IB505007EN 049-264
Sure-Lites
Installation Instructions for the Sure-Lites SEL Emergency Lights with
Self-Diagnostics and Remote Capacity
WARNING
Risk of Fire/Electric Shock
If not qualified, consult an electrician.
Important Safeguards
WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY
PRECAUTIONS SHOULD ALWAYS BE OBSERVED INCLUDING
THE FOLLOWING.
1. READ AND FOLLOW ALL SAFETY INSTRUCTIONS
2. Do not use outdoors.
3. Do not use in hazardous locations, or near gas or electric
heaters.
4. Do not let power supply cords touch hot surfaces.
5. Use caution when servicing batteries. Battery acid can
cause burns to skin and eyes. If acid is spilled on skin or in
eyes, flush acid with fresh water and contact a physician
immediately.
6. Do not use this equipment for other than the intended use.
7. Installation is to be performed only by qualified personnel.
8. Install in accordance with National Electric Code and local
regulatory agency requirements.
9. The use of accessory equipment not recommended by the
manufacturer may cause an unsafe condition.
10. Equipment should be mounted in locations and at heights
where it will not readily be subjected to tampering by
unauthorized personnel.
11. SAVE THESE INSTRUCTIONS
MAX MOUNTING HEIGHT:
17.24 FT for SEL25 models
25.39 FT for SEL50 models
27.6 FT for SEL60 models
WARNING
Risk of Electric Shock
Disconnect power at fuse or circuit breaker before
installing or servicing.
INSTALLATION
1. De-energize the circuit at the junction box (J-box) where
the emergency light is to be installed.
2. Open the emergency light by inserting a screwdriver in the
two slots at the bottom of the unit, then tipping the cover
up off of the backplate.
3. To mount to a junction box - Drill out the appropriate
mounting pattern and the wire pass hole in the backplate
to fit the J-box being used.
4. To mount to conduit – Cut out the U shaped knockout on
the cover using snips, then attach the ½” conduit hub to
the backplate
5. Once the backplate is secured, the housing can be held in
place during installation using the EZ Hang feature. (see
Fig. 1)
6. Connect the incoming wires to the fixture’s power supply
wires using the wire nuts provided. Connect the white
wire to neutral. If using 120V, connect the black wire to
the hot lead. If using 277V, connect the orange wire to the
hot lead. Cap the unused lead. Secure the emergency light
to the wall and/or junction box using installer supplied
hardware.
7. Connect the battery to the PCB. See schematic for detail.
8. Snap the cover onto the backplate.
9. Energize AC supply. The test button should illuminate, and
LED heads will illuminate briefly when the test button is
pushed.
10. If the unit has remote capacity, LED remotes can be
connected using the violet (+) and yellow (-) wires.
See schematic.
11. Adjust the heads as needed.
12. If the fixture is to be powered down for an extended
period after initial installation, replace the EZ Key. This
will prevent the battery from discharging when AC power
is removed. However, it will also prevent the battery
from charging when AC power is restored, so it must be
removed once the unit is ready for regular operation.
IB505007EN
SEL-SD Emergency Lights with Self-Diagnostic and Remote Capacity Installation Instructions
Figure 1
Slide snaps through holes
in housing for temporary
mount when wiring.
ACTIVATING TIME DELAY
The SEL-SD series has an integrated time delay circuit that
allows them to remain in emergency mode 15 minutes after
power is restored. To activate the time delay, remove the
jumper on the circuit board labeled TDI/J1.
OPERATION
The Sure-Lites Eagle Eye Self Diagnostics is continuously
monitoring your emergency fixture, and will signal any failure
through the 3 color indicator LED.
Initial Operation:
When the unit is first powered up, it will go into a 24 hour fast
charge, indicated by the indicator LED pulsing green. Once the unit
has fully charged, it will perform a self calibration, after which the
LED will change to steady green, indicating the unit is fully charged
and float charging the battery to maintain readiness.
Automatic Testing:
The unit will perform a battery capacity, lamp/LED, and charge circuit test every 30 days for 30 seconds. During this time, the indicator LED will change to a steady yellow. It will perform a full battery
capacity (90 minute) test once per year. During this time, the indicator LED will change to a blinking yellow.
Manual Testing:
• 10 Second “Installation” test – Press and release the test button
once during fast charge (blinking green) to initiate a 10 second
quick test. The sign will switch to emergency mode for 10 seconds allowing the installer to verify proper installation of the unit,
and the LED indicator will turn solid yellow.
• 30 Second Test -Press and release the test button once during
float charge (steady green). The indicator LED will turn steady
yellow to indicate the unit is performing a 30 second test of the
batteries and lamps/LEDs.
• 90 Minute Test -Press and release the test button a second time
during a 30 second test (steady yellow) to change to a 90 minute
test. During this test, the LED indicator will change to blinking
yellow, and the circuit will perform a full battery capacity, charge
circuit, and LED test.
• Canceling Test – Press and release the test button during the 90
minute test (flashing yellow) to return the fixture to its original
state (fast charge or float charge).
Laser Test
The SEL-SD series is equipped with a Laser Test function, that
allows the unit to be manually tested without the need to physically
press the test button. Shining a laser pointer in the hole marked
“LASER TEST” on the bottom of the unit has the same effect as a
press and release of the test button.
Clearing Failure Codes
• A battery failure (LED two blink red) can be cleared by replacing
the battery. Disconnecting the battery and AC power, or performing a full 90 minute discharge, will reset the error code, however,
it will return if the battery is faulty.
• Charge Circuit (LED three blink red) and lamp/LED failure (LED
four blink red) will clear when the unit successfully passes a
manual or automatic 30 second test.
Indicators
• LED Off -No power to unit, emergency mode.
• LED Steady Green -Unit is fully charged and is float charging the
battery to maintain readiness.
• LED Green Pulse -Unit is in a 24 hour fast charge of the battery.
• LED Two Blink Red -Battery has failed a capacity test, or the battery is disconnected. See “Clearing Failure Codes” above.
• LED Three Blink Red -Battery charge circuit has failed. See
“Clearing Failure Codes” above.
• LED Four Blink Red -Lamps have burned out, or on an EXIT/
Combo, 50% or more of the LEDs have failed. See “Clearing
Failure Codes” above.
• LED Steady Yellow -30 second test or 10 second quick test (Fast
Charge only).
• LED Blinking Yellow -90 minute test
2