Cooper Power Systems 900X User Guide

EkaNet™ Har dwar e Manual
Document Number
10156
Revision 04
Eka Systems, Inc.
20251 Century Boulevard, Suite 120
Tel (301) 990-3450
Fax (301) 990-3451
EKA CONFIDENTIAL
Confidential and Proprietary
Reproduction or Distribution Prohibited
This document is for informational purposes only. It contains information that is confidential and proprietary. This document has been prepared by and is the property of Eka Systems, Inc. By accepting and reviewing this document, you agree that you will treat its contents as confidential and proprietary, and that you will not copy, distribute or otherwise disclose the information contained herein to third parties.

Table of Contents

Table of Contents
1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 - 1
1.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 - 1
1.1.1 Product Highlights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 - 1
1.2 Supporting Documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 - 2
1.3 Version History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 - 2
2. ECR-2400 Node Hardware. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 1
2.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 1
2.1.1 ECR-2400 Node Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 1
2.1.2 ECR-2400 Node Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 2
2.2 Installation and Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 3
2.2.1 What the Blinking Lights Mean . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 3
2.2.1.1 The Green LED. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 3
2.2.1.2 The Red LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 3
2.3 ECR-2400 Node Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - 4
3. Elster A3/Alpha Plus Node Hardware. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 1
3.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 1
3.1.1 Elster A3/Alpha Plus Node Features . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 2
3.1.2 Elster A3/Alpha Plus Node Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 2
3.2 Installation and Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 3
3.2.1 What the Blinking Lights Mean . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 4
3.2.1.1 The Green LED. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 4
3.2.1.2 The Red LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 4
3.3 Elster A3/Alpha Plus Node Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 4
4. RESI-MON Node Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 1
4.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 2
4.1.1 RESI-MON Node Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 2
4.1.2 RESI-MON Node Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 3
4.2 Installation and Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 4
4.2.1 What the Blinking Lights Mean . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 4
4.2.1.1 The Green LED. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 4
4.2.1.2 The Red LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 4
4.3 RESI-MON Node Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 - 5
5. Gateway Hardware. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 1
5.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 1
5.1.1 EkaNet Gateway Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 1
EkaNet Hardware Manual 10156-04
Eka Proprietary and Confidential
Table of Contents
5.2 Configuring the Gateway Using the Field Tool . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 1
5.3 The Compact Flash Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 5
5.4 Installing an Indoor Gateway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 6
5.5 Installing an Outdoor Gateway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 8
5.6 Verifying Gateway Connectivity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 11
5.7 Gateway Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 12
5.2.1 IP Config Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 2
5.2.2 User Config Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 3
5.2.3 NTP Config Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 - 5
10156-04 EkaNet Hardware Manual
Eka Proprietary and Confidential

List of Figures

Figure 1.1: The Architecture of the EkaNet Wireless Mesh Network System ............ 1 - 1
Figure 2.1: ECR-2400 Node .......................................................................................2 - 1
Figure 2.2: ECR-2400 Node Layout ........................................................................... 2 - 2
Figure 2.3: Eka Node Placement within a ECR-2400 Meter ...................................... 2 - 3
Figure 3.1: Elster A3/Alpha Plus Node - Top View .................................................... 3 - 1
Figure 3.2: Elster A3/Alpha Plus Node - Side View ................................................... 3 - 1
Figure 3.3: Elster A3/Alpha Plus Node Layout ........................................................... 3 - 2
Figure 3.4: Eka Node Placement within an Alpha Meter ............................................ 3 - 3
Figure 4.1: RESI-MON Node ..................................................................................... 4 - 2
Figure 4.2: RESI-MON Node Layout .......................................................................... 4 - 3
Figure 5.1: Gateway Maintenance IP Configuration .................................................. 5 - 2
Figure 5.2: Gateway Maintenance User Configuration .............................................. 5 - 3
Figure 5.3: Successful Update to User Information ................................................... 5 - 4
Figure 5.4: Gateway Maintenance NTP Configuration ............................................... 5 - 5
Figure 5.5: Indoor Gateway ........................................................................................ 5 - 6
Figure 5.6: Indoor Gateway - Power Connection ....................................................... 5 - 7
Figure 5.7: Indoor Gateway - Cover Removed .......................................................... 5 - 7
Figure 5.8: Weather Proof Outdoor EkaNet Gateway - Closed ................................. 5 - 8
Figure 5.9: Weather-Proof Outdoor Gateway - Latches ............................................. 5 - 9
Figure 5.10: Internal Components of an Outdoor Gateway ....................................... 5 - 10
Figure 5.11: Power Input Terminals on an Outdoor Gateway .................................... 5 - 11
List of Figures
EkaNet Hardware Manual 10156-04
Eka Proprietary and Confidential

