Cooper Lighting VSLN648005Z, ELVSLW571005Z, ELVSLW695005Z, VSLN536005Z, VSLW695005Z Installation Instructions

...
Instruction Leaflet K1110V
Product luminaires comply with EN60598 and are suitable for use in normal interior conditions. This luminaire has an ambient temperature range of -25 C to 25 C for the non-emergency version For Emergency variants - This luminaire has an ambient temperature range of 5 C to 25 C, to ensure the batteries work correctly
1
Disassemble
o o
October 2016
IMPORTANT: ISOLATE
o o
IP65
SUPPLY BEFORE
SERVICING
a
2
Mounting
a
This luminaire is IP65 rated, this rating only applies when the luminaire is mounted observing the correct orientation and must not be positioned in direct sunlight. In exterior applications luminaires must be protected under a canopy or cover. Housings are not suitable for mounting with the base directly on a vertical surface in the horizontal orientation.
b
b
Fix into position with
fixings supplied
c
Lift gear tray out of fitting
3
Wiring
Feed mains cable into fitting.
Ensure IP rating is retained by
fitting either cable gland or
grommet (both supplied)
Mains
- Brown (Switched) Live
L
- Green/Yellow (Earth)
- Blue (Neutral)
N
DALI Dimming: Where applicable a 2 way terminal is provided in the
luminaire geartray.
Product suitable for looping with max conductor size 2 x 2.5mm
Once complete follow the steps in section 1 in reverse order
Emergency
2
- Brown (Switched) Live
- Black (Unswitched) Live
1
- Green/Yellow (Earth)
- Blue (Neutral)
N
2
4
!! CRITICAL TO SAFETY !!
Fit Qty 4 fixing screws (supplied)
Housing clip has two holes, one in the front part and one in the hinge part. Align holes and initially insert screw by hand. If fitting is surface mounted, it is recommended to use a flexible screwdriver adaptor for final tightening
DO NO OVER TIGHTEN SCREWS!
All Fitting Sizes - Second clip position from each end, on both sides.
Housing
Clip Hole
Instruction Manual - K1110V
October 2016
5
Dimensions
VersaLite
Model
4ft single
4ft twin 1265 165 110 907 8
5ft single 1565 105 110 907 10
5ft twin 1565 165 110 907 10
6ft single 1865 105 110 1170 12
6ft twin 1865 165 110 1170 12
Length (L) (mm)
1265 105 110 907 8
Width (W) (mm)
Depth (D) (mm) B (mm) # Clips
B
Safe Operation
1. Check the rating label for voltage and frequency before connecting this luminaire to the electrical supply.
2. Ensure that the mains supply is switched off when working on this luminaire, whether installing or carrying out any other servicing.
3. To prevent damage to driver, do not mix with conventional magnetic ballasts on the same electrical circuit.
4. Where use in more onerous situations is required, e.g. In part-completed buildings before “drying-out” is completed, or areas where ambient temperatures are outside the normal temperature range, then consult our Sales Office.
5. The light source contained in this luminaire shall only be replaced by the manufacturer or his service agent or a similar qualified person.
Servicing and Disposal
1. At commissioning and handing over of installation ensure that a copy of these instr uctions is presented to the authority responsible for the operation and maintenance of the luminaries.
2. Servicing , e.g. cleaning, must only be carried out after the electricity supply has been switched off. It must not be assumed that luminaries with lamps not lit are switched off-always check before servicing.
3. Cleaning should be carr ied out at regular intervals to ensure that dirt does not accumulate to an extent that will impair the thermal safety or optical performance of the luminaire. Regular cleaning will also ensure that the optical performance of the luminaries is maintained.
4. Avoid touching the LED array surface. To clean - Blow surface with either dry air or nitrogen gas.
5. At the end of life the luminaire is classed as WEEE under directive 2012/19/EU and should be disposed of in accordance with local legislation.
Luminaire Cleaning
End of Life and Components Disposal