IB525005EN
Installation Instructions - 0-10V Class 1 and Class 2 Wiring
Instructions d’installation - Câblage de catégories 1 et 2 pour les
unités de 0 à 10 V
Instrucciones de instalación - Cableado 0-10V Clase 1 y Clase 2
Overview
0-10V ballasts and drivers are connected together by
a 2-wire low voltage bus that is suitable for Class 1 or
Class 2 wiring installations. This application note explains
how both Class 1 and 2 wiring are made and how they
both meet National Electric Code (NEC) regulations.
To reduce the risk of interference it’s highly
recommended that 0-10V and communication wires
be run as Class 2. The dimming performance of 0-10V
can be impaired if the system is wired in a Class 1
configuration, especially if long distances of line voltage
wiring are used. If Class 1 is desired, then actions should
be taken to reduce the length of the 0-10V wires.
Wiring Details – Class 2 (Preferred
Method):
The ballasts and drivers seen below are wired in a
Class 2 configuration.
ote:NFor more information on Class 2 wiring and
additional Class 2 wiring requirements see
National Electric Code Article 725.
With regards to factory installed wiring, as per
UL1598 section 6.17.1:
Factory-installed power limited wiring and branch
circuit wiring that come in random contact within the
luminaire shall have insulation rated for the maximum
voltage that exists in any of the circuits.
If wiring with the properly rated insulation is used, then
no spacing or separation is required regardless of the
circuit conductor voltage.
Class 2 wiring of the 0-10V ballasts and drivers
follow the NEC Requirement 725.136(D) (references
to Class 3 are eliminated).
Class 2 circuit conductors in compartments,
enclosures, device boxes, outlet boxes, or similar
fittings shall be permitted to be installed with
electric light, power, Class 1 … circuits where they
are introduced solely to connect the equipment
connected to Class 2 circuits and where (1) or (2)
applies:
(1) The electric light, power, Class 1 … circuit conductors
are routed to maintain a minimum of 6 mm (.25 in)
separation from the conductors and cables of Class 2.
(2) The circuit conductors operate at 150 volts or less to
ground and also comply with one of the following:
a. The Class 2 circuits are installed using Type CL3,
CL3R, or CL3P or permitted substitute cables
provided these Class 3 cable conductors extending
beyond the jacket are separated by a minimum of
6 mm (0.25 in) or by a nonconductive sleeve or
nonconductive barrier from all other conductors.
b. The Class 2 circuit conductors are installed as a
Class 1 circuit.
0-10V ballasts and drivers have a minimum spacing
of 0.25 inches between line voltage and the bus
terminals (purple and grey wires) for Class 2
installations.
Conduit
Conduit
V
g
n
L
LED
DRIVER
g
V
n
L
LED
DRIVER
Positive
LED ARRAY
Negative
Positive
LED ARRAY
Negative
Figure 1. 0-10V Ballasts and Drivers Wired for Class 2
COOPER LIGHTING SOLUTIONS IB525005EN
Installation instructions
Installation Instructions - 0-10V Class 1 and Class 2 Wiring
Wiring Details – Class 1:
The ballasts and drivers seen below are wired in a Class 1
configuration.
Class 1 wiring methods follow the NEC Requirement
725.48
Class 1 circuits shall be permitted to be installed with other
circuits as specified in 725.48 (A) and (B):
(A) Class 1 circuits shall be permitted to occupy the
same cable, cable tray, enclosure, or raceway
without regard to whether the individual circuits are
alternating or direct current, provided all conductors
are insulated for the maximum voltage of any
conductors in the cable, cable tray, enclosure or
raceway.
(B) Class 1 circuits shall be permitted to be installed
with power supply conductors as specified:
(1) Class 1 and power supply circuits shall be
permitted to occupy the same cable, enclosure,
or raceway only when functionally associated.
Since the 0-10V ballast and driver meets Class 2
installation requirements, it can also be installed in a
Class 1 configuration when Class 2 markings are not
present. The NEC allows the reclassification of Class 2
circuits per Article 725.130 Exception No.2:
Class 2 and circuits shall be permitted to be
reclassified and installed as Class 1 circuits if the
Class 2 markings ... are eliminated and the entire
circuit is installed using the wiring methods and
materials in accordance with Part II, Class 1 circuits.
ote:NFor more information regarding Class 2 wiring and
additional requirements see the National Electrical
Code Article 725.
