Cooper Instruments DFI-INFINITY CS Installation Manual

DFI INFINITY CS
STRAIN METER/CONTROLLER
USER’S GUIDE
www.cooperinstruments.com
PH: 540-349-4746 FAX: 540-347-4755
CONTENTS
PREFACE ....................................................................................................................................1
1.0 INTRODUCTION....................................................................................................................2
1.1 Unpacking........................................................................................................................................2
1.2 Safety Considerations....................................................................................................................2
2.0 ABOUT THE METER .............................................................................................................3
2.1 Description ......................................................................................................................................3
2.2 Features...........................................................................................................................................3
2.3 Available Accessories....................................................................................................................3
2.4 Front of the Meter ...........................................................................................................................4
2.5 Back of the Meter............................................................................................................................5
2.6 Disassembly....................................................................................................................................6
3.0 GETTING STARTED..............................................................................................................7
3.1 Rating/Product Label......................................................................................................................7
3.2 Main Board Power Jumpers (Refer To Figure 3-1).......................................................................7
3.3 Panel Mounting ...............................................................................................................................9
3.4 Connecting Sensor Inputs .............................................................................................................9
3.5 Connecting Main Power ...............................................................................................................11
3.6 Connecting External Tare Switch................................................................................................12
3.7 Connecting Analog and Relay Outputs ......................................................................................12
4.0 CONFIGURING THE METER...............................................................................................14
4.1 Selecting the Input Type ...................................................................................................14
4.2 Selecting a Decimal Point Position ..................................................................................14
4.3 Using Reading Scale and Offset .....................................................................................14
4.3.1 Scaling with Known Loads (On-Line Calibration)...............................................................14
4.3.2 Scaling without Known Loads..............................................................................................16
4.4 Using Reading Configuration ...........................................................................................16
4.4.1 Selecting Ratiometric/Non-Ratiometric Operation..............................................................17
4.4.2 Setting Input Resolution........................................................................................................17
4.4.3 Displaying the Filtered/Unfiltered Input Signal ...................................................................17
4.4.4 Selecting Gross/Net or Peak Display ...................................................................................17
4.5 Selecting a Display Color .............................................................................................18
4.6 Using Setpoint 1 Configuration .......................................................................................18
4.6.1 Setting Setpoint 1’s Active Band..........................................................................................18
4.6.2 Selecting if Setpoint 1 is Latched of Unlatched..................................................................18
4.6.3 Assigning Setpoint 1 Values to Net or Gross Readings.....................................................18
4.7 Using Setpoint 2 Configuration .......................................................................................19
4.7.1 Setting Setpoints 2’s Active Band........................................................................................19
4.7.2 Selecting if Setpoint 2 is Latched or Unlatched..................................................................19
4.7.3 Assigning Setpoint 2 Values to Net or Gross Readings.....................................................19
4.8 Setting the Setpoint 1 Deadband .....................................................................................19
4.9 Setting the Setpoint 2 Deadband .....................................................................................20
4.10 Using Output Configuration ...........................................................................................21
4.10.1 Enabling or Disabling the Analog Output..........................................................................21
4.10.2 Selecting Analog Output as Current or Voltage................................................................21
4.10.3 Selecting Analog Output or Proportional Control.............................................................21
4.11 Using Output Scale and Offset .....................................................................................21
4.11.1 Examples for Output Scale and Offset...............................................................................22
4.12 Using Lock Out Configuration .......................................................................................23
4.12.1 Enabling or Disabling the RESET button in the Run Mode..............................................23
4.12.2 Enabling or Disabling the SETPOINT Changes.................................................................23
4.12.3 SETPOINT Display Function: Firmware version or Setpoint value ................................23
4.13 Using Display Brightness Configuration ............................................................................23
4.13.1 Changing Brightness Level.................................................................................................23
5.0 DISPLAY MESSAGES.........................................................................................................24
6.0 MENU CONFIGURATION DISPLAYS.................................................................................25
7.0 SETPOINT CONFIGURATION DISPLAYS..........................................................................28
8.0 SPECIFICATIONS................................................................................................................28
9.0 FACTORY PRESET VALUES..............................................................................................31
10.0 CE APPROVALS INFORMATION.....................................................................................31
WARRANTY REPAIR POLICY..................................................................................................32
DFI INFINITY CS (V- M3598/N/0906) iii CF 70
PREFACE
Manual Objectives This manual shows you how to set up and use the Programmable Digital Meter.