1. Introduction

1.1 Overview

1.1.1 Product Highlights

EkaNet™ Har dwar e Manual
This document describes the node and gateway hardware components of an EkaNet wireless mesh network
EkaNet’s wireless mesh network consists of multiple nodes communicating via a gateway with a server through either an IP connection or phone modem. In this self-configuring, peer-to-peer, multi-hop network, data is intelligently routed between nodes and gateways in the most efficient manner. Figure 1.1 shows the components of an EkaNet wireless mesh network including those supplied by the customer. This do cument describes the node and gateway hardwar e that make up the EkaNet wireless mesh network.
Figure 1.1 The Architecture of the EkaNet Wireless Mesh Network System
10156-04 1 - 1 EkaNet Hardware Manual
Eka Proprietary and Confidential
Introduction

1.2 Supporting Documents

The following documents contain supporting details on the operation of your EkaNet wireless mesh network:

1.3 Version History

EkaNet System Description — describes the system features of EkaNet’s wireless mesh network for embedded device networking applications
EkaNet Operations Manual describes the procedures to plan, deploy, and maintain your EkaNet wireless mesh network
EkaNet Field Tool User Manual — describes the features and use of the EkaNet Field tools
Network Manager User Guide — describes the use of the Network Manager software. Includes sizing, installation, and administration information.
Revision
Number
01 September 2005 Initial Version - 10156 02 March 2006 Added RESI-MON Node (See “RESI-MON
03 May 2006 Updated Gateway section with instructions on
04 July 2006 Updated Radio Specifications (See “Radio
Date Released Comment
Node Hardware” on page 4 - 1), Elster Node (See “Elster A3/Alpha Plus Node Hardware” on page 3 - 1) sections.
gateway configuration (See “Configuring the Gateway Using the Field Tool” on page 5 - 1).
Specifications” on page 2-4.) Add ed FCC Warning (See “Warning” on page 4-1.)
This document was prepared by: Eka Systems, Inc. Germantown, MD © Eka Systems, Inc., 2006
EkaNet Hardware Manual 1 - 2 10156-04
Eka Proprietary and Confidential
ECR-2400 Node Hardware

2. ECR-2400 Node Hardware

2.1 Overview

The ECR-2400 node is an under-the-glass board designed for installation in an ECR-2400 meter. The node plugs into the meter and provides an easy and reliable way to enable meters to automatically form a wireless mesh network. This section describes the procedures to integrate an ECR-2400 node with a
ECR-2400 meter.
Figure 2.1 ECR-2400 Node

2.1.1 ECR-2400 Node Features

ECR-2400 nodes:
operate in the 2.4 GHz band
fit “under the glass”
performs automatic time synchronization
provide real-time access to interval data
contain local non-volatile data storage
provide full wireless routing capability
10156-04 2 - 1 EkaNet Hardware Manual
Eka Proprietary and Confidential
ECR-2400 Node Hardware

2.1.2 ECR-2400 Node Layout

Figure 2.2 below is a simple diagram of an ECR-2400 node. The primary components of the node are:
the meter interface connector - connects the node to the meter
the AC power connection - supplies power to the node
the node’s serial number - the node’s unique identifier
LEDs - red and green lights displaying node’s operating status
Meter Interface
Connector
LED S t atus Light s
AC Power Connector
Bar C ode and label contain t he node’s
radio address and
serial number .
These num bers are also em bedded in the node’s s of tware .
Antenna
Figure 2.2 ECR-2400 Node Layout
Each ECR-2400 node is uniquely identified with a serial number . This number is displayed on the label and is contained on th e bar code. In addition, the number is also embedded in the node’s software. This serial number is the number displayed on the Field Tool and Network Manager to identify the node.
During installation, it is important to note the Eka Serial Numb er and the serial number of the meter in which it is installed in the event that the node and/or meter require troubleshooting.
EkaNet Hardware Manual 2 - 2 10156-04
Eka Proprietary and Confidential
ECR-2400 Node Hardware