The 0-10V ballast and driver is labeled ”Class 2” rather
than “Class 1 or Class 2” because the ballast is a sink
of power, not a source. According to UL 935 SB12.3:
When the ballast is the sink of a “Class 2” limited
power circuit shall be identified as such with
words “Class 2 Circuit” to indicate that the ballast
is intended for connection to a Class 2 circuit and
that the controlling circuit is not affected by the
presence of the ballast.
Since the ballast is not a source for this link, it is prohibited
from being marked “Class 1 or Class 2” even though it is
allowed to be wired either way.
Positive
LED ARRAY
Negative
Positive
LED ARRAY
Negative
Conduit
Conduit
n
L
n
L
g
V
LED
DRIVER
g
V
LED
DRIVER
Figure 2 0-10V Ballasts and Drivers Wired for Class 1
2
COOPER LIGHTING SOLUTIONS
IB525005FR
Installation instructions
Instructions d’installation – Câblage de catégories 1 et 2 pour les unités de 0 à 10 V
Présentation
Les pilotes et les ballasts de 0 à 10 V sont reliés par une
barre omnibus bifilaire à basse tension qui convient aux
installations de câblage de catégories 1 et 2. Cette note
d’application explique comment les câblages de catégories
1 et 2 sont réalisés et comment ils répondent aux
règlementations du NEC (National Electric Code ou code
national de l’électricité)
Afin de réduire le risque d’interférence, il est hautement
recommandé que les unités de 0 à 10 V et les fils de
communication fonctionnent en catégorie 2. La performance
de gradation des unités de 0 à 10 V peut être affectée si
le système est câblé selon la configuration de catégorie
1, en particulier si les câbles pour la tension de secteur
sont utilisés sur de longues distances. Si la catégorie 1 est
souhaitée, il faudra alors réduire la longueur des câbles de
0 à 10 V.
(1) Les conducteurs de circuit de lampe électrique,
d’alimentation, de catégorie 1 [...] sont acheminés pour
maintenir une séparation minimale de 6 mm (0,25 po)
entre les conducteurs et les câbles de catégorie 2.
(2) Les conducteurs de circuit fonctionnent à 150 V ou
moins vers la mise à la terre et respectent également
un des éléments suivants :
a. Les circuits de catégorie 2 sont installés avec des
câbles de type CL3, CL3R ou CL3P ou bien tout
substitut autorisé, à condition que les conducteurs
des câbles de catégorie 3 sortant de la gaine soient
séparés de tous les autres conducteurs par une
distance minimale de 6 mm (0,25 po) ou bien par
un manchon non conducteur ou une protection non
conductrice.
b. Les conducteurs de circuit de catégorie 2 sont
installés selon un circuit de catégorie 1.
Les pilotes et les ballasts de 0 à 10 V ont un
espacement minimum de 6 mm (0,25 po) entre
Détails du câblage – catégorie 2 (méthode
privilégiée) :
les bornes de la tension de secteur et de la barre
omnibus (câbles violets et gris) pour les installations de
catégorie 2.
Les ballasts et les pilotes illustrés ci-dessous sont câblés
selon une configuration de catégorie 2.
emarque:RPour obtenir davantage d’informations sur
le câblage de catégorie 2 et les exigences
supplémentaires, consultez l’article 725 du
Conduit
NEC.
En ce qui concerne un câblage installé en usine,
conformément à la norme UL 1598, section 6.17.1 :
Les câbles limités en courant et les câbles de circuit de
dérivation installés en usine qui touchent le luminaire
de manière aléatoire doivent être isolés pour la tension
maximale existante dans un circuit.
Conduit
Si des câbles correctement isolés sont utilisés, il n’est pas
nécessaire d’avoir un espacement ou une séparation quelle
que soit la tension du conducteur du circuit.
Le câblage de catégorie 2 pour les pilotes et les
ballasts de 0 à 10 V respecte l’exigence 725.136(D) du
NEC (les références à la catégorie 3 sont supprimées).
Il est permis d’installer des conducteurs de circuit
Figure 1. Pilotes et ballasts de 0 à 10 V câblés pour la
catégorie 2
de catégorie 2 dans les compartiments, les
boîtiers, les boîtes d’appareil, les boîtes de sortie
ou tout boîtier similaire avec les circuits de lampe
électrique, d’alimentation, de catégorie 1 [...] s’ils
sont présents uniquement pour relier l’équipement
connecté aux circuits de catégorie 2 et si la
condition (1) ou (2) s’applique :
n
L
n
L
V
g
DEL gRAD
nIVEAU
g
V
DEL gRAD
nIVEAU
Positif
RAngÉE DE DEL
Négatif
Positif
RAngÉE DE DEL
Négatif
3
Loading...
+ 4 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.