the equipment. Use the lifting lugs provided. Lift the unit smoothly and do not allow the unit to shift. Improper lifting can result in equipment damage.
G106.2
WARNING: Hazardous Voltage. Solidly ground all equipment. Failure to comply can result in
death, severe personal injury, and equipment damage.
T223.2
SAFETY
FOR LIFE
!
!
Sling Height
Distance Between
Lugs
!
Page 10
Type GV and GW Installation Instructions
10
Figure 10. Mounting hardware for Type GV sectionalizer.
Figure 9. Type GW sectionalizer in the KA146W3 pole-mounting hanger.
Grounding Lug (two 2/0–250 MCM)
Lifting Holes
Mounting Holes for 3/4 Bolts (Bolts not furnished)
978 mm
546 mm
(21.5")
(38.5")
292 mm
(11.5")
330 mm
(13")
32 mm
622 mm
(1.25")
(24.5")
1346 mm
(53")
289 mm
(11.5")
289 mm
(11.5")
537 mm (21.25")
508 mm
(20")
330 mm
(13")
(30")
362
(14.25)
762
244 mm
(9.75")
324 mm (12.75")
383 mm
(15")
711
(28")
5/8" Bolts (4) (not furnished)
432 mm
(17")
489 mm (19.25")
(26.5)
473 mm
(18.5")
378 mm
(14.5")
670
654
(25.75)
244 mm
(9.5")
324 mm (12.75")
699 mm
(27.5")
383 mm (15.25")
Holes for 3/4" bolts
622 mm
(24.5")
KA19H3 Crossarm Hanger
Adjustable for 3 1/4 x 4 1/4 to 4 x 5 crossarms and 1/2 to 4" channels.
KA116H3 Broadside Pole Hanger
Page 11
11
!
High-Voltage Connections
It is desirable to provide the sectionalizer with switches and protection as shown in Figure 11. Surge protection on both sides of the sectionalizer is recommended. However, if provided on only one side, it should be on the source side. In substations, surge protection should be provided on the load side of the sectionalizer.
The universal clamp-type terminals used for main line con­nections accept No. 2 solid through 350 mcm copper or aluminum cables.
The parallel connector grounding clamp on the tank of the Type GV and the cover of the GW sectionalizers will accept No. 8 through No. 2 stranded wire.
120 Vac Wiring
A 120 Vac source voltage is required if the mechanism cabinet heater and the potential charger for the trip capacitor are to be energized.
The line voltage is connected to pins B and D of the source-voltage plug shown in Figure 12.
Internal Wiring
A connection diagram for the GV and GW sectionalizers is shown in Figures 12 and13.
11
S270-20-3
Figure 11. Main Wiring Connections.
Figure 12. 125 Vac Input Connector Plug.
Keyway
Socket Insert
Socket E
Max wire size No. 12 AWG
Rubber Grommet accommodates 3/8 to 1/2 dia. cable
SAFETY
FOR LIFE
Bypass Switches
Disconnect
Switches
Surge
Arrestor
120 Vac Input
Disconnect
Switches
SECTIONALIZER
Operator
Cabinet
Surge
Arrester
E
A
B
D
C
Page 12
Type GV and GW Installation Instructions
12
Figure 13. Internal Connections Diagram.
14
15
16
17
18
19
20
21
22
BLK
øC
WHT
BLK
øB
WHT
BLK
RED
Bushing
Current
Transfomer
BLK
YEL
WHT
BLK
WHT
BLK
øA
E
F
YEL
Zenar Diode
Zenar
RED
Diode
RED
1
RED
2
BLK
3
4
7
8
KEY
RED YEL
+
Low-Energy Tripper
RED
G
H
RED
G
WHT
YEL
YEL
C
A
BLK
A
H
C
F
E
WHT
BLK
WHT
BLK BLK
BLK
ORG
BRO
C.T.
Protector
G
C
B
G
BLK
C
B
BLU
GRN
A
A
BLU
GRN
BLK
BLU
BLK
BLU
BLK
NC
NO
NC
C
NO
Count
C
Reset Switch
Input Receptacle
One­Count Switch
120 Vac
WHT
BLK
D
B
Heater
WHT
BLK
Potential
Charger
Board
WHT BLK
BLK
WHT
BLK
A B
C
D
E
F
Arrester
3 4
ORG
YEL
GRN
WHT
Surge
2 1
Page 13
13
!
Auxiliary Switch (KA46GV3)
The auxiliary switch, mounted to the top of the operator cabinet, in a weather-proof housing, is used for relaying or interlocking schemes and remote contact indication.