2.2 Installation and Operation

Install the ECR-2400 node in the ECR-2400 meter as shown in Figure 2.3.
Front Face Plate
EC R-2400 Meter Board
EC R-2400 N ode
Antenna
AC Power Connector
LED Stat us Light s
Meter Interface
Connector
Figure 2.3 Eka Node Placement within a ECR-2400 Meter
1. Connect the ECR-2400 Meter Board to the Meter Interface Connector on the ECR-2400 Node.
2. Connect the AC power connector on the ECR-2400 node to the line and neutral connectors on the base of the ECR-2400 meter.
As soon as the meter is installed and powered on, the ECR-2400 node will begin operation.

2.2.1 What the Blinking Lights Mean

2.2.1.1 The Green LED
During the initial boot up the green LED may blink unevenly. However after 10 seconds the green LED should begin blinking at a steady r ate of 1/2 second on and 1/2 second off. This is considered the node’s “heartbeat.” If the green light fails to come on, is a solid green, or flashes at any other rate, the node has malfunctioned and the node must be replaced.
2.2.1.2 The Red LED
During the initial boot up the red LED may blink unevenly. During system operation the red LED will be a solid red whenever it is communicating with any other Eka node. If the red light flashes continuously, the node has malfunctioned and the node must be replaced.
10156-04 2 - 3 EkaNet Hardware Manual
Eka Proprietary and Confidential
ECR-2400 Node Hardware

2.3 ECR-2400 Node Specifications

Application Specifications

Compatibility ECR-2400 Meter Serial Interface Data storage Stores 1 month of data (1 channel @ 15 min. intervals) Data Integrity Non-volatile data storage provides extra security in the
Advanced features Load profile, remote demand reset, remote connect/

Radio Specifications

Operating frequency 2.400 - 2.4835 GHz Reliable data transmission Error detection, correction and retransmission
event of communication failure or power outage
disconnect capability
RF output power (typical) 20 dBm Data rate 1 Mbps Receiver sensitivity Sensitivity -80 dBm (@ 0.1% BER, +85°C) Range (w/ omni antenna)
Outdoor > 400 m (1200 ft.)
Indoor 25 - 50 m (75 - 150 ft.)
Mode Frequency hopping spread spectrum

Interface Specifications

Meter manufacturer proprietary protocol

Mechanical

Weight: 45 g (1.6 oz.) Dimensions: 97 x 80 x 33 mm.
7
/8 x 3 1/8 x 1 1/3 in.)
(3
EkaNet Hardware Manual 2 - 4 10156-04
Eka Proprietary and Confidential
ECR-2400 Node Hardware

Network Specifications

No hard limitation on number of meters per Gateway (actual number of meters per Gateway depends on network performance requirements)
Full peer-to-peer communication Fully self-configuring Automatic routing No network address management required Automatic network acquisition Automatic time synchronization of all nodes in the network 128 bit authentication/encryption

Operating Conditions

Environmental -40°C to +70°C
5 - 95% non-condensing humidity
Power Supply Internal to meter
1 10 - 240 VAC
Power Consumption 0.6 Watt typical
10156-04 2 - 5 EkaNet Hardware Manual
Eka Proprietary and Confidential
Elster A3/Alpha Plus Node Hardware

3. Elster A3/Alpha Plus Node Hardware

3.1 Overview

The Elster A3/Alpha Plus node is an under-the-glass board designed for installation in an Elster A3/Alpha Plus meter. The node plugs into the meter and provides an easy and reliable way to enable meters to automatically form a wireless mesh network.
This section describes the procedures to integrate a Elster A3/Alpha Plus node with an Elster A3/Alpha Plus meter.
Figure 3.1 Elster A3/Alpha Plus Node - Top
Figure 3.2 Elster A3/Alpha Plus Node - Side View
View
EkaNet Hardware Manual 3 - 1 10156-04
Eka Proprietary and Confidential
Elster A3/Alpha Plus Node Hardware

