Cooper Lighting HZX User Manual

COOPER LIGHTING - SURE-LITES
®
HZX SERIES
Hazardous Location Exit
EXIT LIGHTING
INDUSTRIAL & HAZARDOUS LOCATION Exit Signs
• 120 VAC input voltage
• Factory-sealed, explosion­proof housing of copper­free aluminum
• Impact-resistant white acrylic edgelit face panel with 6" high red letters
• Available in pendant­mount, wall-mount, or end­mount styles
• Two 60W, 60T10 clear lamps wired in parallel
• No provisions for battery operation
• Provides safe operation in the presence of volatile gases, vapor or dust
• Internal rectifier extends lamp life
• Relamping tool provided
• Listed per UL 844 for hazardous locations up to and including NEC Class I, Division 1, Groups C, D and Class II, Division 1, Groups E, F and G, Life Safety NFPA 101, NEC/OSHA, most state and local codes
DESCRIPTION
The Sure-Lites HZX Series Explosion-Proof Edgelit Exit signs are designed for use in locations classified as
DIMENSIONS
END
MOUNT
6"
(152mm)
WALL
MOUNT
4 3/8"
(111mm)
PENDANT
MOUNT
4 1/32"
(102mm)
15 1/2" (394mm)
hazardous due to the presence of flammable vapors, gasses or combustible dust. They are suitable for use in Class I, Division 1, Groups C and D, and Class II, Division 1, Groups E, F and G hazardous locations as defined by the National Electrical Code.
ORDERING INFORMATION
Model Number Mounting Style Sign Panel
HZX21 Wall Single Face HZX22 End Double Face HZX23 Pendant Double Face
NATIONAL ELECTRICAL CODE (NEC)
16 1/8"
(410mm)
16 7/8"
(429mm)
17 1/2"
(445mm)
The National Electrical Code (NEC) defines a hazardous location as “a location where fire hazards or explosion hazards may exist due to flammable gases or vapors, flammable liquids, combustible dust or ignitable fibers or filings.
The Code further separates these hazardous locations into three classes: Class I – locations containing gases and vapors Class II – locations containing dust Class III – locations containing fibers and filings. Each of these classes is broken into divisions. These divisions are separated into groups according to
characteristics.
The following chart summarizes these classifications:
Class Division Group
I Gas 1 Hazard Exists – Always present A Acetylene
II Dust 1 Hazard Exists E Conductive and Combustible Metal Dust
III Fibers 1 Production Areas Combustible
1 in atmosphere B Hydrogen and Manufactured Gases containing Hydrogen
2 Potential Exists – May be present A Acetylene
1 in atmosphere B Hydrogen and Manufactured Gases containing Hydrogen
2 Potential Exists F Combustible Carbon Dust
2 Handling/Storage Areas Combustible
C Petrochemicals D Petrochemicals
C Petrochemicals D Petrochemicals
G Non-Conductive Combustible Dust
666
COOPER LIGHTING
Energy Data
Input Current (Max.):
Model No. 120V 277V HZX21, HZX22, HZX23 120W 1.0A ZZ14=60T10 Halogen lamp 120V 60Watt