A three-stage auxiliary switch is provided. Each stage consists of two independent contact assemblies with either “a” (normally open) or “b” (normally closed) con­tacts which can be easily changed in the field. A data plate attached to the switch cover shows the switch arrangement. Related switch contact positions are shown in Table 5.
The switch is permanently wired to two multipin recepta­cles in the bottom of the operator cabinet. Table 6 shows the pin arrangement of the the mating plug shown in Figure 14.
The switch contacts are insulated for 600 V and have a continuous current rating of 10 A. Their interrupting rat­ings are shown in Table 7.
Switching positions can be changed from “a” or “b” oper­ation by repositioning the cams inside each switch sec­tion. To change any cam position, complete the following:
1. Remove the auxiliary switch cover.
2. Detach the switch from the switch link by removing
the groove pin and C-rings.
3. Remove the machine screws attaching the assembly to the cabinet.
4. With the switch removed, unfasten the two hex nuts and lockwashers from the long machine screws that hold the switch sections together.
5. Starting with the rear switch section, lift the cams off the operating shaft, replacing the cams in one of the positions shown in Figure 15.
6. Reposition the switch sections together, reassemble the auxiliary switch, and remount the switch on the sectionalizer.
13
S270-20-3
When Sectionalizer Contacts Are Closed Open
Auxiliary “a” contacts are Closed Open
Auxiliary “b” contacts are Open Closed
Table 5 Related Switch Contact Positions
Figure 14. Auxiliary Switch Connector Plug.
Rubber grommet accommodates 0.750 to 0.812
O.D. Cable No. 12 AWG Max Conductor size
Pin G
Keyway
Pin insert
Table 6 Switch Leads to Receptacle Terminals
Switch Stages Switch Receptacle Switch
Terminal Pin Contact
1A
b
Stage 1 2B
3C
a Rear
4D
5E Receptacle
b
Stage 2 6F
7G
a
8H
9A
b
Stage 3 10 B Front
11 C Receptacle
a
12 D
Table 7 Interrupting Ratings - Switch Contacts
Inductive Non-Inductive Inductive Non-Inductive
Volts ac ac dc dc
(A) (A) (A) (A)
24 dc —— 15 20 48 dc —— 7.5 10 120 ac 60 80 —— 125 dc —— 1.5 2 240 ac 30 60 —— 250 dc ——0.45 0.5
SAFETY
FOR LIFE
F
E
D
G
A
H
B
C
Page 14
Type GV and GW Installation Instructions
14
Figure 15. Cam positions inside the Auxiliary Switch.
CONTACT SECTION
END PLATE AND GASKET
When assembling be sure that the roll pin hole and punch mark on the shaft are in vertical plane with the punch mark in the end plate (as shown).
CAMS
TERMINALS 3, 7, 11, 15
TERMINALS 1, 5, 9, 13
CONTACTS
SQUARE SHAFT
TERMINALS 2, 6, 10, 14
CAM POSITION NO. 1
TERMINALS 4, 8, 12, 16
Both contacts closed.
SQUARE SHAFT
CAMS
CLOSED
POSITION
CAM POSITION NO. 2
Both contacts open.
45°
OPEN
POSITION
CAM POSITION NO. 3 One contact open and one contact closed.
Page 15
15
!
Initial Operation
With the sectionalizer connected into the system and the source-side high-voltage lines energized, the sectional­izer can be placed into service. Follow approved local practices, which may involve closing the line disconnect switches, closing the sectionalizer, and then opening the bypass circuit.
Routine Operation
Under normal operating conditions, the sectionalizer counts overcurrent interruptions of the backup protective device and automatically opens if the counts registered exceed the control setting. Once open, the sectionalizer will remain open until manually closed. In addition, the sectionalizer can be opened manually by one operation of the yellow pullring of the manual trip rod.
To close the sectionalizer, after either a manual or auto­matic trip, the gray manual-closing pullring must be oper­ated approximately 10 to 12 times. (When the sectional­izer closes, the resistance on the pullring is eliminated.) This is the only means of closing the sectionalizer.
Automatic Return to Zero Count
A switch operated by the tripping linkage of the section­alizer mechanism will automatically erase any accumu­lated counts every time the sectionalizer opens either man­ually or automatically.
One-Count-to-Open
As an added safety precaution during downline hot-line work, the sectionalizer can be programmed for one­count-to-open without opening the operator mechanism housing and disturbing the normal operating settings. The one-count-to-open lever overrides the COUNTS­TO-OPEN SELECTOR switch to provide the capability of opening the sectionalizer on the first overcurrent inter­ruption. The hookstick-operated lever locks into position when pulled down and must be manually reset.
