06/25/2007 5:03:18 PM
Consult your representative for additional options and finishes.
Specifications and Dimensions subject to change without notice.
The Fail-Safe SCH24 Series is designed for use in horizontal or non-laminar 
air flow clean rooms. The enclosed and gasketed housing and door protect 
against infiltration of airborne bacteria. Fixtures tested to 100 PSI hosedown. 
Higher ratings available (consult factory). The mitered edges on the door 
frame and the hole-free design of the housing prevent air exchange 
between the fixture and plenum, allowing relamping without contamination 
of the clean areas. These luminaires are manufactured in accordance with 
U.S.D.A., F.D.A., N.S.F. and Federal Standard 209E.
The SCH24 Series is suitable for 
use in I.E.S. Class 10 (M2.5), 100 (M 
3.5), 1,000 (M 4.5), 10,000 (M 5.5) 
and 100,000 (M 6.5) clean room 
environments. Applications include 
cleanrooms, technical and bio-
medical labs, food processing/
testing centers and pharmaceutical 
Lens is clear extruded with prisms 
positioned inside fixture and 
smooth surface on the outside for 
Flush mounted, stainless steel 
machine screws secure through 
captive cage nuts in housing and 
are evenly spaced to compress 
Nominal 5" deep recessed one-
piece housing made of 20 ga. CRS. 
Die-formed and seam welded to 
Unique, Particulock(TM) lens 
retention system utilizes con-
tinuous, 18 ga. media clamp-
downs. Lens is hermetically sealed 
with silicone RTV to door frame for 
an airtight seal against the 
Reversible drop-link hinging 
system for easy maintenance.
Optional) Door can be extruded 
aluminum, fully gasketed, outside 
flanged door with mitered edges 
eliminates seams which could 
entrap microscopic contaminants. 
Not standard, must specify. One-
piece, die-formed stainless steel 
Standard Class P, CBM/ETL ballast.
MicroSeal(TM) gasketing system 
features silicone RTV sealant 
surrounding the perimeter of lens 
to seal lens to door frame and 
extruded silicone rubber gasketing 
around perimeter of door to seal 
door to ceiling. White, closed cell 
Flexiseal(TM) seals fixture to 
ceiling system after installation.
A gasketed access plate on top of 
the housing with two flattened, 
7/8" diameter knockouts allows 
connection of vapor tight conduit 
U.L. listed, C.S.A. certified, 
C
D
I
B
F
J
H
A
E
G
5"
[127mm]
23 3/16" [589mm]
23 3/8" [594mm]
24” [610mm]
E N E R G Y  D A T A 
Input Watts:
STD Ballasts & STD Lamps 
(2) 20W T12 Fluorescents: 53W 
(3) 20W T12 Fluorescents: 85W 
(4) 20W T12 Fluorescents: 106W 
(2) 40W Biaxial Fluorescents: 82W 
(3) 40W Biaxial Fluorescents: 127W
ES Ballasts & STD Lamps 
(2) 17W T8 Fluorescents: 45W 
(3) 17W T8 Fluorescents: 68W 
(4) 17W T8 Fluorescents: 90W 
(2) 31W U1/U6 Fluorescents: 71W 
(3) 31W U1 Fluorescents: 108W 
(2) 32W T8 Fluorescents: 71W 
(3) 32W T8 Fluorescents: 108W 
(4) 32W T8 Fluorescents: 142W 
(2) 40W T12 Fluorescents: 86W 
(3) 40W T12 Fluorescents: 136W 
(4) 40W T12 Fluorescents: 172W 
(2) 40W U6 Fluorescents: 86W
ES Ballasts & ES Lamps
(2) 40W T12 Fluorescents: 76W 
(3) 40W T12 Fluorescents: 120W 
(4) 40W T12 Fluorescents: 152W 
(2) 40W U6 Fluorescents: 76W
Electronic Ballast Data:
Consult Cooper Lighting Representative
Extruded aluminum mitered door frame with 
extruded silicone rubber perimeter gasketing
One piece stainless steel door frame with 
extruded closed cell silicone perimeter gasketing
3/4"
[19mm]
Max.
