Cooper Lighting AEL1SD User Manual

COOPER LIGHTING - SURE-LITES
®
ARCHITECTURAL EMERGENCY
EMERGENCY LIGHTS Architectural
LIGHT SERIES
DIE CAST ALUMINUM
Emergency Light
• Dual-voltage input 120/277VAC, 60Hz
• Die cast aluminum housing with powder coat finish
DESCRIPTION
The Sure-Lites Architectural Emergency Light is designed to provide superior illumination while blending into the surrounding space. The housing is constructed of die cast aluminum with an integral refractive polycarbonate lens. The emergency light’s advanced optical design in conjunction with high output Xenon lamps provide maximum path of egress lighting performance. The Sure-Lites Architectural Emergency Light is listed for temperatures between ­20°C and 40°C (-4°F and 104°F) and has silicone gaskets that provide protection from moisture and rain. [Remote unit temperature range: -40°C and 65°C (-40°F and 149°F)] Standard features include Watchguard EMS self-diagnostic system which meets NFPA 101 testing requirements and a FasTest photocell which enables remote testing of the emergency light.
DIMENSIONS
10 7/8”
[276.23mm]
3 7/8”
[98.43mm]
7”
[177.8mm]
Self-Diagnostics
The self-diagnostic unit will automatically perform all tests required by UL924, and NFPA
101. The system indicates the status of the exit at all times using the LED indicator near the test switch on the side of the unit. A 90 minute battery power (emergency mode) simulation test will occur randomly once every six months.
• Three 6V 6W High output Xenon lamps
• Sealed Nickel Cadmium Battery Maintenance Free, Long Life, Full Recharge time, 24 Hours
• Watchguard EMS Self­Diagnostic System
• Photocell Test Switch (requires accessory LASER for activation)
• Universal Pattern Knockouts on rear of housing for direct mounting to junction box
• UV Stable Polycarbonate Lens
• Line-Latching, Solid-state Voltage Limited Charger, Low-Voltage Disconnect, Brownout Circuit, Overload/Short Circuit Protection, Test Switch/Power Indicator Light
• UL 924 Listed Self­Diagnostics, UL Outdoor Wet Location Listed (suitable for wet and damp locations), Life Safety NFPA 101, NEC/OSHA, Most State and Local Codes
ELECTRICAL RATINGS
Rated Wattage to 87 1/2% of Rated D.C. Voltage Lamp Information
Model DC Voltage 1 1/2 Hours
AEL1SD 6 18
ORDERING INFORMATION
SAMPLE NUMBER: AEL1SD
AEL1
Family AEL1=Architectural
Emergency Light
ENERGY DATA
AEL1SD
Input Current (Max.)
120V = .10A 277V = .07A
Housing Finishes
Blank=Silver
BK=Black BZ=Bronze WH=White
SD=Self Diagnostics
AEL1WHSD
(Standard)
Type Wattage Number Spacing
Xenon 6 each 11549423 30.0'
Options TDM=Time Delay
Monitor
Remote=Remote
AEL1BKSD
Unit
Accessories (order separately)
LASER=Key Chain, Red Laser
Pointer (activation tested at 15 feet)
AEL1BZSD
1
602
COOPER LIGHTING
(1)
The "Rule of Thumb" spacing guidelines are designed to achieve 1 foot-candle average and 0.1 foot-candle minimum with a 40:1 maximum/minimum ratio. The corridor used is 100 feet long, 9 foot ceiling with a 6 foot wide walkway and 3 foot path of egress. The reflectances are 80% ceiling, 50% walls and 20% floors. The fixture mounting height is 8.5 feet. Cooper Lighting assumes no responsibility for local requirements or specific project variables. This is a guideline to be used as a design aid, not as guarantee of any code compliance.