CT PROTECTOR BOARD
Should the control be removed, the CT protector board, shown in Figure 16, will automatically protect the current sensing CTs. This is done by limiting the open-circuit voltages to non-destructive levels.
15
S270-20-3
OPERATING INSTRUCTIONS
Figure 16. Control Circuitry.
84577KMA
CT Protector Board
Voltage Charging Board
Heater
WARNING: This equipment is not intended to
protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply can result in death, severe personal injury, and equipment dam­age. G102.1
WARNING: Do not rely on the open position of
the yellow operating handle; it does not ensure that the line has been de-energized. Always establish a visible disconnect. Failure to follow proper safety practices can result in contact with high voltage, which will cause death or severe personal injury. G116.0
WARNING: Always use a hotstick when work-
ing with this equipment. Failure to do so could result in contact with high voltage, which will cause death or severe personal injury. G108.1
SAFETY
FOR LIFE
!
!
!
Page 16
Type GV and GW sectionalizers are carefully tested at the factory prior to shipment. Well-equipped test facili­ties, a detailed testing procedure, and trained test per­sonnel assure that the unit will operate according to pub­lished data. Permanent records are kept of each sec­tionalizers test performance.
Each sectionalizer leaves the factory ready for installa­tion. Preinstallation testing is not necessary. However, should verification of operation prior to installation be desired, the these procedures should be used.
Test Circuit Equipment
A suggested test circuit is shown in Figure 17. In this test setup, the test current is obtained by back-feeding a 500:5 A current transformer (T2, located in the primary loop of one phase of the sectionalizer) from an adjustable 120 Vac source. The ammeter scales (A) should be selected to accommodate the appropriate range of test currents.
Pre-Test Procedure
Before performing any of the test procedures that follow, make sure the 120 Vac power to the heater and voltage charging board (Figure 15) is disconnected to disable the voltage restraint feature. The sectionalizer will not count as long as the voltage restraint feature (part of the voltage charging board) is energized.
Test Procedures
While performing the following tests, monitor the conti­nuity between test points C and D on the circuit board. (see Figure 6). If no continuity exists between either set of test points upon closing of the sectionalizer, apply 6 A of load current by closing switch S1 for 3.5 seconds. Once continuity has been restored, open S1 and pro­ceed with the test procedures.
Minimum Actuating Current
The minimum actuating current can be verified by test­ing at the ± 10 percent values of the phase and ground actuating current ratings.
For example, the minimum actuating resistor rated at 80 A is tested at 72 A (no count) and at 88 A (count regis­tered).
Type GV and GW Installation Instructions
16
Figure 17. Test Circuit Schematic.
TESTING
WARNING: This equipment is not intended to
protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply can result in death, severe personal injury, and equipment dam­age. G102.1
WARNING: The switchgear and high voltage
transformer must be in a test cage or similar pro­tective device to prevent accidental contact with the high voltage parts. Solidly ground all equipment. Failure to comply can result in death, severe personal injury, and equipment damage. T221.3
!
!
120 V
AC Source
T1– VARIABLE AUTO TRANSFORMER T2– 500:5 CURRENT TRANSFORMER S1– SPST TOGGLE SWITCH S2– SPST PUSHBUTTON SWITCH R1– DROPPING RESISTOR, 2 k-10 W A – AMMETER
60 Hz
T1
A
R
S1
S2
T2
Page 17
Phase Minimum Actuating Current
When checking the phase minimum actuating current, the ground fault sensing portion of the sectionalizer must be disabled. Testing an individual phase without disabling the ground sensing circuits will cause a false count.
The following procedure is used:
1. Jumper the ground actuating current resistor with a short lead to disable the ground sensing circuit.
2. Jumper terminals P and D together.
3. Program the sectionalizer for one-count-to-open by
setting the COUNTS-TO-OPEN SELECTOR switch to 1.
4. Close the sectionalizer by operating the close pull­ring the required number of times.
5. With the test circuit connected to phase A of the sec­tionalizer and S1 open, hold S2 closed and slowly raise the test current from zero to the appropriate value shown in Column A of Table 8. Hold S2 closed for at least three seconds.
6. Release S2 to simulate a backup opening. The sec­tionalizer should not open.
7. Close S2 and adjust the test current to the appropri­ate value shown in Column B of Table 8.
8. Release S2 to simulate a backup opening. The sec­tionalizer should count the overcurrent interruption and open.
9. Repeat steps 3 through 7 for phases B and C.
10. Remove the jumper from terminals P and D.
11. Remove the jumper from across the ground actuat-
ing current resistor upon completion of this portion of the test.
