Cooper Lighting CX User Manual

COOPER LIGHTING - SURE-LITES
EXIT SIGNS Architectural
®
DIMENSIONS
DESCRIPTION
The CX Surface Mounted Die
5 1/16" [129mm]
15/16" [24mm]
4 3/8"
[111mm]
Cast Aluminum Exit combines the strength and durability of die casting with the bright even illumination of LED lamp sources. Unlike competitive units that have a pronounced dot effect from protruding diodes, the CX LED offers
8 1/4"
(210mm)
unequalled uniform illumination and brightness. The CX Self-Powered LED comes standard with the Watchguard EMS self-diagnostic system insuring
12 5/8" [321mm]
ORDERING INFORMATION
SAMPLE NUMBER: CX7170RSD
2 1/4"
[57mm]
Self-Diagnostics
The self-diagnostic unit will automatically perform all tests required by UL924 and NFPA 101. The system indicates the status of the unit at all times using the LED indicator near the test switch on the side of the unit. A 90 minute battery power (emergency mode) simulation test will occur randomly once every six months.
fixture reliability and reducing maintenance costs.
CX
Family CX=Die Cast
Aluminum Exit
Series 6=AC Only, LED 7=Self-Powered,
LED
Face Options 1=Single 2=Double
Energy Data — Self-Powered Exits
LED Exits -Red Letters 2.8W 2.9W .03A .02A > .81 > .77 < 32% < 46% LED Exits -Green Letters 3.9W 3.6W .08A .04A > .41 > .43 < 48% < 49%
Battery Blank=No
Battery (CX6) 70=Nickel Cadmium Battery (CX7)
Letter Colors R=Red G=Green
Sealed Nickel Cadmium Battery
Input Power: Input Current (Max.): Power Factor: T.H.D.:
120V 277V 120V 277V 120V 277V 120V 277V
Housing Finishes Blank=
Brushed Aluminum Face with Black Housing
W=White B=Black
LED Exits
SD=Self-
Diagnostic *(CX7 only)
Options 2C=Two Circuit
Operation, FTBR (CX6 Only)
Accessories (Order Separately) CAX18PKBK=18" Pendant Kit,
Black
CAX18PKWH=18" Pendant Kit,
White
CAX18PKHTBK=18” Hang-True
Pendant Kit, Black
CAX18PKHTWH=18” Hang-True
Pendant Kit, White
VS1=Polycarbonate Vandal Shield
(Wall Mount Only)
VS1WP=Weather Resistant
Polycarbonate Vandal Shield (Wall Mount Only)
WG10=Wire Guard (Wall Mount
Only)
WGS11=Wire Guard (Ceiling or
End Mount Only)
CX SERIES
Die Cast
AC Only
Self-Powered
EXIT LIGHTING
• Dual-voltage Input 120/277 VAC, 60 Hz, isolation transformer
• Die cast aluminum housing
• Die cast canopy included
• LED Lamping
• Watchguard EMS Self-Diagnostic System (CX7 Only)
• Exit can be universally mounted ceiling, wall or end
• Universal pattern knock­outs on rear of single face housing for direct mounting to junction box
• NFPA 101 compliant knockout chevrons allow quick conversion to directional signs
• Self-powered Exits feature line-latching, solid-state voltage limited charger, low-voltage disconnect, brownout circuit, over­load/short-circuit protection, test switch/ power indicator light
• Damp Location Listed (AC Only), UL 924 Listed, CSA Certified, Life Safety NFPA 101, NEC/OSHA, Energy Star Listed, AC Only-UL FTBR when specified with the “2C” option, most state and local codes, suitable for floor proximity installation.
Energy Data — AC Only Exits
Input Power: Input Current (Max.): Power Factor: T.H.D.:
120V 277V 120V 277V 120V 277V 120V 277V
LED Exits
LED Exits -Red Letters 2.4W 2.5W .03A .02A > .78 > .73 < 33% < 48% LED Exits -Green Letters 3.2W 3.0W .08A .03A > .33 > .35 < 50% < 52%
COOPER LIGHTING
633