Cooper Lighting P4C800 User Manual

COOPER LIGHTING - LUMARK
8 23/32" [221mm]
2 13/32" [61mm]
4 5/8"
[117mm]
3 3/4"
[95mm]
8 7/8" [225mm]
7 15/16" [202mm]
DESCRIPTION
The LumaWatt controller accepts inputs from up to four
INDUSTRIAL
CML
LUMAWATT INDUSTRIAL HID DIMMING SYSTEM
remote-mounted motion detectors and provides a low-voltage output capable of controlling up to 25 fixtures. Upon receiving a 24 volt DC signal from an attached motion sensor or dry contact switch, it switches connected fixtures from low intensity to high, providing maximum light when an area is occupied and lowered energy usage when the area is empty. U.L. listed and CSA certified.
®
DIMENSIONS
Controls all LumaWatt­Equipped Lumark HID Industrial Luminaires
CONTROL MODULE
• Low voltage output controls up to 25 LumaWatt­equipped fixtures
• Allow daisy-chaining of multiple controllers
• Terminal block provides input connections for one to six passive infrared motion sensors
• Input terminal allows use of user-supplied dry­contact switch. Switch overrides motion sensors, putting system into high brightness mode
• Standard transformer accepts 120V or 277V user-configurable input. 208V, 240V, 347V and 480V are also available
• Three front panel lights show system status: amber indicates that the controller is receiving power, red indicates that output from the controller is at full brightness and green indicates that output is at low brightness
ORDERING INFORMATION
SAMPLE NUMBER: SAMPLE NUMBER: CML-120/277
Aux.
Controller
+ - +
1, 2
Product Family CML=LumaWatt
Control Module
LumaWatt Lamp Input Watts
Wattage High (HW) Low Change (PC)
Metal Halide
1000W 1080 666 38%
400W 455 238 48%
250W 295 162 45%
175W 209 101 52%
Control
Output
#2
2 + + - +
2 +
Input Voltage 120/277V=User-selectable 120V or 277V input voltage 208V 240V 347V 480V
Aux.
Controller
Wattage High (HW) Low Change (PC)
High Pressure Sodium
1000W 1100 616 44%
400W 465 215 54%
250W 300 151 50%
150W 196 118 40%
Dry
Contact – 2 +
• Front panel test switch provides same function as remote dry-contact switch
• CMOS timer maintains system in full brightness mode for a 15 minute warm-up period when power is applied
• Operating temperature 2°C (35°F)—55°C (131°F)