3.1.1 Elster A3/Alpha Plus Node Features

Elster A3/Alpha Plus nodes:
operate in the 915 MHz or 2.4 GHz license-free bands
fit “under the glass”
perform automatic time synchronization
provide real-time access to interval data
contain local non-volatile data storage
provide full wireless routing capability

3.1.2 Elster A3/Alpha Plus Node Layout

Figure 3.3 below is a simple diagram of an Elster A3/Alpha Plus node. The primary components of the node are:
the meter interface connector - connects the node to the meter
the node’s serial number - the node’s unique identifier
LEDs - red and green lights displaying node’s operating status
Bar C ode and l abel cont ain t he node’s
radio address and
serial num ber.
Thes e numbe rs are also em bedded in the node’s s oft w are.
Each Elster A3/Alpha Plus node is uniquely identified with a serial number. This number is displayed on the label and is contained on the bar code. In addition, the number is also embedded in the node’s softwa re. This serial number is the number displayed on the Field Tool and Network Manager to identify the node.
During installation, it is important to note the Eka Serial Number and the serial number of the meter in which it is installed in the event that the node and/or meter require troubleshooting.
LED S t atu s Lights
Eka Sy st e m s Inc .
Meter Interface
Connector O n
Unders ide of node
Figure 3.3 Elster A3/Alpha Plus Node Layout
10156-04 3 - 2 EkaNet Hardware Manual
Eka Proprietary and Confidential
Elster A3/Alpha Plus Node Hardware

3.2 Installation and Operation

Install the Eka Elster A3/Alpha Plus node in the Elster A3/Alpha meter as sho wn in Figure 3.4.
Figure 3.4 Eka Node Placement within an Alpha Meter
Connect the Elster A3/Alpha Plus Meter Board to the Meter Interface Connector on the Elster A3/Alpha Plus Node.
As soon as the meter is installed and powered on, the Elster A3/Alpha Plus node will begin operation.
Because the EkaNet node communicates with the A3 meter at 9600 baud, the meter must be configured to ensure that it commu nicates at 960 0 bau d. Please refer to the A3 meter documentation for configuration procedures.
EkaNet Hardware Manual 3 - 3 10156-04
Eka Proprietary and Confidential
Elster A3/Alpha Plus Node Hardware

3.2.1 What the Blinking Lights Mean

3.2.1.1 The Green LED
During the initial boot up the green LED may blink unevenly. However after 10 seconds the green LED should begin blinking at a steady r ate of 1/2 second on and 1/2 second off. This is considered the node’s “heartbeat.” If the green light fails to come on, is a solid green, or flashes at any other rate, the node has malfunctioned and the node must be replaced.
3.2.1.2 The Red LED
During the initial boot up the red LED may blink unevenly. During system operation the red LED will be a solid red whenever it is communicating with any other Eka node. If the red light flashes continuously, the node has malfunctioned and the node must be replaced.

3.3 Elster A3/Alpha Plus Node Specifications

Application Specifications

Compatibility Elster A3/Alpha Plus Meter Pulse Interface Data storage Stores 1 month of data (1 channel @ 15 min. intervals) Data Integrity Non-volatile data storage provides extra security in the
event of communication failure or power outage
Advanced features Load profile, remote demand reset

Radio Specifications

Operating frequency 902 - 928 MHz 2.400-2.4835 GHz Reliable data
transmission RF output power (Max.) 20 dBm 20 dBm
Data rate 76.8 Kbps 1 Mbps Receiver sensitivity -93 dBm (@ 0.1% BER,
Error detection, correction and retransmission
+25°C)
Error detection, correction and retransmission
Max transmit power 20 dBm Sensitivity -80 dBm (@
0.1% BER, +85°C)
10156-04 3 - 4 EkaNet Hardware Manual
Eka Proprietary and Confidential
Elster A3/Alpha Plus Node Hardware
Radio Specifications
Range (w/ omni antenna) > 400 m (1200 ft.)
Mode Frequency hopping

