These instructions do not claim to cover all details or variations in the equipment, procedure, or process described, nor to provide directions for meeting every possible 
contingency during installation, operation or maintenance. When additional information is desired to satisfy a problem not covered sufficiently for user’s purpose, please 
contact your nearest representative.
INSTALLATION INSTRUCTIONS
IMPORTANT: Read carefully before installing fixture. Retain for future reference.
VAPOR-TIGHT 
WALL MOUNT
5/01 IMI-447
LUMARK       1121 HIGHWAY 74 SOUTH PEACHTREE CITY, GEORGIA 30269 5/01 IMI-447 ADH010709
FIXTURE
BLACK LINE (HOT) 
WHITE
NEUTRAL
GROUND
GREEN/GROUND
For Models: 
ICVW1 Series 
(200 Watt / 120 Volt) 1/2 NPS 
ICVW2 Series 
(300 Watt / 120 Volt) 3/4 NPS
Instructions:
• Disconnect all electrical power from the source as per the 
NEC.
➔ Turn off and lock circuit breakers and remove fuses
protecting the circuit.
• Complete connections as per the diagram and the NEC 
using approved methods and devices. Proper grounding 
must include ground screw and ground wire.
• A surface mounted fixture requires the use of caulking 
compounds to provide a moisture tight seal. Use RTV 
silicone sealant.
• Relamp with proper wattage lamp only -- allow fixture to 
cool for relamping.
➔ Lamps: (Sizes vary by manufacturer, so caution must 
be taken with Max Lamp Sizes stated.) 
ICVW1: 200W MAX; A21 MAX; 120V MIN 
ICVW2: 300W MAX; PS25 MAX; 120V MIN
• Min Supply Conductor Requirements.
ICVW1: 75ºC 
ICVW2: 90ºC
Applications:
• Suitable for operation in Ambients not exceeding 40ºC.
• Suitable for Wet Locations.
Warning:
• FAILURE TO FOLLOW INSTRUCTIONS MAY RESULT IN 
SERIOUS INJURY OR DEATH
• This fixture is not suitable for Hazardous 
or Classified Locations. Disconnect all 
electrical power before installation or 
servicing.
• Not for use above cooking equipment.
• This product must be installed in 
accordance with the applicable installation 
code by a person familiar with the 
construction and operation of the product 
and the hazards involved. Consult a 
qualified electrician to ensure correct 
branch circuit conductor.
Not Required in 
Some Applications
Mounts to Standard 
J-Boxes when 
Desired.
Ground Screw 
Connection when 
Standard J-Box 
Desired
Ground Screw