08/02/2008 3:26:09 PM
Consult your representative for additional options and finishes.
Specifications and Dimensions subject to change without notice.
Ecofit conversion kits are an economical means of increasing fixture
efficiency and energy savings. Ecofit conversion kits are ideal for
applications where fixture removal is cost-prohibitive.
Ecofit conversion kits are designed for applications with conventional
3- or 4-lamp recessed 2' x 4' fixtures. Retrofitting 3-and 4-lamp troffers to
2-lamps with high performance retrofit conversion kits can reap up to 50%
Socket tracks are die formed
20 gauge cold rolled steel. Toolless
ballast access for easy wiring
Optional electronic ballasts are
Class "P" and are positively
secured by mounting bolts.
(1) UL/CUL listed. Suitable
Die formed reflectors are faceted
for 2 lamp configuration with two
optical distributions: medium and
wide. Medium beam optical
modules utilize 95% specular
Miro 4 substrate while the wide
distribution utilizes a high
performance 91% reflective
polyester powder coated finish.
Retrofit installation in standard
2' x 2' and 2' x 4' recessed troffers.
Length=45-1/2"
[1143mm]
19-13/16"
[505mm]
1-7/8" [48mm]
A B C
D
LAMPS CONTAIN MERCURY. DISPOSE ACCORDING
TO LOCAL, STATE OR FEDERAL LAWS
Safe and convenient means of
disconnecting power
1-7/8"
[48mm]
19-3/16" [505mm]
9-3/4"
[248mm]
All components
reflectors, reflector end
caps, socket brackets,
sockets, screws, and
wire nuts) are included
in each kit for
installation and require
only a few basic tools
for assembly.
COOPER LIGHTING - METALUX
®
Specifications and Dimensions subject to change without notice.
Z on al L um en S um ma ry
Zone Lumens %Lamp %Fixture
0-30
0-40
0-60
0-90
0-180
C an de la
Angle Along II 45° Across
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
ECT-332-W-EB81
Electronic Ballast
(3) FO32/841 lamps
2850 lumens
Spacing criterion:
(II) 1.3 x mounting
height, ( ) 1.4 x
mounting height
Efficiency 88.1%
Test Report:
ECT332WEB81
2397 2397 2397
2386 2394 2398
2356 2381 2394
2304 2349 2366
2239 2297 2311
2147 2218 2231
2041 2117 2132
1918 1998 2028
1774 1852 1923
1619 1703 1829
1445 1560 1723
1263 1413 1596
1068 1257 1444
870 1090 1167
660 864 919
449 593 760
237 395 321
60 86 54
0 0 0
1907 22.3 25.3
3152 36.9 41.8
5753 67.3 76.4
7534 88.1 100.0
7534 88.1 100.0
L um in an ce D at a
Average Average Average
Angle 0-Deg 45-Deg 90-Deg
in Deg cd/sm cd/sm cd/sm
45 3238 3406 3658
55 3114 3484 3935
65 2911 3647 3905
75 2453 3240 4152
85 973 1395 876
C oe ffi c ie nt s of U ti li za ti on
Effective floor cavity reflectance 20%
rc 80% 70% 50% 30% 10% 0%
rw 70 50 30 10 70 50 30 10 50 30 10 50 30 10 50 30 10 0
RCR
0
1
2
3
4
5
6
7
8
9
10
105 105 105 105 102 102 102 102 98 98 98 94 94 94 90 90 90 88
95 91 87 84 93 89 86 82 85 82 80 82 79 77 79 77 75 73
86 79 73 67 84 77 71 67 74 69 65 71 67 63 68 65 62 60
78 69 61 55 76 67 60 55 65 59 54 62 57 53 60 56 52 50
72 61 53 47 70 60 52 46 57 51 46 55 50 45 53 48 44 42
66 54 46 40 64 53 45 40 51 44 39 49 43 39 48 42 38 36
61 48 40 35 59 48 40 34 46 39 34 45 38 34 43 38 33 32
56 44 36 30 55 43 36 30 42 35 30 40 34 30 39 34 30 28
52 40 32 27 51 39 32 27 38 31 27 37 31 27 36 30 26 25