Standard Procedures:
Checking voltage jumpers, or changing voltage power
Mounting the panel
Selecting the input type
Selecting a decimal point position
Scaling with known loads (on-line calibration)
Scaling without known loads
Selecting ratiometric/non-ratiometric operation
Displaying the filtered/unfiltered input signal
Selecting a display color
Setting the setpoint’s active band
Selecting a latched or unlatched operation
Setting setpoint deadbands
Enabling/disabling setpoint changes
Enabling/disabling the RESET button in the Run Mode
Optional Procedures:
Setting input resolution
Enabling/ disabling analog output
Selecting analog output as current or voltage
Assigning the output to net/gross reading
Scaling analog output
Features with segment characters shown are for the “B” version.
are for the “B” version which has three-color programmable “Big” LED display – All
For first-time users: Refer to the QuickStart Manual for basic operation and set-up instructions.
Table A-1 Sections of the Manual
IF YOU WANT TO READ ABOUT: REFER TO SECTION
Unpacking; safety considerations 1 Introduction Meter description and features 2 About the Meter Main board power jumpers; panel mounting, sensor input, main power and analog and relay output Input type; decimal point position; reading scale & offset; reading configuration; display color; setpoint configuration; setpoint deadbands; output configuration (analog output); analog output scaling; lock out configuration; display brightness Display messages 5 Display Messages Meter menu/sub-menu messages 6 Menu Configuration Setpoint configuration messages 7 Setpoint Configuration Displays Specifications 8 Specifications Factory Preset Values 9 Factory Default Setup as Shipped
NOTES, WARNINGS and CAUTIONS
Information that is especially important to note is identified by three labels:
NOTE
WARNING
CAUTION
IMPORTANT
3 Getting started 4 Configuring the Meter
DFI INFINITY CS (V- M3598/N/0906) 1 CF 70
NOTE: provides you with information that is important to successfully setup and use the Programmable Digital Meter.
CAUTION or WARNING: tells you about the risk of electric shock. CAUTION, WARNING or IMPORTANT: tells you of circumstances or practices that can affect the meter’s
functionality and must refer to accompanying documents.
TIP: provides you helpful hints.
1.0 INTRODUCTION
1.1 Unpacking
Remove the Packing List and verify that all equipment has been received. If there are any questions about the shipment, please call Cooper Instruments at 1-800-344-3921.
Upon receipt of shipment, inspect the container and equipment for any signs of damage. Take particular n ote of any evidence of rough handling in transit. Immediately report any damage to the shipping agent.
The carrier will not honor any claims unless all shipping material is saved for their examination. After examining and removing contents, save packing material and carton in the event reshipment is necessary.
Verify that you receive the following items in the shipping box:
QTY DESCRIPTION
Programmable Digital Meter indicator/controller with all applicable connectors attached.
1
Owner’s Manual
1
Set Mounting brackets
1
If you ordered any of the available options, they will be shipped in a separate container to avoid any damage to your indicator/controller.
1.2 Safety Considerations
This device is marked with the international caution symbol. It is important to read this manual before installing or commissioning this device as it contains important information relating to Safety and EMC (Electromagnetic Compatibility).
This instrument is a panel mount device protected in accordance with EN 61010-1:2001, electrical safety requirements for electrical equipment for measurement, control and laboratory. Installation of this instrument should be done by qualified personnel. In order to ensure safe operation, the following instructions should be followed.
