Cooper Lighting Lifeway II C User Manual

COOPER LIGHTING - SURE-LITES
LIGHTING INVERTERS
®
DIMENSIONS
DESCRIPTION
The Sure-Lites Lifeway II C Series is a single phase inverter that provides uninterrupted power. This pulse width modulated inverter utilizes IGBT technology and has a 2 millisecond transfer time. The unit’s operating efficiency is
A
98%, well above a typical fast transfer inverter. The C Series inverter is UL 924 Listed and meets NFPA 101 requirements by providing 90 minutes of illumination for emergency egress lighting. Other run times and voltages are
Height Width Depth
ABC
47" 30" 25"
SPECIFICATION DATA
B
C
available. Please consult your Cooper Lighting Representative.
Input Voltage 120 or 277VAC 1-phase 2 wire +10%-15%. Contact factory for all other voltages. Input Frequency 60Hz, ±3% Input Protection Input Circuit Breaker Input Harmonic Distortion <10% Input Power Factor 0.5 lag/lead Output Voltage 120 or 277VAC 1-phase 2 wire. Contact factory for all other voltages. Static Voltage Load current change ±2%, battery discharge ±12.5% Dynamic Voltage ±2% for ±25% load step change, ±3% for a 50% load step change, recovery within 3
cycles
Output Harmonic Distortion <3% THD for linear load Output Frequency 60 Hz. ±0.05Hz during emergency mode Load Power Factor 0.5 lag to 0.5 lead Inverter Overload 125% for 5 minutes Output Protection Optional Distribution Circuit Breakers Battery 10 Year Valve-regulated Sealed Lead Calcium (standard) Environmental
Altitude <10,000 feet without derating Operating Temp. System operates safely from 0° to 40°C (32° to 104°F) up to 95% humidity. UL rating,
20° to 30°C (68° to 86°F), includes battery performance wich can be affected by temperature. Contact factory for details.
Storage Temp. -20° to 70°C (Electronics Only) Humidity <95% (non-condensing)
LIFEWAY II
SINGLE PHASE
C SERIES
1.5-16.7 KVA
HID, Fluorescent and
Incandescent
ON-LINE POWER
INVERTER SYSTEMS
• Input 120 or 277VAC 1 phase 2 wire
• Custom voltages available
• Generator compatibility
• Forced air cooling only during emergency operation, no filters required
• 90 minute runtime standard; other runtimes available upon request
• 98% efficient PWM/IGBT technology with micro­processor control
• User programmable with password protection
• Self-Testing and Self­Diagnostic with Event, Test and Alarm Logs
• RS232 communications port
• UL 924 listed
LIFEWAY II SINGLE PHASE C SYSTEM PART NUMBER / RATING / MECHANICAL SPECIFICATIONS
Par t Pwr Rtg Pwr Rtg Effi c. Audible Heat Loss UPS Cabinet Dimensions UPS Battery Battery Battery Battery Cabinet Dimensions No. of Total Total Number kVA kW
ISC015 1.5 1.5 98 45 75 30/77 47/120 25/64 250/114 48 39 90 na2na ISC022 2.25 2.25 98 45 100 30/77 47/120 25/64 265/121 72 38 90 na2na ISC030 3.0 3.0 98 45 160 30/77 47/120 25/64 295/134 96 38 90 na2na ISC037 3.75 3.75 98 45 200 30/77 47/120 25/64 305/139 120 37 90 na2na ISC048 4.8 4.8 98 45 245 30/77 47/120 25/64 315/143 144 40 90 na2na ISC060 6.0 6.0 98 45 300 30/77 47/120 25/64 350/159 180 40 90 30/77 47/120 25/64 1 2 1670/759 ISC080 8.0 8.0 98 45 400 30/77 47/120 25/64 375/171 240 39 90 30/77 47/120 25/64 1 2 2087/949 ISC100 10.0 10.0 98 45 500 30/77 47/120 25/64 435/198 144 82 90 30/77 47/120 25/64 2 3 2631/1195 ISC125 12.5 12.5 98 45 660 30/77 47/120 25/64 465/211 180 82 90 30/77 47/120 25/64 2 3 3105/1409 ISC167 16.7 16.7 98 45 840 30/77 47/120 25/64 530/241 240 80 90 30/77 47/120 25/64 2 3 3954/1795
ORDERING INFORMATION
SAMPLE NUMBER: ISC037120120
@ full load Noise BTU Width Height Depth Weight Voltage Current Run Width Height Depth Battery No. of System
% db@1m in/cm in/cm in/cm lb/kg VDC Amperes Minutes in/cm in/cm in/cm Cabinets Cabinets
2
2
na
2
2
2
2
na21 546/249
2
na
na21 709/323
2
na
na21 887/403
2
na
na21 1045/475
2
na
na21 1203/546
Weight (lb/kg)
ISC
Series ISC=Single
Phase C
KVA Rating 015=1.5 022=2.25 030=3.0 037=3.75 048=4.8
060=6.0 080=8.0 100=10.0 125=12.5 167=16.7
Voltage Input 120 277
Voltage Output 120 277
Options
See page 693 for options
COOPER LIGHTING
691