Interface Specifications

ANSI C12.18/C12.19 for the A3 Meter manufacturer proprietary protocol for the Alpha Plus

Mechanical

Weight: 31 g (1.1 oz.)
25 - 50 m (75 - 150 ft.)
Outdoor > 1,000 m (3,200 ft.) Frequency hopping
spread spectrum
Indoor 75 - 150 m (225 - 490 ft.)
spread spectrum
Dimensions: 76 x 76 mm.
(3
x 3 in.)

Network Specifications

No hard limitation on number of meters per Gateway (actual number of meters per Gateway depends on network performance requirements)
Full peer-to-peer communication Fully self-configuring Automatic routing No network address management required Automatic network acquisition Automatic time synchronization of all nodes in the network 128 bit authentication/encryption

Operating Conditions

Environmental -40°C to +70°C
5 - 95% non-condensing humidity
Power Supply Internal to meter Power Consumption 0.6 Watt typical
EkaNet Hardware Manual 3 - 5 10156-04
Eka Proprietary and Confidential
RESI-MON Node Hardware

4. RESI-MON Node Hardware

FCC Notice
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
The Original Equipment Manufacturer (OEM) must ensure that FCC Labeling requirements are met. This includes a clearly visible label on the outside of the OEM enclosure specifying the appropriate EKA Systems FCC identifier for this product as well as the FCC Notice below.
Warning
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and (2) This device must accept any interference received, including interference that may cause
Warning
undesired operation.
Warning
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation.
If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.
10156-04 4 - 1 EkaNet Hardware Manual
Eka Proprietary and Confidential
RESI-MON Node Hardware

4.1 Overview

The RESI-MON node is an under-the-glass board designed for installation in an RESI­MON meter. The node plugs into the meter and provides an easy and reliable way to enable meters to automatically form a wireless mesh network.
This section describes the procedures to integrate a RESI-MON node with a RESI­MON meter.

4.1.1 RESI-MON Node Features

RESI-MON nodes:
Figure 4.1 RESI-MON Node
operate in 915 MHz license-free bands
fit “under the glass”
perform automatic time synchronization
provide real-time access to interval data
contain local non-volatile data storage
provide full wireless routing capability
EkaNet Hardware Manual 4 - 2 10156-04
Eka Proprietary and Confidential
RESI-MON Node Hardware

4.1.2 RESI-MON Node Layout

Figure 4.2 below is a simple diagram of a RESI-MON node. The primary components of the node are:
the pulse interface connector - connects the node to th e meter
the DC power connection - supplies power to the node
the node’s serial number - the node’s unique identifier
LEDs - red and green lights displaying node’s operating status
Mounting Hol es
Bar Code and label contain the node’s
radio address and
serial number .
These numbers are also embedded in the node’s software .
LED S tat us Lights
Mounting Hol es
Pulse -
Pulse +
FCC ID: P9X-900X
Eka SystemsInc.
+5V DC
GND
Figure 4.2 RESI-MON Node Layout
Each RESI-MON node is uniquely identified with a serial number. This number is displayed on the label and is contained on the bar code. In addition, the number is also embedded in the node’s software. This seria l number is the number displayed on the Field Tool and Network Manager to identify the node.
During installation, it is important to note the Eka Serial Number and the serial number of the meter in which it is installed in order to map billing data from the Eka serial number to the meter serial number at the database.
10156-04 4 - 3 EkaNet Hardware Manual
Eka Proprietary and Confidential
RESI-MON Node Hardware

4.2 Installation and Operation

To install the RESI-MON node in the RESI-MON meter:
1. Connect the RESI-MON Meter Board to the Pulse Interface Connector on the RESI-MON Node.
2. Connect the DC power connector on the RESI-MON node to 5V DC power and ground.
3. Verify that the power polarity is correct before applying power to the device.
As soon as the meter is installed and powered on, the RESI-MON node will begin operation.

