Cooper Lighting GC15132, GC15032, GC15042, GC15022, GC15182 User Manual

...
COOPER LIGHTING - SURE-LITES
EMERGENCY LIGHTS Architectural
®
DIMENSIONS
23 3/4" (603mm)
6 5/8"
(168mm)
5 3/4"
(146mm)
DESCRIPTION
The GC Series combines a clean, sleek, contemporary appearance with state-of-the-art electronics. Specifically designed for initial and retrofit
6 5/8"
(168mm)
installations where a recessed unit is desired to maximize aesthetics. The unit is ideal for locations with limited wall space and where panoramic
5 1/8"
(130mm)
positioning is necessary for the ceiling mounted lampholders to provide proper light distribution. Ideal for stores, offices, hospitals and school corridors.
ELECTRICAL RATINGS
Model Battery DC Voltage 1 1/2 hours 2 hours 3 hours 4 hours Type Wattage Number
GC15012 SLC 6 27 24 18 14 Incandescent 9 29-84 GC15022 SLC 6 54 48 36 28 Incandescent 9 29-84
GC15032 SLC 6 85 66 50 40 Incandescent 9 29-84
GC15042 SLC 12 36 30 20 16 Incandescent 9 29-86
GC15052 SLC 12 54 48 36 28 Incandescent 9 29-86
GC15122 SNC 6 15 12 8 6 Incandescent 7.2 29-88 GC15132 SNC 6 24 18 12 10 Incandescent 7.2 29-88
GC15142 SNC 6 48 36 24 20 Incandescent 7.2 29-88
GC15172 SNC 12 30 24 16 12 Incandescent 9 29-86
GC15182 SNC 12 48 36 24 20 Incandescent 9 29-86
SLC=Sealed Lead Calcium Battery SNC=Sealed Nickel Cadmium Battery
ORDERING INFORMATION
SAMPLE NUMBER: GC15012CL
Rated Wattage to 87 1/2% of rated D.C. Voltage Lamp Information
GC SERIES
Recessed Housing
Suspended Ceiling
EMERGENCY LIGHT
• Dual-voltage input 120/277VAC, 60Hz
• 20 gauge die-formed steel housing with white powder coat finish
• Two high-impact, fully adjustable thermoplastic heads
• Knockout, conduit or cord set
• Flanged for mounting in grid-type suspended ceilings
• Above ceiling access required for maintenance
Model Number GC15012 GC15022 GC15032 GC15042 GC15052 GC15122 GC15132 GC15142 GC15172 GC15182
Energy Data
Model No. 120V 277V
GC15012, GC15022, GC15032 .12A .05A GC15042, GC15052 .30A .13A
GC15122 .06A .03A GC15132 .07A .04A GC15142 .08A .05A GC15172 .13A .06A GC15182 .15A .07A
Options
(Add as suffix)
A=Ammeter CL=Cylinder Heads DR=Halogen Pinchback Designer
Heads
SD=Self-Diagnostics (GC15012,
GC15042, GC15052, GC15122, GC15132, GC15172, GC15182, Only)
TDM=Time Delay Monitor V=Voltmeter Alternate Lamps Other Options
(1)
(1)
Input Current (Max.):
Accessories
(Order separately)
VK1 =Voltmeter WG12 =Wire Guard WG17 =Wire Guard for use
with CL heads
• Single modular electrical connector
• Remote Capability
• Line-latching, Solid-State voltage limited charger, Solid-State switching, low­voltage disconnect, brownout circuit, overload/short-circuit protection, test switch/power indicator light
• UL 924 Listed, Life Safety NFPA 101, NEC/OSHA, most state and local codes
(1)
Consult your Cooper Lighting Representative.