49 37 29 24 47 36 29 24 35 29 24 34 28 24 33 28 24 22
46 34 27 22 44 33 26 22 32 26 22 32 26 22 31 25 22 20
Z on al L um en S um ma ry
Zone Lumens %Lamp %Fixture
0-30
0-40
0-60
0-90
0-180
C an de la
Angle Along II 45° Across
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
ECT-232-M-EB81
Electronic Ballast
(2) 32W T8
F32T8/TL841 lamps
6100 lumens
Spacing criterion:
(II) 1.2 x mounting
height, ( ) 1.1 x
mounting height
Efficiency 88%
Test Report:
ECT232MEB81
2547 2547 2547
2537 2532 2522
2493 2486 2473
2413 2404 2378
2301 2275 2240
2148 2121 2088
1971 1937 1929
1756 1737 1744
1499 1496 1536
1216 1238 1284
951 998 1013
715 745 760
533 511 550
394 327 402
312 226 314
258 193 263
188 159 199
95 87 107
0 0 0
1896 31.1 35.3
2988 49.0 55.7
4632 75.9 86.3
5366 88.0 100.0
5366 88.0 100.0
L um in an ce D at a
Average Average Average
Angle 0-Deg 45-Deg 90-Deg
in Deg cd/sm cd/sm cd/sm
45 2661 2709 2810
55 1929 2010 2050
65 1443 1197 1472
75 1542 1154 1572
85 1687 1545 1900
C oe ffi c ie nt s of U ti li za ti on
Effective floor cavity reflectance 20%
rc 80% 70% 50% 30% 10% 0%
rw 70 50 30 10 70 50 30 10 50 30 10 50 30 10 50 30 10 0
RCR
0
1
2
3
4
5
6
7
8
9
10
105 105 105 105 102 102 102 102 98 98 98 94 94 94 90 90 90 88
97 93 89 86 94 91 88 85 87 85 82 84 82 80 81 79 77 76
89 82 77 73 87 81 76 72 78 74 70 75 71 68 72 69 67 65
82 74 67 62 80 72 66 61 70 65 60 67 63 59 65 61 58 56
76 66 59 54 74 65 58 53 63 57 53 61 56 52 59 55 51 49
70 60 52 47 68 59 52 47 57 51 46 55 50 46 54 49 45 44
65 54 47 42 64 53 47 42 52 46 41 51 45 41 49 44 41 39
61 50 42 37 59 49 42 37 48 41 37 46 41 37 45 40 37 35
57 46 39 34 55 45 38 34 44 38 33 43 37 33 42 37 33 32
53 42 35 31 52 42 35 31 41 35 30 40 34 30 39 34 30 29
50 39 32 28 49 39 32 28 38 32 28 37 32 28 36 31 28 26
2ECT-217-X-NB 1.2 lbs.
2ECT-217-X-UNV 2.7 lbs.
2ECT-232-X-NB 2.1 lbs.
2ECT-232-X-UNV 3.6 lbs.
2ECT-224-X-NB 1.2 lbs.
2ECT-224-X-UNV 2.7 lbs.
2ECT-254-X-NB 2.1 lbs.
2ECT-254-X-UNV 3.6 lbs.
Catalog No. Wt.
S AM PL E N UM B ER : 2 EC T- 21 7- M- UN V- EB 81 -1 0B
No. of Lamps
2=2 Lamps
3=3 Lamps
Lamp Type
17=17W T8 Lamp (24")
32=32W T8 Lamp (48")
24=24W T5HO Lamp (24")
54=54W T5HO Lamp (48")
Series
ECT=Ecofit Troffer
Width
2=24" Wide (only)
Voltage
(1)
NB=No Ballast
UNV=Universal Voltage
Ballast Included
Packaging
10B=10 Pack Quantities
80B=80 Pack Quantities
U=Unit Pack
Optics
M=Medium (Specular
Aluminum)
W=Wide (White Painted)
NOTES:
(1)
When using Ecofit Kits without ballasts, indicate ballast type and system
to designate shunted or unshunted sockets. Ex: 2ECT-2 32-M-EB81-10B.
Ballast/Socket Type
(1)
T8 Systems
EB8 =T8 Electronic Instant Start.
Total Harmonic Distortion < 10%
EB8 /PLUS= T8 Electronic Instant Start.
High Ballast Factor >1.13. Total
Harmonic Distortion < 20%
ER8
=T8 Electronic Program Rapid Start.
Total Harmonic Distortion < 10%
EB8 /L=T8 Electronic Instant Start w/ <0.80
Ballast Factor
T5 Systems
EBT =T5HO Electronic Program Start.
Total Harmonic Distortion < 10%
No. of Ballast
1, 2 or Blank
No. of
Ballast
1 or 2
No. of Ballast
1, 2 or Blank
No. of Ballast
1, 2 or Blank
No. of Ballast
1 or 2
Metalux • Customer First Center • 1121 Highway 74 South • Peachtree City, GA 30269 • TEL 770.486.4800 • FAX 770.486.4801