IB505008EN
Instructions for Surelites LED Emergency Battery Packs
Includes the following model numbers: EL7W, EL14W
Sure-Lites
WARNING
Risk of Fire/Electric Shock
If not qualified, consult an electrician.
For use in
temperature rating
0°C to 55°C
EBPLED Class 2 Output
Important Safeguards
WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY
PRECAUTIONS SHOULD ALWAYS BE OBSERVED INCLUDING
THE FOLLOWING.
1. READ
2. Do
3. Do not mount near gas or electric heaters
4. Equipment should be mounted in locations and at adequate
5. The use of accessory equipment not recommended by
6. Do not use this equipment for other than its intended
7. Not for use with sealed and gasketed fixtures
8. SAVE THESE INSTRUCTIONS
NOTES
1. To prevent voltage from being present on the output wires
2. This product is for use with LED fixtures that have LED
AND FOLLOW ALL SAFETY INSTRUCTIONS
not use outdoors.
heights to prevent tampering by unauthorized personnel.
Cooper Lighting Solutions may cause an unsafe condition
and will void the warranty.
purpose.
(Red/White & Blue/White), do not connect the test button
assembly to the EBP or insure the EZ key is securely in
place.
loads capable of the output wattage and that have LED
forward voltage within the ranges below.
WARNING
Risk of Electric Shock
Disconnect power at fuse or circuit breaker before
installing or servicing.
CONTAINS N ICKEL-CADMIUM
RECHARGEABLEBATTERY.
MUST BE RECYCLEDOR
DISPOSED OF PROPERLY.
Output Power (W) Min Vf (V) Max Vf (V)
All 7 Watt
Versions
All 14 Watt
Versions
3. Make sure all of the connections are in accordance with
the National Electrical Code and any local regulations.
4. To reduce the risk of electrical shock, disconnect both
normal and emergency power supplies and the test button
indicator light (which disconnects the battery) before
servicing. Insuring the battery disconnect is securely in
place also prevents battery powered operation.
5. These emergency ballasts can be field or factory installed
depending on version. See mounting section for details.
6. This product is for use in indoor fixtures only. Do NOT
use near heated air handling outlets, wet locations or
hazardous locations.
7. An un-switched AC power source is required. (120 - 277
volts 50/60 HZ) for proper operation.
8. Do not attempt to service the battery. The sealed,
no-maintenance battery is not field replaceable. Contact
the manufacturer for information on service.
9. All maintenance should be performed by qualified service
personnel.
7 8 55
14 16 55
FEATURES
This emergency battery pack (EBP) includes extra features
which enhance its operation and maintainability.
1. Patented EZ key battery disconnect: When the EZ key is
inserted into the test button, the battery is disconnected.
This feature prevents unnecessary cycling of the battery
during the construction process. It can also be used if the
room is decommissioned for an extended period of time to
prevent the batteries from being over discharged.
2. Patent pending Test Button / Indicator Light / Laser Input:
The test button houses the EZ key, powers the indicator
light, contains the laser input for testing and functions as
the mechanical test button. Integration of these functions
improves performance and fixture aesthetics.
Ni -Cd
3. Power controlled output: This feature maintains consistent
light output during the entire 90 minutes of emergency
operation ensuring there is no drop in lumen output as the
battery voltage drops.
INSTALLATION
1. Mounting The EBP can be mounted inside a fixture channel,
on the back of a fixture, or near the fixture. The flex conduit
should be connected to a junction enclosure which allows
access to the wiring connections for grounding.
(Note: EBP assemblies without conduit must be factory
installed in the wireway of the fixture).
2. Wiring Refer to the block diagram below for the wiring of the
LED load, AC driver, and AC power.
The unswitched AC power for the EBP and the power for the
AC driver should be from the same branch circuit to prevent
disconnecting 2 sources of power and the battery during
servicing.
Block Diagram of wiring for EBPLED
Test Button /
Indicator Light /
Laser Input /
Outside of fixture color is BLK
Power for AC Driver WHT/BLK
Outside of fixture color is BLU
Unswitched 120-277VAC
50/60 Hz BLK/ORG
Outside of fixture color is WHT
120-277VAC Neutral WHT
Battery Disconnect
L
Emergency Driver
EBPLED
N
WHT/BLK
Wire
Plenum
RED/WHT
BLU/WHT
RED
+
LED Load
-
MAINTENANCE
Although no routine maintenance is required to keep the
emergency LED driver functional, it should be checked periodically
to verify proper operation. Follow any applicable local or national
codes. The following schedule is the minimum required to meet
NFPA 101 standards:
1. Visually inspect that the charging light is illuminated
monthly.
2. Test the emergency operation of the fixture monthly for a
minimum of 30 seconds. Perform the test by pressing the
test button / indicator light for 30 seconds or aiming a laser
pointer at the clear test button. The LED load should operate
at the rated output.
(Note: The laser test will not trigger if the ambient light is
too high. The light must be switched off in fixtures where
the test button is in close proximity to the light, or the test
will need to be triggered mechanically)
3. Conduct a 90 minute discharge test annually by
disconnecting the unswitched power. The LED load should
operate at the rated output for at least 90 minutes.
4. Keep written records of testing
Refer any service requirements indicated by these
checks to qualified personnel.
WARRANTIES AND LIMITATION OF LIABILITY
Please refer to www.cooperlighting.com for our terms and
conditions.
L +
AC Driver
N -
3. Mounting the Test Button / Indicator Light / Laser Input
Mount the Test Button / Indicator Light / Laser Input so the
indicator light is visible once the fixture is installed. Proper
mounting is required for accessibility and functionality of the
laser input testing feature and EZ key battery disconnect.
OPERATION
Once AC power is permanently applied to the blue wire of the
fixture remove the EZ key and store it for later use. When AC
power is applied, the charging indicator light is illuminated,
indicating the battery is being charged. When the power fails, the
emergency ballast automatically switches to emergency power,
operating its LED load at the rated output for at least 90 minutes.
NOTE: The battery is not fully charged until 24 hours after the AC
power is applied.
Image of Test Button / Indicator Light / Laser Input
With Battery Disconnected (Left)
Without Battery Disconnected (Right)
Cooper Lighting Solutions
1121 Highway 74 South
Peachtree City, GA 30269
P: 770-486-4800
www.cooperlighting.com
20 Cooper Lighting Solutions
© 20
All Rights Reserved
Printed in USA
Publication No. IB505008EN
Cooper Lighting Solutions is a
registered trademark. All
trademarks are property
of
their respective owners.