Ground Minimum Actuating Current
To prevent the possibility of a false count, the phase sensing portion of the sectionalizer control circuit should be disabled when the ground minimum actuating current is being checked. The following procedure is used:
1. Jumper the phase actuating current resistor with a short lead to disable the phase sensing circuit.
2. Jumper terminals P and D together.
3. Check that the sectionalizer control is set for one-
count-to-open.
4. Close the sectionalizer by operating the close pull­ring the required number of times.
5. With the test circuit connected to phase A of the sec­tionalizer and S1 open, hold S2 closed and slowly raise the test current from zero to the appropriate values shown in Column A of Table 8. Hold S2 closed for at least three seconds.
6. Release S2 and simulate a backup opening. The sectionalizer should not open.
7. Close S2 and adjust the test current to the appro­priate value shown in Column B of Table 8.
8. Release S2 to simulate a backup opening. The sec­tionalizer should count the overcurrent interruption and open.
9. Repeat steps 3 through 7 for Phases B and C.
10. Remove the jumper from terminals P and D.
11. Remove the jumper from across the phase actuat-
ing current resistor.
17
S270-20-3
!
Table 8 Test Circuit Operating Limits for Actuating Current Settings
Column A Column B
Actuating Sectionalizer Must Sectionalizer Must
Current Setting Not Count Below Count At
(A) (A) (A)
3.5 3 4 7 6.3 7.7 16 14.4 17.6 20 18 22 24 21.6 26.4 28 25.2 30.8 40 36 44 56 50.4 61.6 80 72 88 112 101 124 160 144 176 224 201 247 256 230 282 296 266 326 320 288 352 448 403 483 480 432 528 640 576 704
SAFETY
FOR LIFE
Page 18
Count Restraint
The count restraint feature prevents erroneous counts of overcurrents interrupted by downline protective devices by blocking the counting operation as long as a mini­mum of 0.5 A of uninterrupted line current flows through the sectionalizer.
The operation of the count restraint can be verified by superimposing an interruptible overcurrent on a constant minimum line current. The sectionalizer will not count or open on the interruption of the overcurrent as long as the minimum line current is not interrupted. To check the count restraint feature, proceed as follows:
1. Jumper the ground actuating current resistor with a short lead to disable the ground sensing circuit.
2. Jumper terminals P and D together.
3. Check that the sectionalizer control is set for one-
count-to-open.
4. Close the sectionalizer by operating the close pullring the required number of times.
5. With the test circuit connected to phase A of the sec­tionalizer and S1 closed (to simulate a constant load current of approximately 6 A), hold S2 closed and raise the test current to slightly above the appropriate values shown in Column B of Table 8. Hold S2 closed for at least three seconds
6. Release S2 to simulate a downline device clearing the overcurrent. The sectionalizer should not open verify­ing the operation of the count restraint feature.
7. Open S1 and again close and adjust S2 to simulate a backup device clearing the fault. This time the section­alizer should count the overcurrent interruption and open.
8. Remove the jumper from terminals P and D.
Voltage Restraint
When energized at 120 Vac, the voltage charging board provides fast charging times for the trip energy storage capacitors. It also acts as a voltage restraint; the sectional­izer will not count an overcurrent interruption of the protec­tive device unless the voltage at the control is also inter­rupted. To check the voltage restraint feature, proceed as follows:
1. Jumper the ground actuating resistor with a short lead to disable the ground sensing circuit.
2. Jumper terminals P and D together.
3. Program the sectionalizer for one-count-to-open.
4. Close the sectionalizer.
5. Connect 120 Vac across pins B and D of the 120 Vac
input receptacle.
6. With the test circuit connected to Phase A of the sec­tionalizer and S1 open, Close S2 and raise the current slightly above the appropriate value shown in Column B of Table 8. Hold S2 closed for at least three sec­onds.
7. Release S2 to simulate a downline device clearing the overcurrent. The sectionalizer should not open.
8. Disconnect the 120 Vac from the input receptacle.
9. Again close and release S2. The sectionalizer should
open.
10. Remove the jumper from terminals P and D.
Number of Counts-to-Open
The number of counts-to-open can be verified by inter­rupting, the preset number of times, an overcurrent through the sectionalizer. For example, with the control set for three counts, the sectionalizer will open upon the third overcurrent interruption. Proceed as follows:
1. Jumper the ground actuating current resistor with a short lead to disable the ground sensing circuit.
2. Jumper terminals P and D together.
3. Program the sectionalizer for three counts-to-open by setting the COUNTS-TO-OPEN SELECTOR switch to 3.
4. Close the sectionalizer by operating the close pullring
the required number of times.
