Cooper Lighting Solutions OSW-D-010, VSW-D-010 User Manual

Project Catalog # Type
PIR Activated
Ultrasonic Activated
Self-Adjusting
1.732”
Prepared by Notes Date
Greengate
0-10V Dual Tech Sensor Dimmer
3-in-1 Solution that combines functionality of a switchpack, a sensor and a 0-10V dimmer into one wallbox device
OSW-D-010 / VSW-D-010
Typical Applications
Private Oces • Restrooms • Closets • Copy Rooms • Small enclosed spaces
Product Certication
Interactive Menu
• Order Information page 2
• Additional Resources page3
• Wiring Diagrams page 3
Part 15 Class A
Product Features
• Meets ASHRAE Standard 90.1 requirements
Meets CEC Title 24 requirements
California
California
Title 20
Title 20
Compliant
Compliant
Top Product Features
Compatible with dimmable 0-10V LED and FLR ballasts
Dual Technology Passive Infrared and Ultrasonic sensor technology
Fully adjustable Auto ON/Manual ON light level settings
Provides 180 degree eld of view with 900 sq. ft. of major and 324 sq. ft. of minor motion coverage
Selectable time delay of 15 seconds (Test mode), 5 minutes, 10 minutes, 15 minutes, 20 minutes (factory default), 30 minutes
Dimensional and Mounting Details Scale or Mounting Height
(44mm)
4.195”
(106.5mm)
58” / 1470mm
48” / 1210mm
additional product diagrams
PS503244EN page 1
June 2020
Order Information
SAMPLE ORDER NUMBER: OSW-D-010-W
One single gang wallplate included
Catalog Number
Catalog Number Description
OSW-D-010-* (*-W, V, LA, G, B, R)
VSW-D-010-* (*-W, V, LA, G, B, R)
Note
Not all colors are available in stock and some color options may have extended lead times.
0-10V Dual Tech Sensor Dimmer - Occupancy with LED Single pole/3-Way preset
0-10V Dual Tech Sensor Dimmer - Vacancy with LED Single pole/3-Way preset
Compatible
Lamp Types
0-10VDC LED/FLR
0-10VDC LED/FLR
Product Specications
Key Features
Compatible with dimmable 0-10V LED and FLR ballasts
Fully adjustable Auto ON/Manual ON light level settings
Adjustable high-end and low-end trim setting
Push pad design provides minimal travel and crisp actuation
Digital circuitry provides aesthetically pleasing soft ON/fade OFF
No leakage to load in OFF mode
Integrated photocell for daylighting
• Zero crossing for long relay life
Technology
0-10V Dual Tech Sensor Dimmer
Dual Technology Passive Infrared and Ultrasonic sensor technology
Mechanical
Mounting Plate/Strap Dimensions: 4.19” H x 1.73” W (106.55mm x 44mm) Product Housing Dimensions: 2.7” H x 1.73” W x 2.19”D
(68.5mm x 43.9mm x 55.62mm)
Environment:
• Operating temperature: 32°F to 104°F (0°C to 40°C)
• Relative humidity operating: 20% to 90% non-condensing
For indoor use only
Housing: Durable, polycarbonate decorator housing with gloss nish Mounting: Fits in a standard 3.5” deep back box
Electrical
• Neutral is required for installation of device
Wiring type:
Single pole and 3-way
8” pre-stripped wire leads,
#16 AWG for Load and GND wires
#18 AWG for all other wires
Electrical ratings: 8A 120/277VAC @ 60Hz (LED) Light Intensity Control: Full-range, continuously variable dimming Class 2 dimming output section: 0-10 VDC, 80mA maximum current sink.
