Cooper Lighting CC4, CC3, CC6, CC5 User Manual

COOPER LIGHTING - SURE-LITES
®
CC3
EMERGENCY LIGHTS Commercial
CC4 CC5 CC6
Contractor’s Choice
EMERGENCY LIGHT
• Dual-voltage input 120/277VAC, 60Hz, isolation transformer
• Injection-molded, color­stable, high-impact UL-94-5V rated polycarbonate housing and mounting plate (Housing is tethered to mounting plate)
• Designer-white textured finish
• Two PAR36 type lamps in fully adjustable high-impact polycarbonate lampholders
DESCRIPTION
The CC Series Contractor’s Choice Emergency Lighting Unit is the ideal
DIMENSIONS
13"
(330mm)
choice when a simple installation and a reasonable cost are required. Its contemporary round corner styling,
6 3/8"
(162mm)
designer white finish, and consistent family appearance enables it to blend with any decor. The components are
17 1/2"
(445mm)
injection molded from tough polycarbonate materials which resist discoloration due to age and ultraviolet radiation.
Model DC Voltage 1 1/2 hours 2 hours 3 hours 4 hours Type Wattage Number
CC3 6 10.8 7.2 - - Incandescent 5.4 29-121 CC3 NC 6 16 - - - Incandescent 5.4 29-121 CC4 6 18 15 10 8 Incandescent 9 29-84 CC4 NC 6 18 Incandescent 9 29-84 CC5 6 27 24 18 14 Incandescent 9 29-84 CC5 NC 6 24 Incandescent 9 29-84 CC6 6 32 - - - Incandescent 9 29-84
ORDERING INFORMATION
SAMPLE NUMBER: CC5WHSD
Rated Wattage to 87 1/2% of rated D.C. Voltage Lamp Information
SURE-LITES
4 3/4"
(121mm)
• Sealed lead calcium maintenance free battery
• Cutouts provided for surface conduit on top
• Universal J-box mounting pattern, keyhole slots
• Remote Capability CC5, CC6
• Line-Latching, Solid-State Voltage Limited Charger, Solid-State Switching, Low­Voltage Disconnect, Brownout Circuit, Overload/Short Circuit Protection, Test switch/power Indicator light
• UL 924 Listed, UL Damp Location Listed (CC5SD Only), Life Safety NFPA 101, CSA Certified, NEC/OSHA, most state and local codes
616
COOPER LIGHTING
Model Number CC3 CC3NC CC4 CC4NC CC5 CC5NC CC6
Energy Data
Housing Finish
(Must be
(4)
specified)
WH=White
(4), (6)
BK=Black
(4), (6)
Voltage Blank= 347=120/347 VAC
120/277
Input Current (Max.):
Model No. 120V 277V 347V
CC3 .12A .05A .01A
CC4 .12A .05A .01A
CC5 .13A .06A .06A
CC6 .13A .06A .06A
(1)
Provision for one meter only.
damp location standard.
(2)
Consult your Cooper Lighting Representative.
(6)
CC4NC, CC5NC not available in SD.
Options
(add as suffix) MRT=MR16 Heads (5W
Standard CC3, CC3NC; 9W Standard CC4, CC5, and CC6)
SQ=Square Head (5.4W
Standard)
A= Ammeter SD=Self-Diagnostics V=Voltmeter TDM=Time Delay Monitor Alternate Lamps Other Options
(1)
(3), (5), (6)
(1)
(2)
(2)
Accessories
(Order separately)
WG1 =Wire Guard WG2 =Wire Guard (use
for heads adjusted at 45° or greater) VS1=Polycarbonate
Vandal Shield
VS1WP=Polycarbonate
Vandal Shield Weather Resistant
CSK120=Cord Set 120V
(3)
Not available w/CC6.
(4)
NC=Nickel Cadmium Battery.
(5)
CC5SD is
Loading...