COOPER LIGHTING - SURE-LITES
®
RD SERIES
Two Injection Molded
EMERGENCY LIGHTS Architectural
Thermoplastic Heads
RLM SERIES
Two High-Impact 
Thermoplastic Heads
Recessed Housing 
EMERGENCY LIGHT
• Dual-voltage input 
120/277VAC, 60Hz
• 20 gauge die-formed steel 
housing with white powder 
coat finish
• Heads match housing 
finish
DESCRIPTION
The RD Series is a recessed 
emergency lighting system 
designed for locations where 
aesthetics are of utmost
DIMENSIONS
4 5/8"
(118mm)
  8 1/4" 
(210mm)
3 1/2"
(89mm)
6"
(152mm)
(RD4 Only)
importance. The housing is 
fully recessed in dry wall or 
grid ceiling installations. 
Designer pinchback heads 
rotate 358° and swivel 90° to 
0°. Ideal for commercial and 
institutional environments 
where easy recessed 
installation and minimal
6 1/4" (159mm)
9 1/4" (235mm)
  5 1/8" 
(130mm)
10 1/4" (260mm) 
12 7/8" (327mm)
7" max.
(178mm)
maintenance are desired.
The RLM Series is a recessed
8 1/4"
(210mm)
4 5/8"
(118mm)
system packaged in an 
attractive flame-resistant 
metal housing. It is the unit 
of choice for installations 
where a recessed product is
3 1/2"
(89mm)
6"
(RLM4 Only)
(152mm)
9 1/4"
(235mm)
desired and the size and cost 
of emergency lighting must 
be kept to a minimum 
without sacrificing 
dependability or light output. 
ELECTRICAL RATINGS 
Model Battery DC Voltage 1 1/2 hours 2 hours 3 hours 4 hours Type Wattage Number
RD1 SLC 6 18 15 10 8 Tungsten Halogen 6 29-12 
RD3 SLC 6 27 24 18 14 Tungsten Halogen 12 29-66 
RD4 SLC 12 54 - - - Incandescent 9 029-86 
RD6 SNC 6 15 12 8 6 Tungsten Halogen 6 29-12 
RD7 SNC 6 24 18 12 10 Tungsten Halogen 12 29-66 
RLM1 SLC 6 10.8 7.2 - - Incandescent 5.4 29-121 
RLM2 SLC 6 18 15 10 8 Incandescent 9 29-84 
RLM3 SLC 6 27 24 18 14 Incandescent 9 29-84 
RLM4 SLC 12 54 - - - Incandescent 9 029-86 
RLM8 SNC 6 15 12 8 - Incandescent 7.2 29-88 
RLM9 SNC 6 24 18 12 10 Incandescent 7.2 29-88
SLC=Sealed Lead Calcium Battery 
SNC=Sealed Nickel Cadmium Battery
ORDERING INFORMATION
SAMPLE NUMBER: RD1V
Rated Wattage to 87 1/2% of rated D.C. Voltage Lamp Information
5 1/8"
(130mm)
10 1/4" (260mm)
12 7/8" (327mm)
6 1/4" 
(159mm)
9 1/4" (235mm)
• Knockout, conduit or cord 
set
• Supplied with hanger bars, 
T-Bar clips 
• Single modular electrical 
connector
• Remote capability
• Line-latching, Solid-State 
voltage limited charger, 
Solid-State switching, 
low- voltage disconnect, 
brownout circuit, 
overload/short-circuit 
protection, test 
switch/power indicator 
light
• UL 924 Listed, Life Safety 
NFPA 101, NEC/OSHA, 
most state and local codes
COOPER LIGHTING
606
Model Number 
RD1 
RD3 
RD4 
RD6 
RD7 
RLM1 
RLM2 
RLM3 
RLM4 
RLM8 
RLM9
Energy Data
Options
(Add as suffix)
A=Ammeter 
SD=Self-Diagnostics 
TDM=Time Delay Monitor 
V=Voltmeter 
Alternate Lamps 
Other Options
(2)
(2)
(1)
Input Current (Max.): 
Model No. 120V  277V 
RD1, RD3 .12A .05A
RD4, RLM4 .30A .13A 
RD6 .06A .03A
RD7 .07A .04A
RLM1, RLM2, RLM3 .12A .05A
RLM8 .06A .03A 
RLM9 .07A .04A
(1)
Consult your Cooper Lighting Representative. 
Accessories
(Order separately)
WG2 =Wire Guard 
WG7 =Wire Guard 
VS=Choose polycarbonate
(1)
(2)
Provision for one meter only.
vandal shield desired 
from accessories 
sheet