5. With the test circuit connected to phase A of the sec­tionalizer and S1 open, close S2 and raise the test cur­rent to slightly above the appropriate value shown in Column B of Table 8. Hold S2 closed for at least three seconds.
6. Open and close S2 a number of times. The sectionaliz­er should open upon the third opening of S2.
7. To verify the two-counts-to-open setting, set the COUNTS-TO-OPEN SELECTOR switch to 2 and repeat steps 3 through 5. The sectionalizer should open upon the second opening of S2.
8. Remove the jumper from terminals P and D.
Type GV and GW Installation Instructions
18
Page 19
Count Reset
The count reset feature resets the sectionalizer count to zero whenever current below the actuating level flows through the sectionalizer for longer than the pro­grammed reset time without interruption. The reset time settings have a tolerance of ±10 percent.
It can be verified by interrupting an overcurrent flow through the sectionalizer one time less than the counts­to-open setting, then allowing load current to flow for periods just under and just over the reset setting. The sectionalizer should open if the overcurrent for the final count is interrupted within the reset time period (count has reset to zero). The following procedures may be used to verify the count reset:
1. Jumper the ground actuating current resistor with a short lead to disable the ground-sensing circuit.
2. Program the sectionalizer control for two counts-to­open and set the COUNT RESET SELECTOR to 15 seconds.
3. Jumper terminals P and D together.
4. Close the sectionalizer.
5. With test circuit connected to phase A of the section-
alizer and S1 open, close S2 and raise the test cur­rent to slightly above the appropriate value shown in Column B of Table 8. Hold S2 closed for at least three seconds.
6. Release S2 to simulate a backup protective device clearing the overcurrent. The sectionalizer will regis­ter a count.
7. Close S1 for 13.5 seconds.
8. Momentarily close and then release switch S2. The
sectionalizer should open, verifying that the count reset has not been activated.
9. Reclose the sectionalizer and then close and release S2 once to register one overcurrent interruption count.
10. Close S1 for slightly more than 16.5 seconds.
11. Momentarily close and release switch S2. The sec-
tionalizer should not open, verifying that the count reset has been activated and the first count has been erased.
12. Again, close and release S2. The sectionalizer should open.
13. Remove the jumper form terminals P and D.
Inrush-Current Restraint
The inrush-current restraint feature distinguishes between fault currents and inrush currents. For fault cur­rent interruptions, the sectionalizer counts and opens normally. For an inrush-current condition, the phase and ground minimum actuating current detection is blocked for three seconds to prevent counting the inrush current.
The three-second time interval allows for system inrush parameters to stabilize prior to allowing the sensitivity of the sectionalizer to return to its programmed state.
The operation of the inrush-current restraint can be veri­fied by simulating a fault condition (the overcurrent is preceded by an overcurrent interruption) and an inrush condition (the overcurrent is preceded by a load current interruption).
The following procedure can be used to verify the inrush-current restraint feature.
1. Jumper the ground actuating current resistor with a short lead to disable the ground sensing circuit.
2. Set the COUNTS TO OPEN SELECTOR switch to 1.
3. Manually close the sectionalizer.
4. With the test circuit connected to phase A of the sec-
tionalizer and S1 open, hold S2 closed and raise the test current to slightly below the appropriate value shown in Column A of Table 8.
5. Release S2 to simulate a backup opening with only load current flowing through the sectionalizer when current was interrupted. The sectionalizer should
not open.
6. Close S2 and in no more than three seconds
adjust the test current to just below twice the appro­priate value shown in Column A of Table 8 to simu­late an inrush condition. Release S2. The sectional­izer should not open, verifying that the inrush restraint feature has been activated.
7. Reset the inrush restraint as follows:
A. Short test terminals D and P together.
B. Close S1 closed for 3.5 seconds.
C. Open S1 and remove short from Test Terminals D
and P.
8. Close S2 and raise the test current to slightly above the appropriate value shown in Column B of Table 8.
9. Release S2 to simulate a backup opening with fault current flowing through the sectionalizer when cur­rent was interrupted. The sectionalizer should open.
10. Close the sectionalizer.
11. Repeat step 9 to simulate a fault condition.
12. Release S2. The sectionalizer should open verifying
that the inrush restraint has not been activated.
Post-Test Procedures
After testing has been completed, make sure that the control settings are programmed to the operating param­eters as originally specified.
19
S270-20-3
!
SAFETY
FOR LIFE
Page 20
1045 Hickory Street Pewaukee, WI 53072 USA www.cooperpower.com
© 2005 Cooper Power Systems or its affiliates. Kyle®is a registered trademark of Cooper Power Systems or its affiliates..
KA2048-101 Rev: 01
!
SAFETY
FOR LIFE
KDL
6/05
Loading...