4.2.1 What the Blinking Lights Mean

4.2.1.1 The Green LED
During the initial boot up the green LED may blink unevenly. However after 10 seconds the green LED should begin blinking at a steady r ate of 1/2 second on and 1/2 second off. This is considered the node’s “heartbeat.” If the green light fails to come on, is a solid green, or flashes at any other rate, the node has malfunctioned and the node must be replaced.
4.2.1.2 The Red LED
During the initial boot up the red LED may blink unevenly. During system operation the red LED will be a solid red whenever it is communicating with any other Eka node. If the red light flashes continuously, the node has malfunctioned and the node must be replaced.
EkaNet Hardware Manual 4 - 4 10156-04
Eka Proprietary and Confidential
RESI-MON Node Hardware

4.3 RESI-MON Node Specifications

Application Specifications

Compatibility RESI-MON Meter Pulse Interface Data storage Stores 1 month of data (1 channel @ 15 min. intervals) Data Integrity Non-volatile data storage provides extra security in the
Advanced features Load profile

Radio Specifications

Operating frequency 902 - 928 MHz Reliable data transmission Error detection, correction and retransmission RF output power (Max.) 20 dBm Data rate 76.8 Kbps Receiver sensitivity -93 dBm (@ 0.1% BER, +25°C)
event of communication failure or power outage
Range (w/ omni antenna)
Outdoor > 1,000 m (3,200 ft.)
Indoor 75 - 150 m (225 - 490 ft.)
Mode Frequency hopping spread spectrum

Interface Specifications

Dry contact closure pulse inter fa c e

Mechanical

Weight: 34 g (1.2 oz.) Dimensions: 38 x 127 mm.
(1 1/2 x 5 1/
in.)
4
10156-04 4 - 5 EkaNet Hardware Manual
Eka Proprietary and Confidential
RESI-MON Node Hardware

Network Specifications

No hard limitation on number of meters per Gateway (actual number of meters per Gateway depends on network performance requirements)
Full peer-to-peer communication Fully self-configuring Automatic routing No network address management required Automatic network acquisition Automatic time synchronization of all nodes in the network 128 bit authentication/encryption

Operating Conditions

Environmental -40°C to +70°C
5 - 95% non-condensing humidity
Power Supply Internal to meter
5 volt DC
Power Consumption 0.5 Watt typical
EkaNet Hardware Manual 4 - 6 10156-04
Eka Proprietary and Confidential
Gateway Hardware

5. Gateway Hardware

5.1 Overview

The EkaNet gateway is a reliable, fully bidirectional interface between the Internet/backbone network and the nodes on the local EkaNet wireless network.

5.1.1 EkaNet Gateway Features

EkaNet gateways:
operate in 2.4 GHz and 915 MHz license-free bands
act as a bi-directional interface between the Internet and the wireless
Eka nodes
maintain status information for each node
contain local storage for up to 45 days of interval data for each node
provide simple remote configuration of the EkaNet wireless devices
are available for installation indoors (See Installing an Indoor
Gateway) or a weather-proof version is available for installation outdoors (See Installing an Outdoor Gateway)

5.2 Configuring the Gateway Using the Field Tool

Before installing the gateway, you must first configure the gateway usin g th e PDA (Field Tool Survey kit) provided. Complete details on the use of the Field Tool are provided in the EkaNet Field Tool User Manual.
The instructions below describe the procedures to configure the gateway IP, NTP server, and user parameters on the compact flash card prior to installation
of the gateway.
Place the gateway’s compact flash card (See “The Compact Flash Card” on page 5 - 5) into the compact flash slot on the PDA (Field Tool) before performing this function as all changes made on this tab will be written directly to the compact flash card.
Select EKA Gateway Mx Manager Config on the Field Tool.
Use the Config tab to:
configure gateway IP, NTP Server, and user parameters on the
verify gateway settings on the compact flash card
change gateway settings on the compact flash card
compact flash card
10156-04 5 - 1 EkaNet Hardware Manual
Eka Proprietary and Confidential
Gateway Hardware

