Cooper Lighting SVA1600 User Manual

Catalog #
Project
Comments
Prepared by
Date
SPECIFICATION FEATURES
04/04/2007 12:26:16 PM
Consult your representative for additional options and finishes.
Specifications and Dimensions subject to change without notice.
ADC040909
DOOR FRAME
MOUNTING DIMENSIONS
DESCRIPTION
The CHF Series is designed to deliver highly efficient H.I.D. lighting to clean
areas. These H.I.D. units are ideal for ceiling heights up to 18'. Lower
wattages are also available for standard 8' to 9' ceilings. Units are enclosed
and gasketed to protect against the chance of foreign matter entering high
tech environments through the light fixture. The housing and one-piece
flanged door are designed to work with conventional sheet rock or plaster
ceilings. Door frames include a gasket which eliminates ledge or crevice
exposure preventing the harboring of contaminants. These luminaires are
U.L. listed and C.S.A. certified for wet locations.
Application
The CHF Series is suitable for use
in I.E.S. Clas 100, 1000, 10,000 and
100,000 clean room environments.
Fixtures are manufactured in
accordance with U.S.D.A., F.D.A.,
N.S.F. and Federal Standard 209E.
200 PSI Hose Down Rating is
standard. Applications include
clean rooms, technical and bio-
medical labs, food processing/
testing centers and pharmaceutical
labs.
A ... Lens
One-piece, clear prismatic, tem-
pered Corning lens with internal
prism pattern. Choice of clear
polycarbonate or clear tempered
glass on environmental side.
B ... Fasteners
Flush mounted, stainless steel
machine screws secure through
captive cage nuts in housing and
are evenly spaced to compress
gasketing on all sides.
C ... Housing
Die-formed, 18 ga. CRS with tightly
butted and spot welded, sealed
end caps. Contains no holes that
would allow air passage. Standard
white high reflectance polyester
powder coat finish. Gloss: 85%;
Reflectance: 93%; Hardness: 2H;
Salt Spray: 500 Hours.
D ... Lamps
(By Others)
E ... Lens Retention
Unique, Particulock(TM) lens
retention system utilizes
continuous, 18 ga. media
clampdowns to sandwich
gasketing and integrate lens and
door frame for even environmental
seal.
F ... Hinge
Two braided, stainless steel cables
on one side of door provide
hinging.
G ... Door
One-piece, 18 ga. door with baked
white polyester powder coat, fully
gasketed, outside door with die-
formed edges eliminates seams
which could entrap microscopic
contaminants. Optional doors
available.
H ... Ballast
Copper wound, HPF ballast is
standard.
I ... Gasket
White, closed cell, Flexiseal(TM)
gasketing surrounds perimeter of
lens to seal lens to door frame and
around perimeter of door to seal
door to housing. Another layer
seals fixture to ceiling system after
installation.
J ... Access
A gasketed access plate on top of
the housing with two flattened,
7/8" diameter knockouts allows
connection of vapor tight conduit
fitting. Optional, above ceiling, top
access door for luminaire main-
tenance is available and ideal for
food processing and cleanroom
applications.
Labels
U.L. listed, C.S.A. certified,
standard wet label.
CHF
250W - 400W
Metal Halide
250W - 400W
High Pressure Sodium
165W
QL Induction
H.I.D. FLANGE
One-Piece Door
Flange Type-One-piece Door
C
B
D HJ
A
F
I
G
E
22 5/8"
[575mm]
26 3/4"
[679mm]
1 1/2"
[38mm]
19 1/2"
[495mm]
8 13/16"
[224mm]
23" Sq
[584mm]
(2) 7/8" [22mm] KO Gasketed Access Plate
(4) 3/8"x1 1/4" [10mmx32mm] Hanger Mounting Hole
ENERGY DATA
Input Watts:
250W Metal Halide: 295W 400W Metal Halide: 458W 250W High Pressure Sodium: 295W 400W High Pressure Sodium: 457W
FAIL-SAFE
®
Specifications and Dimensions subject to change without notice.
ORDERING INFORMATION
PHOTOMETRICS
CHF
2500
5000
7500
10000
12500
C and le po we r Di st ri bu ti on
Z ona l Lu me n Su mm ar y
Zone Lumens %Lamp %Luminaire
0-30 8404 23.3 38.0
0-40 13487 37.5 61.0
0-60 20037 55.7 90.6
0-90 22115 61.4 100.0
90-180 0 0.0 0.0
0-180 22115 61.4 100.0
80% 70% 50% 30% 10% 0%
70 50 30 10 50 30 10 50 10 50 10 50 10 0
73 73 73 73 71 71 71 68 68 65 65 63 63 61
68 66 64 62 65 63 61 62 59 60 58 58 56 55
64 60 57 54 59 56 53 57 52 55 51 53 50 49
59 54 50 47 53 50 47 52 46 50 45 49 44 43
55 49 45 41 48 44 41 47 40 46 40 44 39 38
51 44 40 36 44 39 36 42 36 41 35 40 35 34
47 40 36 32 40 35 32 39 32 38 32 37 31 30
44 37 32 29 36 32 28 35 28 34 28 34 28 27
41 33 28 25 33 28 25 32 25 31 25 30 25 24
38 30 25 22 29 25 22 29 22 28 22 28 22 21
35 27 23 20 27 23 20 26 19 26 19 25 19 18
rc=Ceiling reflectance, rw=W all reflectance, RCR=Room cavity ratio CU Data Based on 20% Effective Floor Cavity Reflectance.
Test No. 5911.2
CHF-400MH
Lamp=400W Lumens=22115
Spacing Criteri
a
=1.
3 =1.3
Efficiency=61.4%
rc
rw
RCR
0 1 2 3 4 5 6 7 8 9
10
C oef fi ci en t of U ti li za ti on
Ave ra ge L umi na nc e
Deg.
45 8230 8120
55 4758 4822
65 3241 3011
75 2539 2628
85 2021 2154
Fail-Safe • Customer First Center • 1121 Highway 74 South • Peachtree City, GA 30269 • TEL 770.486.4800 • FAX 770.486.4801