Cooper Lighting CC11, CC9, CC12, CC10 User Manual

COOPER LIGHTING - SURE-LITES
EMERGENCY LIGHTS Commercial
®
DESCRIPTION
DIMENSIONS
The Contractor’s Choice FasTest™ Ultra High-Capacity Emergency Lighting Units are an affordable, yet attractive, alternative to standard two-headed emergency lighting units. All components snap together to facilitate installation in 5 minutes or less. Field versatility is not sacrificed for cost, both
TABLE OF CONTENTS
lighting heads offer horizontal and vertical adjustability. Moreover, proper operation of the transfer circuit and emergency lamps can be quickly and safely verified by using a convenient laser pointer (sold as an accessory). In addition, Watchguard EMS self diagnostic system is standard.
The CC Series Ultra High-Capacity Emergency Lighting Units are ideal for applications that demand the minimum cost but also require maximum flexibility, reliability and convenience in an attractive unit.
Verify proper operation of the transfer circuit and emergency lamps with convenient laser pointer (sold as an accessory).
ELECTRICAL RATINGS
Rated Wattage to 87 1/2% of Rated D.C. Voltage
Model DC Voltage 1 1/2 Hours Remote Capability
CC9SD 12 160 136W CC10SD 12 200 176W CC11SD 12 240 216W CC12SD 12 300 276W CC9SDMRT 12 160 136W CC10SDMRT 12 200 176W CC11SDMRT 12 240 216W CC12SDMRT 12 300 276W
ORDERING INFORMATION
SAMPLE NUMBER: CC9SDMRT2142SM
Options (add as suffix) Accessories (order separately)
Model Number CC9SD CC10SD CC11SD CC12SD
SQ=Square Head (12W Standard) MRT=MR16 Heads (12W Standard) Alternate Lamps -
lamp number (from Technical Information section) and mounting location (below), e.g. CC9SD2134SM319TM219BM
SM=Side Mount Heads
(2 lamp max.)
TM=Top Mount Heads (3 lamp max.)
Specify quantity,
BM=Bottom Mount Heads
(3 lamp max.)
Electrical Options A=Ammeter V=Voltmeter TDM- Time Daily Monitor CSK120=120V Cord Set CSK277= 277V Cord Set Other Options: Consult Cooper
12”
[305mm]
9 7/8”
[250mm]
Lighting Representative
21 11/16” [551mm]
19”
[483mm]
8 7/16”
[214mm]
Self-Diagnostics
The self-diagnostic unit will automatically perform all tests required by UL924, and NFPA
101. The system indicates the status of the exit at all times using the LED indicator near the test switch on the side of the unit. A 90 minute battery power (emergency mode) simulation test will occur randomly once every six months.
Lamp Information
Type Wattage Number Spacing
Incandescent 12 ea. 029-132 24' Incandescent 12 ea. 029-132 24' Incandescent 12 ea. 029-132 24' Incandescent 12 ea. 029-132 24' MR16 12 ea. 029-141 50’ MR16 12 ea. 029-141 50’ MR16 12 ea. 029-141 50’ MR16 12 ea. 029-141 50’
LASER=Key Chain, Red Laser Pointer
(activation tested at 30 feet)
VS1=Polycarbonate Vandal Shield VS1WP=Polycarbonate Vandal Shield
Weather Resistant
WG3=Wire Guard 2MSWH=Mounting Shelf
Contractor’s Choice Ultra High Capacity
EMERGENCY LIGHT
• Dual-Voltage Input 120/277 VAC, 60 Hz
• Injection-Molded, Color­Stable, High-Impact UL 94-5V Rated Polycarbonate Housing and Mounting Plate
• Designer white textured finish
• Maintenance Free Sealed Lead Calcium Battery
• Housing Has (8) Locations
(3)
for Mounting of Heads; Consult Factory (3 optional bottom-mount and 3 optional top- mount locations)
• Knockouts/Cutouts Provided in Housing for Surface Conduit Attachment
• Watchguard EMS self diagnostic system
• Remote Photocell Test Switch with Automatic 30-Sec. Test Upon Switch Activation
• Line-Latching, Solid-State Voltage Limited Charger, Solid-State Switching, Low­Voltage Disconnect, Brownout Circuit, Overload/Short Circuit Protection, Push-Button Test Switch/Power Indicator Light
• UL 924, Life Safety NFPA 101, NEC/OSHA, Most State and Local Codes
CC9 CC10 CC11 CC12
(1)
The "Rule of Thumb" spacing guidelines are designed to achieve 1 foot-candle average and 0.1 foot-candle minimum with a 40:1 maximum/minimum ratio. The corridor used is 100 feet long, 9 feet ceiling with a 6 feet wide walkway and 3 feet path of egress. The reflectances are 80% ceiling, 50% walls and 20% floors. The fixture mounting height is 7.0 feet with a lamp head angle of 45 degrees. Cooper Lighting assumes no responsibility for local requirements or specific project variables. This is a guideline to be used as a design aid, not as guarantee of any code compliance.