5.2.1 IP Config Settings

Tap the Config tab to configure gateway IP and user parameters. The information displayed is dependent upon the configuration type (IP or User) selected.
Select IP Config from the Config Type to modify the IP settings.
Figure 5.1 Gateway Maintenance IP Configuration
EkaNet Hardware Manual 5 - 2 10156-04
Eka Proprietary and Confidential
Gateway Hardware

5.2.2 User Config Settings

Select User Config as the Config T ype to modify User settings.
Select Reset to restore the user settings.
Select Save to save the user settings to the compact flash card.
Figure 5.2 Gateway Maintenance User Configuration
To modify a user, select the UserID from the drop-down list and make the necessary changes.
To create a new user:
1. Type the new User Id in the UserID text area
2. Select the Access Level from the drop-down list
3. Complete the Password
4. Reenter the password
5. Tap the Save button.
You may create multiple users before hitting the Save button.
On the Configuration screens, labels will change to a red font when changes are made to the associated values.
10156-04 5 - 3 EkaNet Hardware Manual
Eka Proprietary and Confidential
Gateway Hardware
A confirmation dialog (Figure 5.3) will be displayed after you have successfully updated the user information.
Figure 5.3 Successful Update to User Information
EkaNet Hardware Manual 5 - 4 10156-04
Eka Proprietary and Confidential
Gateway Hardware

5.2.3 NTP Config Settings

Select NTP Config as the Config Type to modify NTP settings.
Select Remove to remove highlighted server name from the list of NTP servers.
Select Reload to reload the list of server names stored on the compact flash card.
Complete the NTP Server using the valid name or IP address of an NTP (Network Time Protocol) server and tap Add.
Figure 5.4 Gateway Maintenance NTP Configuration

5.3 The Compact Flash Card

The compact flash card on the gateway contains the EkaNet gateway software and data collected from the nodes on the network. It may be necessary during system operation to remove and replace the compact fla sh card with a new card
supplied by Eka.
Power to the gateway must be turned off before removing and/or replacin g the compact flash card.
To remove the flash card, press the release button next to the compact flash card. The card will pop out and may be removed. To re-insert the card, slide it securely back into the slot.
Once the compact flash card has been removed from the gateway it may be inserted into the Field Tool. Refer to the EkaNet Field Tool User Manual for instructions on troubleshooting problems with the gateway using the Field Tool.
10156-04 5 - 5 EkaNet Hardware Manual
Eka Proprietary and Confidential
Gateway Hardware

5.4 Installing an Indoor Gateway

Y our EkaNet Gateway suit able for indoor installation will be enclosed in a plastic housing as shown in Figure 5.5.
This housing is not suitable for outdoor installation.
To install an indoor gateway:
1. Attach your ethernet cable to the LAN connection on the gateway.
LAN connection
Figure 5.5 Indoor Gateway
EkaNet Hardware Manual 5 - 6 10156-04
Eka Proprietary and Confidential
Gateway Hardware
2. Attach the gateway’s power supply to the 5V connection on the gateway.
3. Plug the power supply into an electrical outlet.
Power connection
.
Antenna
Figure 5.6 Indoor Gateway - Power Connection
Antenna
Compact Flash Card
Figure 5.7 Indoor Gateway - Cover Removed
10156-04 5 - 7 EkaNet Hardware Manual
Eka Proprietary and Confidential
Gateway Hardware