This instrument has no power-on switch. An external switch or circuit breaker shall be included in the building installation as a disconnecting device. It shall be marked to indicate this function, and it shall be in close proximity to the equipment within easy reach of the operator. The switch or circuit-breaker shall not interrupt the Protective Conductor (Earth wire), and it shall meet relevant requirements of IEC 947-1 and IEC 947-3 (International Electrotechnical Commission). The switch shall not be incorporated in the main supply cord.
Furthermore, to provide protection against excessive energy being drawn from the main supply in case of a fault in the equipment, an overcurrent protection device shall be installed.
Do not exceed voltage rating on the label located on the top of the instrument housing.
Always disconnect power before changing signal and power connections.
Do not use this instrument on a work bench without its case for safety reasons.
Do not operate this instrument in flammable or explosive atmospheres.
Do not expose this instrument to rain or moisture.
Unit mounting should allow for adequate ventilation to ensure instrument does not exceed operating
temperature rating.
DFI INFINITY CS (V- M3598/N/0906) 2 CF 70
Use electrical wires with adequate size to handle mechanical strain and power requirements. Install without exposing bare wire outside the connector to minimize electrical shock h azards.
EMC Considerations
Whenever EMC is an issue, always use shielded cables.
Never run signal and power wires in the same conduit.
Use signal wire connections with twisted-pair cables.
Install Ferrite Bead (s) on signal wires close to the instrument if EMC problems persist.
Failure to follow all instructions and warnings may result in injury!
2.0 ABOUT THE METER
2.1 Description
The Digital Programmable Strain meter is a value packed indicator/controller. Four full digits and broad scaling capability allow for a display in virtually all engineering units. A wide variety of DC current and voltage input ranges cover typical strain applications. Standard features include sensor excitation and front panel or remote tare. Your meter may be a basic indicator or it may include analog output or dual relay output. Analog or dual relay output must be ordered at time of purchase. Analog output is fully scalable and may be configured as a proportional controller, or to follow your display. Dual 5 amp, form C relays control critical processes. A mechanical lockout has been included to guard against unauthorized changes.
2.2 Features
The following is a list of standard features:
4-digit, three color Programmable, Big LED display or 4-digit, Standard LED display
NEMA 4 Front Bezel
±0.03 % accuracy
8 DC input ranges: 0-100 mV, ±50 mV, 0-5 V, 1-5 V, 0-10 V, ±5 V, 0-20 mA, and 4-20 mA
5,10,12, or 24 Vdc sensor excitation
Peak detection
Front panel and remote tare function
Nonvolatile memory-no battery backup
115 or 230 Vac 50/60 Hz power supply or
10 – 32 Vdc or 26-56 Vdc
The following is a list of optional features:
Dual 5 amp, form C relay output
Scalable analog output
Proportional control
Easy setup for proportional control
2.3 Available Accessories
Table 2-1 Accessories and Add-Ons
Add-On Options
FS Special Calibration/Configuration SPC4 NEMA-4 Splash proof Cover SPC18 NEMA-4 Splash Proof Cover, NEW
Accessories
TP1A Trimplate panel adaptor - Adapts DIN1A/DIN2A cases to larger panel cutouts RP18 19-in. Rack Panel for one (1) 1/8 DIN instrument RP28 19-in. Rack Panel for two (2) 1/8 DIN instruments
DFI INFINITY CS (V- M3598/N/0906) 3 CF 70
RP38 19-in. Rack Panel for three (3) 1/8 DIN instruments
2.4 Front of the Meter
Figure 2-1 shows each part of the front of the three-color programmable “Big” LED display Meter (Version
B).
Digital LED Display:
-1.9.9.9 or 9.9.9.9 4-digit three color programmable, 21 mm (0.83”) high LED display with programmable decimal point.