0-10V output supports up to 40 ballasts/ drivers that draw the standard 2mA each Surge Protection: Meets ANSI/IEEE Std. C62.41, tested to withstand voltage
surges up to 6000V and current surges of up to 3000A Radio Frequency Interference: Designed to reduce interference with radio,
audio and video equipment 0-10VDC FLR and LED ballasts
Voltage Ratings: Permanently marked on device label Flammability: Meets UL 94 requirements; V2 rated
0-10V Dual Tech Sensor Dimmer
Ratings
Watt
960
2200
960
2200
Hardware Specifications
Status Indicators: LED Indicators to indicate motion LED indicators
Red LED = PIR detection
Green LED = Ultrasonic detection
Controls and Performance
Selectable Time delays:
15 seconds (Test mode)
5 minutes, 10 minutes, 15 minutes, 20 minutes (factory default), 30 minutes
Coverage:
Provides 180 degree eld of view with 900 sq. ft. of major and 324 sq. ft. of minor motion coverage
Occupancy Sensor:
Occupancy Sensor version allows operations to toggle between Auto ON/Auto OFF or Manual ON/Auto OFF mode
Occupancy Sensor version provides a selectable ambient light override preventing lights from switching ON when there is acceptable natural light
Dimming control:
Full-range preset dimming control provided with horizontal dim/bright bar
Standards/Ratings
cULus Listed to UL1472, le no. E325082
FCC Part 15 Class A
• Meets ASHRAE Standard 90.1 requirements
Meets CEC Title 24 requirements
California Title 20 Compliant
Warranty
Five year warranty standard
Ratings
V/AC
120
277
120
277
Color
W=White, V=Ivory, LV=Light Almond, G=Gray, B=Black, R=Red
W=White, V=Ivory, LV=Light Almond, G=Gray, B=Black, R=Red
PS503244EN page 2
June 2020
0-10V Dual Tech Sensor Dimmer
Overview
Cooper Lighting Solutions’ 0-10V Dual Tech Sensor Dimmer is a 3 in 1 solution that combines functionality of a switchpack, a sensor and a 0-10V dimmer into one wallbox device to help customers save labor costs as well as meet the latest energy codes and standards. Eaton’s 0-10V Dual Tech Sensor Dimmer solution offers a convenient and cost effective way for users to satisfy commercial energy codes like ASHRAE 90.1 and California Title 20 that require designs that enable energy savings for Commercial facilities. Some of the requirements that can be met by a solution incorporating this device include Area Control, Automatic Lighting Shutoff, Manual ON or Partial ON (ASHRAE 90.1 only), Multi-level Lighting Control and Occupancy Sensor Control. This product can be used in Single-pole (one location) as well as 3-Way (multi-location) applications and is aesthetically compatible with Eaton’s decorator style devices and wallplates. This device also allows isolation of its relay for occupancy based control of external power packs. There is an adjustable Auto ON/Manual ON light level setting, so the lights will only initially turn ON to a user dened setting.
Daylight Switching Operation
In Open-Loop Daylight Switching the daylight sensor measures the natural light contribution in order to automatically adjust lighting. The sensor switches the light off if enough ambient light is present and it switches the light on if there is not enough ambient light in the space.
Open-Loop Daylight Dimming Operation
In Open-Loop Daylight Dimming the daylight sensor measures the natural light contribution in order to automatically adjust lighting.
Wiring Diagrams
Single-Pole Wiring Diagram FLR, LED
120-277VAC 50/60Hz
Controls
Neutral (White)
Wall Switch for 3-way switching
Earth Ground (Green)
Earth
Hot (Black)
Neutral (White)Hot (Black)
3-Way Input (Blue) Dry Contact Input (Orange)
Daylight
Sensor
LED
indicator
Dim Positive (Purple)
Dim Negative (Gray)
Dry Contact Output (Red)
Hot (Black)
120-277VAC 50/60Hz
use same branch
Neutral (White)
Lighting Load
Wiring Diagram 1:
Typical Wiring Diagram
(Simple 3-way Switch) Scene Dimming Allowed
Lower
On/Off Toggle
Raise
PS503244EN page 3
June 2020
Field of View
30’
Tested to NEMA WD 7-2011
0-10V Dual Tech Sensor Dimmer
18’
Minor Motion, IR
15’
Major Motion, IR
9’
Maximum coverage area may vary somewhat according to room shape and the presence of obstacles
Control Systems
Greengate
Cooper Lighting Solutions
1121 Highway 74 South Peachtree City, GA 30269 P: 770-486-4800 www.CooperLS.com
© 2019 Cooper Lighting Solutions All Rights Reserved.
Specifications and dimensions subject to change without notice.
PS503244EN page 4
June 2020