Cooper Lighting Solutions IB505007EN, Sure-Lites Installation Manual

IB505007EN 049-264
Sure-Lites
Installation Instructions for the Sure-Lites SEL Emergency Lights with Self-Diagnostics and Remote Capacity
WARNING
Risk of Fire/Electric Shock
If not qualified, consult an electrician.
Important Safeguards
WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD ALWAYS BE OBSERVED INCLUDING THE FOLLOWING.
1. READ AND FOLLOW ALL SAFETY INSTRUCTIONS
2. Do not use outdoors.
3. Do not use in hazardous locations, or near gas or electric heaters.
4. Do not let power supply cords touch hot surfaces.
5. Use caution when servicing batteries. Battery acid can cause burns to skin and eyes. If acid is spilled on skin or in eyes, flush acid with fresh water and contact a physician immediately.
6. Do not use this equipment for other than the intended use.
7. Installation is to be performed only by qualified personnel.
8. Install in accordance with National Electric Code and local regulatory agency requirements.
9. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
10. Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel.
11. SAVE THESE INSTRUCTIONS
MAX MOUNTING HEIGHT:
17.24 FT for SEL25 models
25.39 FT for SEL50 models
27.6 FT for SEL60 models
WARNING
Risk of Electric Shock
Disconnect power at fuse or circuit breaker before installing or servicing.
INSTALLATION
1. De-energize the circuit at the junction box (J-box) where the emergency light is to be installed.
2. Open the emergency light by inserting a screwdriver in the two slots at the bottom of the unit, then tipping the cover up off of the backplate.
3. To mount to a junction box - Drill out the appropriate mounting pattern and the wire pass hole in the backplate to fit the J-box being used.
4. To mount to conduit – Cut out the U shaped knockout on the cover using snips, then attach the ½” conduit hub to the backplate
5. Once the backplate is secured, the housing can be held in place during installation using the EZ Hang feature. (see Fig. 1)
6. Connect the incoming wires to the fixture’s power supply wires using the wire nuts provided. Connect the white wire to neutral. If using 120V, connect the black wire to the hot lead. If using 277V, connect the orange wire to the hot lead. Cap the unused lead. Secure the emergency light to the wall and/or junction box using installer supplied hardware.
7. Connect the battery to the PCB. See schematic for detail.
8. Snap the cover onto the backplate.
9. Energize AC supply. The test button should illuminate, and LED heads will illuminate briefly when the test button is pushed.
10. If the unit has remote capacity, LED remotes can be connected using the violet (+) and yellow (-) wires. See schematic.
11. Adjust the heads as needed.
12. If the fixture is to be powered down for an extended period after initial installation, replace the EZ Key. This will prevent the battery from discharging when AC power is removed. However, it will also prevent the battery from charging when AC power is restored, so it must be removed once the unit is ready for regular operation.
IB505007EN
SEL-SD Emergency Lights with Self-Diagnostic and Remote Capacity Installation Instructions
Figure 1
Slide snaps through holes in housing for temporary mount when wiring.
ACTIVATING TIME DELAY
The SEL-SD series has an integrated time delay circuit that allows them to remain in emergency mode 15 minutes after power is restored. To activate the time delay, remove the jumper on the circuit board labeled TDI/J1.
OPERATION
The Sure-Lites Eagle Eye Self Diagnostics is continuously monitoring your emergency fixture, and will signal any failure through the 3 color indicator LED.
Initial Operation:
When the unit is first powered up, it will go into a 24 hour fast charge, indicated by the indicator LED pulsing green. Once the unit has fully charged, it will perform a self calibration, after which the LED will change to steady green, indicating the unit is fully charged and float charging the battery to maintain readiness.
Automatic Testing:
The unit will perform a battery capacity, lamp/LED, and charge cir­cuit test every 30 days for 30 seconds. During this time, the indica­tor LED will change to a steady yellow. It will perform a full battery capacity (90 minute) test once per year. During this time, the indica­tor LED will change to a blinking yellow.
Manual Testing:
• 10 Second “Installation” test – Press and release the test button once during fast charge (blinking green) to initiate a 10 second quick test. The sign will switch to emergency mode for 10 sec­onds allowing the installer to verify proper installation of the unit, and the LED indicator will turn solid yellow.
• 30 Second Test -Press and release the test button once during float charge (steady green). The indicator LED will turn steady yellow to indicate the unit is performing a 30 second test of the batteries and lamps/LEDs.
• 90 Minute Test -Press and release the test button a second time during a 30 second test (steady yellow) to change to a 90 minute test. During this test, the LED indicator will change to blinking yellow, and the circuit will perform a full battery capacity, charge circuit, and LED test.
• Canceling Test – Press and release the test button during the 90 minute test (flashing yellow) to return the fixture to its original state (fast charge or float charge).
Laser Test
The SEL-SD series is equipped with a Laser Test function, that allows the unit to be manually tested without the need to physically press the test button. Shining a laser pointer in the hole marked “LASER TEST” on the bottom of the unit has the same effect as a press and release of the test button.
Clearing Failure Codes
• A battery failure (LED two blink red) can be cleared by replacing the battery. Disconnecting the battery and AC power, or perform­ing a full 90 minute discharge, will reset the error code, however, it will return if the battery is faulty.
• Charge Circuit (LED three blink red) and lamp/LED failure (LED four blink red) will clear when the unit successfully passes a manual or automatic 30 second test.
Indicators
• LED Off -No power to unit, emergency mode.
• LED Steady Green -Unit is fully charged and is float charging the battery to maintain readiness.
• LED Green Pulse -Unit is in a 24 hour fast charge of the battery.
• LED Two Blink Red -Battery has failed a capacity test, or the bat­tery is disconnected. See “Clearing Failure Codes” above.
• LED Three Blink Red -Battery charge circuit has failed. See “Clearing Failure Codes” above.
• LED Four Blink Red -Lamps have burned out, or on an EXIT/ Combo, 50% or more of the LEDs have failed. See “Clearing Failure Codes” above.
• LED Steady Yellow -30 second test or 10 second quick test (Fast Charge only).
• LED Blinking Yellow -90 minute test