5.5 Installing an Outdoor Gateway

Your EkaNet Gateway suitable for outdoor installation will be enclosed in a plastic water-proof housing as shown in Figure 5.8.
Figure 5.8 Weather Proof Outdoor EkaNet Gateway - Closed
EkaNet Hardware Manual 5 - 8 10156-04
Eka Proprietary and Confidential
Gateway Hardware
To install an outdoor gateway:
1. Open both latches on the side of the housing to reveal the gateway hardware inside.
Other Knock Outs
Knock Out
Latches
Figure 5.9 Weather-Proof Outdoor Gateway - Latch es
2. Remove the Compact Flash Card from the gateway. (See Figure 5.10)
3. Use the PDA (Field Tool Survey kit) provided to configure the gateway IP, NTP server, and user parameters on the compact flash card. (See “Configuring the Gateway Using the Field Tool” on page 5 - 1.)
4. Reinstall the Compact Flash Card in the gateway.
After the gateway is powered up, the compact flash card cannot be removed for configuration.
5. In order to attach the ethernet cable and the power cable to the gateway you will first need to remove the knock out through which these cables will access the electronics inside the housing. There are various knock out locations on the housing. Use the one that best fits the environment in which the gateway will be installed.
10156-04 5 - 9 EkaNet Hardware Manual
Eka Proprietary and Confidential
Gateway Hardware
Antenna
Ethernet
Connection
Compact Flash Card
Ethernet Cabl e
LED Status Light
Top Assem b ly Part #/
Seria l #
AC Power
Connection
Terminals
Link Light - Green
Activity Light - Yellow
GND
L
N
Figure 5.10 Internal Components of an Outdoor Gateway
6. Connect your ethernet cable to the ethernet connection in the gateway.
During normal system operation the Activity light (yellow) on the ethernet connection will blink occasionally and the Link light (green) will be illuminated at all times.
EkaNet Hardware Manual 5 - 10 10156-04
Eka Proprietary and Confidential
Gateway Hardware
7. Connect the input power wires (line marked L, neutral marked N, and ground marked ) to the appropriate power input terminals in the gateway.
8. Install the gateway at its predetermined location.
Figure 5.11 Power Input Terminals on an Outdoor Gateway

5.6 Verifying Gateway Connectivity

A crossover ethernet cable was supplied with your EkaNet Field Tool. To use this cable to verify that the gateway is reachable:
1. Remove your ethernet cable from the gateway.
2. Plug in one end of the crossover cable into the ethernet connection on the gateway.
3. Plug the other end of the crossover cable into the ethernet adapter on the Field Tool.
Refer to the EkaNet Field Tool User Manual for instructions on troubleshooting problems with the gateway using the Field Tool.
AC Power Conn ection
Terminals
10156-04 5 - 11 EkaNet Hardware Manual
Eka Proprietary and Confidential
Gateway Hardware

5.7 Gateway Specifications

Application Specifications

TCP/IP Ethernet 10 BaseT AMD SC-520 microprocessor 128MB flash (1 channel @15 min. interval for 1000 meters for 1 month) Linux Operating System Secure Sockets Layer (SSL) communications

Radio Specifications

Operating frequency 2.400-2.4835 GHz 903-928 MHz Reliable data
transmission
RF output power (Max.) 20 dBm 20 dBm Data rate 1 Mbps 76.8 kbps Receiver sensitivity Max transmit power 20
Range (w/ omni antenna)
Indoor Mode Frequency hopping
Outdoor
Error detection, correction and retransmission
dBm Sensitivity -80 dBm (@
0.1% BER, +85°C)
> 400 m (1200 ft.) 25 - 50 m (75 - 150 ft.)
spread spectrum
Error detection, correction and retransmission
Max transmit power 20 dBm Sensitivity -93 dBm (@
0.1% BER, +25°C)
> 1000 m (3000 ft.) 75 - 150 m (225 - 450 ft.)
Frequency hopping spread spectrum

Interface Specifications

Hardware interface: RJ-45 - 468B

Mechanical

Indoor Weight: 382 g. (13.5 oz.)
Dimensions: 17.1 x 13.3 x 5.7 cm. (6 ¾ x 5 ¼ x 2 ¼ in.)
Outdoor Weight: 1492 g. (52.6 oz.)
Dimensions: 27.9 x 19 x 12 cm. (11 x 7.5 x 4¾ in.)
EkaNet Hardware Manual 5 - 12 10156-04
Eka Proprietary and Confidential
Gateway Hardware

Network Specifications

No hard limitation on number of meters per Gateway (actual number of meters per Gateway depends on network performance requirements)
Full peer-to-peer communication Fully self-configuring Automatic routing No network address management required Automatic network acquisition Automatic time synchronization of all nodes in the network 128 bit authentication/encryption

Operating Conditions

Environmental -40°C to +85°C
5 - 95% non-condensing humidity
Power Supply 110 - 240 VAC, 12W
10156-04 5 - 13 EkaNet Hardware Manual