Figure 2-1 Front-Panel with Big Display
Figure 2-2 shows each part of the front of the standard LED display meter.
Digital LED Display:
-1.9.9.9 or 9.9.9.9 14 segment, 13.8 mm (0.54”) high LED display with programmable decimal point.
Figure 2-2 Front-Panel with Standard Display
These meter display windows (both versions) light when appropriate: 1 Setpoint 1 status 2 Setpoint 2 status
5 Pushbuttons for programming the meter.
METER BUTTONS SETPTS Button
In the Run Mode, this button will sequentially recall the previous setpoint settings. As necessary, use the S/NT/GRS and X/TARE buttons to alter these settings, and then press the SETPTS button to store new values.
Unless you press the SETPTS, X/TARE, or SNT/GRS button within 20 seconds, the meter will scroll to setpoint 2 and then to the Run Mode.
If the dual relay option is not installed, or if SETPTS button will display the meter’s firmware version.
S/NT/GRS Button In the Run Mode, this button will toggle between net/gross readings or peak readings, depending upon setup.
In the Configuration Mode, press this button to change the value of the flashing digit shown on the display and/or toggle between menu choices, such as
or on menu . When configuring your setpoint
values, press the S/NT/GRS button to advance the flashing digit’s value from 0 to 9 by 1.
X/TARE Button In the Run Mode press the X/TARE button to tare your reading (zeroing).
In the Configuration Mode, press this button to scroll to the next digit.
is displayed on the menu, pressing the
DFI INFINITY CS (V- M3598/N/0906) 4 CF 70
MENU Button In the Run Mode, press the MENU button to terminate the current measuring strain and enter you into the Configuration Mode.
Only if you have not installed the lock out jumpers on the main board.
In the Configuration Mode, press the MENU button to store changes in the nonvolatile memory and then advance you to the next menu item.
RESET Button If you hard reset (press the MENU button followed by the RESET button) or power off/on the meter, it shows followed by
.
In the Run Mode, press the RESET button to reset the latched setpoints. The meter shows
and returns to
the Run Mode. In the Configuration Mode, press the RESET button once to review the previous menu. Press the RESET button
twice to perform a hard reset and return to the Run Mode. In the Peak Mode, press the RESET button to reset peak values. The meter shows and returns to the Run
Mode.
In the Setpoint Mode, press the RESET button to reset the latched setpoint. The meter shows
and enters
the Run Mode. In the Tare Mode, press the RESET to reset. The meter shows
.
When in setpoint or Configuration Mode, if the meter shows 9999 or –1999 with all flashing digits, the value has overflowed. Press the S/NT/GRS button to start a new value.
2.5 Back of the Meter
,
Figure 2-3 shows the label describing the connectors on the back of the meter. Table 2-2 on the following page gives a brief description of each connector at the back of the meter.
Figure 2-3 Connectors (AC-Powered and DC-Powered Detail)
DFI INFINITY CS (V- M3598/N/0906) 5 CF 70
Table 2-2 Connector Description
Connector Description
TB1-1 TB1-2 TB1-3 TB1-4 TB1-5 TB1-6 TB1-7 TB1-8 TB1-9 TB1-10 TB1-11 TB1-12
TB2-1 TB2-2 TB2-3 TB2-4 TB2-5 TB2-6 TB2-7 TB2-8
TB5-1 TB5-2 TB5-3
J1 (1-2) Remote tare connection with a momentary switch The DIP switches are located at the S1 position (Refer to Figure 3-2). Use a small instrument such as a paper clip
to change the switches from open to closed. Table 2-3 lists DIP switch settings at the S1 position required to complete the setup of your meter.
