Cooper Lighting 1483 User Manual

DIMENSIONS DESCRIPTION
A
B
The Fail-Safe CFS Series is designed for use in non-
A
laminar air flow clean rooms. This surface mounted clean room luminaire has a hole-free design and is enclosed and
B
gasketed to protect against infiltration of particles and airborne bacteria. The sealed
MOUNTING DOOR FRAME
housing and door frame allow relamping without contamination of the clean
B
areas. An emergency battery pack is available as an option. These luminaires are U.L. listed and C.S.A. certified for wet
C
locations and are manufactured in accordance with U.S.D.A.
ABC
CFS 4 5/16" 11 11/16" 24"
1' x 2' (110mm) (297mm) (610mm) CFS 4 5/16" 11 11/16" 48" 1' x 4' (110mm) (297mm) (1219mm) CFS 4 5/16" 23 11/16" 24" 2' x 2' (110mm) (602mm) (610mm) CFS 4 5/16" 23 11/16" 48" 2' x 4' (110mm) (602mm) (1219mm)
and F.D.A. All fixtures have been tested and reported in compliance with Federal Standard 209E, Class 100 (M3.5). 200 PSI Rating is standard.
FAIL-SAFE
CFS
14W-160W
Fluorescent
1' x 2', 1' x 4', 2' x 2', 2' x 4'
FLUORESCENT SURFACE
ONE-PIECE DOOR
• Lens is clear extruded with prisms positioned inside fixture and smooth surface on the outside for easy cleaning
CLEANROOM
®
ORDERING INFORMATION
SAMPLE NUMBER: CFS-24-440-120-IP12-LE3-SSP-EBP
Series CFS=Fluorescent
Surface Type
Width 12=12" (3 Lamps Max.) 24=24"
Lamp Type
2' Fixture Length
T5 Fluorescents 114=(1) 14W Lamp 214=(2) 14W Lamps 314=(3) 14W Lamps 414=(4) 14W Lamps 124=(1) 24W HO Lamp 224=(2) 24W HO Lamps 324=(3) 24W HO Lamps 424=(4) 24W HO Lamps
T8 Fluorescents 217=(2) 17W Lamps
417=(4) 17W Lamps
T12 Fluorescents 220=(2) 20W Lamps 420=(4) 20W Lamps
Biaxial Fluorescents 240BX=(2) 40W Lamps 340BX=(3) 40W Lamps
Number of Lamps
1,2,3,4
4' Fixture Length
T5 Fluorescents 128=(1) 28W Lamp 228=(2) 28W Lamps 328=(3) 28W Lamps 428=(4) 28W Lamps 154=(1) 54W HO Lamp
=(2) 54W HO Lamps
254 354
=(3) 54W HO Lamps
454
=(4) 54W HO Lamps
T8 Fluorescents
232=(2) 32W Lamps 332=(3) 32W Lamps 432=(4) 32W Lamps
T12 Fluorescents 240=(2) 40W Lamps 340=(3) 40W Lamps 440=(4) 40W Lamps
Voltage 120=120V 277=277V UNV=120V
Lens Type IK12=K-12 Prismatic
IP12=K-12 Prismatic
KSH2 5
93=Prismatic
(3)
through 277V
Acrylic
Polycarbonate
1
=Bat Wing
Distribution
Tempered Glass
3
Ballast LE3=Energy
Saving Ballast for use with T12 Lamp
LEOC8=Energy
Saving Ballast for use with T8 Lamp
Electronic
2
Ballast EB51=(1) Ballast
for use with T5 Lamp
EB52=(2) Ballasts
for use with T5 Lamp
EB81=(1) Ballast
for use with T8 Lamp
EB82=(2) Ballasts
for use with T8 Lamp
EB21=(1) Ballast
for use with T12 Lamp
EB22=(2) Ballasts
for use with T12Lamp
EBX1=(1) Ballast
for use with Biaxial Lamp
EBX2=(2) Ballasts
for use with Biaxial Lamp
Door/Finish Options CRP=CRS/Polyester
Powder Finish
SSN=Stainless Steel
Door/ Brushed 304 Finish
SSP=Stainless Steel
Door/Polyester Powder Coat Finish
ALP=Formed
Aluminum Door/Polyester Powder Finish
ALX=Extruded
Aluminum/ Anodized
ALXP=Extruded
Aluminum/ Polyester Powder Coat Finish
4
4
Options EBP=Emergency
Battery Pack
GLR=Fuse and
Holder
RIF=Radio
Frequency Interference Filter
DSL1=Digital
Lighting System Dimming. See DLS Section for details.
Housing Options SHN=Stainless
Steel, Brushed 304 Finish
SHP=Stainless
Steel, Polyester Powder Finish
ALH=Aluminum,
Polyester Powder Finish
• Flush mounted, stainless steel machine screws
• Die-formed, 20 ga. CRS housing contains no holes . Standard white high reflectance polyester powder coat finish
• Unique, Particulock™ lens retention system utilizes continuous, 18 ga. media clampdowns
• Two braided, stainless steel cables on one side of door provide hinging
• One-piece, 18 ga., fully gasketed, outside door with die-formed and beveled edges
• Standard Class P, CBM/ETL ballast
• White, closed cell, Flexiseal™ triple gasketing system
• Gasketed access plate with two flattened, 7/8" diameter knockouts
NOTES: For additional options, consult your Cooper Lighting Representative. Specifications and Dimensions subject to change without notice.
1
The KSH25 provides improved visual performance and wide angle distribution. This lens has an integral prism pattern designed so that prisms face the lamp cavity and still supply superior photometrics. Highly recommended for all high tech manufacturing environments. For specific electronic ballast, specify brand and catalog number. 3Products also available in non-US voltages and 50Hz for international markets. Consult your Cooper Lighting Representative for availability and ordering information.
4
Not rated for 200 PSI hose down.
2
COOPER LIGHTING
1483
Loading...