2"
[51mm]
1 3/4"
[44mm]
Max.
3/4"
[19mm]
Max.
2"
[51mm]
1 3/4"
[44mm]
Max.
1 1/2"
[38mm]
10"
[254mm]
10"
[254mm]
23 3/16"
[589mm]
(2) 7/8" [22mm] Dia.KO 
Gasketed Access Plate
48 "
[1219mm]
1 7/16"
[37mm]
23 316"
[589mm]
1 1/2"
[38mm]
(2) 7/8" [22mm] Dia. KO 
Gasketed Access Plate
24"
[610mm]
5 7/16"
[138mm]
 

Specifications and Dimensions subject to change without notice.
C a ndl ep ow er D is tr ib ut io n
Z o nal L um en S um ma ry
Zone Lumens %Lamp %Luminaire
0-30 1782 20.8 28.5
0-40 2851 33.4 45.5
0-60 5016 58.7 80.1
0-90 6261 73.2 100.0
90-180 0 0.0 0.0
0-180 6261 73.2 100.0
80% 70% 50% 30% 10% 0%
70 50 30 10 50 30 10 50 10 50 10 50 10 0
87 87 87 87 85 85 85 81 81 78 78 75 75 73
80 77 74 72 76 73 71 72 68 70 66 67 64 63
74 68 63 60 67 62 59 64 57 62 56 60 55 53
68 60 55 50 59 54 50 57 49 55 48 53 47 46
62 54 48 43 53 47 43 51 42 49 42 48 41 40
57 48 41 36 47 41 36 45 36 44 35 42 35 34
52 43 36 32 42 36 31 41 31 39 31 38 31 29
48 38 32 26 38 32 27 37 27 35 27 34 27 25
44 34 28 24 34 28 24 33 24 32 23 31 23 22
41 31 25 21 30 25 21 29 20 29 20 28 20 19
38 28 22 18 28 22 18 27 18 26 18 25 18 17
rc=Ceiling reflectance, rw=W all reflectance, RCR=Room cavity ratio 
CU Data Based on 20% Effective Floor Cavity Reflectance.
630
220
930
1150
1000
400
Test No. 8717
SCH-24-332-120-I
K12-
EB82-SSN
Lamp=F32T8 
No. Lamps=3 
Lumens=2850
Spacing Criteri
a
=1.
2 =1.1
Efficiency=73.2%
rc
rw
RCR
0 
1 
2 
3 
4 
5 
6 
7 
8 
9
10
C o eff ic ie nt o f Ut il iz at io n
Ave ra ge 
L u min an ce
Deg.
45 1499 1433
55 1128 1074
65 779 718
75 405 354
85 102 79
Powder
Battery Pack 
Polyester Powder 
Finish
Catalog Number Weight Catalog Number Weight
SCH-24-217 29 lbs. [13 kg.]
SCH-24-317 29 lbs. [13 kg.]
SCH-24-417 32 lbs. [15 kg.]
SCH-24-220 29 lbs. [13 kg.]
SCH-24-320 29 lbs. [13 kg.]
SCH-24-420 32 lbs. [15 kg.]
SCH-24-231U1 29 lbs. [13 kg.]
SCH-24-331U1 32 lbs. [15 kg.]
SCH-24-231U6 29 lbs. [13 kg.]
SCH-24-232 46 lbs. [21 kg.]
SCH-24-332 46 lbs. [21 kg.]
SCH-24-432 50 lbs. [23 kg.]
SCH-24-240 46 lbs. [21 kg.]
SCH-24-340 46 lbs. [21 kg.]
SCH-24-440 50 lbs. [23 kg.]
SCH-24-240BX 29 lbs. [13 kg.]
SCH-24-340BX 32 lbs. [15 kg.]
SCH-24-240U6 29 lbs. [13 kg.]
Fail-Safe • Customer First Center • 1121 Highway 74 South • Peachtree City, GA 30269 • TEL 770.486.4800 • FAX 770.486.4801
06/25/2007 5:03:18 PM
ADC041659