Function
C= Closed O= Open
Internal 5/10/12 excitation External 5/10/12 excitation Internal 12 Vdc Excitation Internal 10 Vdc Excitation Internal 5 Vdc Excitation
0-100 mV dc ±50 mV dc ±5 Vdc 0-10 Vdc 0-20 mA dc
Setpoint 1: Normally open (N.O.1) connection Setpoint 1: Normally closed (N.C.1) connection Setpoint 1: Common (COM1) connection Setpoint 2: Normally open (N.O.2) connection Setpoint 2: Normally closed (N.C.2) connection Setpoint 2: Common (COM2) connection AC line connection (no connections on DC-powered units) AC neutral connection (+ Input on DC-powered units) AC earth ground (DC-power return on DC-powered units) Analog voltage output Analog current output Analog return
-E: Negative excitation connection from meter (5,10,12 V) +E: Positive excitation connection from meter (5,10,12 V) +20 mA connection for analog input +R (Not used) +24 V output connection +S: Positive signal input
-S: Negative signal input and return for +20 mA or +24 V
-R (Not used) Isolated Analog Voltage Output
Isolated Analog Current Output Isolated Analog Output Return
Table 2-3 DIP Switch Positions/Input Range & Excitation
S1 DIP Switch Positions
1 2 3 4 5 6 7 8
Settings for Excitation Voltage
C - - - - - - ­O - - - - O O ­C - - - - O O ­C - - - - C O ­C - - - - C C -
Settings for Input Ranges
-
-
-
-
-
O O C C O
C C O O C
O O O O C
O C C O O
-
-
-
-
-
-
-
-
-
-
O O C C O
The display must also be configured to the selected input type after setting the DIP switches (see Section
4.1, Selecting the Input Type)
2.6 Disassembly
You may need to open up the meter for one of the following reasons:
DFI INFINITY CS (V- M3598/N/0906) 6 CF 70
To check or change the 115 or 230 Vac power jumpers.
To install or remove jumpers on the main board.
Disconnect the power supply before proceeding.
To remove and access the main board, follow these steps:
Disconnect main power from the meter.
Remove the back case cover.
Lift the back of the main board upwards and let it slide out of the case.
3.0 GETTING STARTED
Caution: The meter has no power-on switch, so it will be in operation as soon as you apply power.
If you power off/on the meter, or perform a hard reset (press the RESET button twice), the meter shows followed by
.
3.1 Rating/Product Label
This label is located on top of the meter housing (refer to Figure 3-4).
3.2 Main Board Power Jumpers (Refer To Figure 3-1)
Important: If you want to change the Factory preset jumpers, do the following steps, otherwise go to Section 3.3. Warning: Disconnect the power from the unit before proceeding. This device must only be reconfigured
by a specially trained electrician with corresponding qualifications. Failure to follow all instructions and warnings may result in injury!
1. Remove the main board from the case. Refer to Section 2.6.
2. Locate the solder jumpers W1, W2, and W3 (located near the edge of the main board alongside the transformer).
3. If your power requirement is 115 Vac, solder jumpers W1 and W3 should be wired, but jumper W2 should
not. If your power requirement is 230 V ac, solder jumper W2 should be wired, but jumpers W1 and W3 should not.
Note: W4 jumper is not used. Figure 3-1 shows the location of solder jumpers W1 through W3.
Figure 3-1 Main Board Power Jumpers
Figure 3-2 shows the location jumper positions on the main board.
DFI INFINITY CS (V- M3598/N/0906) 7 CF 70
Figure 3-2 Main Board Jumper Positions
Figure 3-3 Upper Isolated Analog Output Option Board Installation
S2 jumpers are used for testing purposes. Do not use as reading errors may result. S3 jumpers are used for the following (refer to Figure 3-2):
To enable or disable the front panel push-buttons
To allow for an extremely low resistance load button for analog output
To disable the MENU button
To perform factory calibration procedure
Test pins TP1 – TP11 are for testing purposes. Do not use as reading errors may result. S4-A factory default jumper is removed.
DFI INFINITY CS (V- M3598/N/0906) 8 CF 70
Loading...
+ 25 hidden pages