Manual Objectives
This manual shows you how to set up and use the Programmable Digital Meter.
Standard Procedures:
• Checking voltage jumpers, or changing voltage power
• Mounting the panel
• Selecting the input type
• Selecting a decimal point position
• Scaling with known loads (on-line calibration)
• Scaling without known loads
• Selecting ratiometric/non-ratiometric operation
• Displaying the filtered/unfiltered input signal
• Selecting a display color
• Setting the setpoint’s active band
• Selecting a latched or unlatched operation
• Setting setpoint deadbands
• Enabling/disabling setpoint changes
• Enabling/disabling the RESET button in the Run Mode
Optional Procedures:
• Setting input resolution
• Enabling/ disabling analog output
• Selecting analog output as current or voltage
• Assigning the output to net/gross reading
• Scaling analog output
Features with
segment characters shown are for the “B” version.
are for the “B” version which has three-color programmable “Big” LED display – All
For first-time users: Refer to the QuickStart Manual for basic operation and set-up instructions.
Table A-1 Sections of the Manual
IF YOU WANT TO READ ABOUT: REFER TO SECTION
Unpacking; safety considerations 1 Introduction
Meter description and features 2 About the Meter
Main board power jumpers; panel mounting, sensor input, main power and
analog and relay output
Input type; decimal point position; reading scale & offset; reading
configuration; display color; setpoint configuration; setpoint deadbands;
output configuration (analog output); analog output scaling; lock out
configuration; display brightness
Display messages 5 Display Messages
Meter menu/sub-menu messages 6 Menu Configuration
Setpoint configuration messages 7 Setpoint Configuration Displays
Specifications 8 Specifications
Factory Preset Values 9 Factory Default Setup as Shipped
NOTES, WARNINGS and CAUTIONS
Information that is especially important to note is identified by three labels:
• NOTE
• WARNING
• CAUTION
• IMPORTANT
3 Getting started
4 Configuring the Meter
DFI INFINITY CS (V- M3598/N/0906) 1 CF 70
NOTE: provides you with information that is important to successfully setup and use the Programmable
Digital Meter.
CAUTION or WARNING: tells you about the risk of electric shock.
CAUTION, WARNING or IMPORTANT: tells you of circumstances or practices that can affect the meter’s
functionality and must refer to accompanying documents.
TIP: provides you helpful hints.
1.0 INTRODUCTION
1.1 Unpacking
Remove the Packing List and verify that all equipment has been received. If there are any questions about the
shipment, please call Cooper Instruments at 1-800-344-3921.
Upon receipt of shipment, inspect the container and equipment for any signs of damage. Take particular n ote of
any evidence of rough handling in transit. Immediately report any damage to the shipping agent.
The carrier will not honor any claims unless all shipping material is saved for their examination. After
examining and removing contents, save packing material and carton in the event reshipment is necessary.
Verify that you receive the following items in the shipping box:
QTY DESCRIPTION
Programmable Digital Meter indicator/controller with all applicable connectors attached.
1
Owner’s Manual
1
Set Mounting brackets
1
If you ordered any of the available options, they will be shipped in a separate container to avoid any damage
to your indicator/controller.
1.2 Safety Considerations
This device is marked with the international caution symbol. It is important to read this manual before
installing or commissioning this device as it contains important information relating to Safety and EMC
(Electromagnetic Compatibility).
This instrument is a panel mount device protected in accordance with EN 61010-1:2001, electrical safety
requirements for electrical equipment for measurement, control and laboratory. Installation of this instrument should
be done by qualified personnel. In order to ensure safe operation, the following instructions should be followed.
This instrument has no power-on switch. An external switch or circuit breaker shall be included in the
building installation as a disconnecting device. It shall be marked to indicate this function, and it shall be in close
proximity to the equipment within easy reach of the operator. The switch or circuit-breaker shall not interrupt the
Protective Conductor (Earth wire), and it shall meet relevant requirements of IEC 947-1 and IEC 947-3
(International Electrotechnical Commission). The switch shall not be incorporated in the main supply cord.
Furthermore, to provide protection against excessive energy being drawn from the main supply in case of a
fault in the equipment, an overcurrent protection device shall be installed.
• Do not exceed voltage rating on the label located on the top of the instrument housing.
• Always disconnect power before changing signal and power connections.
• Do not use this instrument on a work bench without its case for safety reasons.
• Do not operate this instrument in flammable or explosive atmospheres.
• Do not expose this instrument to rain or moisture.
• Unit mounting should allow for adequate ventilation to ensure instrument does not exceed operating
temperature rating.
DFI INFINITY CS (V- M3598/N/0906) 2 CF 70
• Use electrical wires with adequate size to handle mechanical strain and power requirements. Install
without exposing bare wire outside the connector to minimize electrical shock h azards.
EMC Considerations
• Whenever EMC is an issue, always use shielded cables.
• Never run signal and power wires in the same conduit.
• Use signal wire connections with twisted-pair cables.
• Install Ferrite Bead (s) on signal wires close to the instrument if EMC problems persist.
Failure to follow all instructions and warnings may result in injury!
2.0 ABOUT THE METER
2.1 Description
The Digital Programmable Strain meter is a value packed indicator/controller. Four full digits and broad scaling
capability allow for a display in virtually all engineering units. A wide variety of DC current and voltage input ranges
cover typical strain applications. Standard features include sensor excitation and front panel or remote tare. Your
meter may be a basic indicator or it may include analog output or dual relay output. Analog or dual relay output
must be ordered at time of purchase. Analog output is fully scalable and may be configured as a proportional
controller, or to follow your display. Dual 5 amp, form C relays control critical processes. A mechanical lockout has
been included to guard against unauthorized changes.
2.2 Features
The following is a list of standard features:
• 4-digit, three color Programmable, Big LED display or
4-digit, Standard LED display
• NEMA 4 Front Bezel
• ±0.03 % accuracy
• 8 DC input ranges: 0-100 mV, ±50 mV, 0-5 V, 1-5 V, 0-10 V, ±5 V, 0-20 mA, and 4-20 mA
• 5,10,12, or 24 Vdc sensor excitation
• Peak detection
• Front panel and remote tare function
• Nonvolatile memory-no battery backup
• 115 or 230 Vac 50/60 Hz power supply or
10 – 32 Vdc or 26-56 Vdc
The following is a list of optional features:
• Dual 5 amp, form C relay output
• Scalable analog output
• Proportional control
• Easy setup for proportional control
2.3 Available Accessories
Table 2-1 Accessories and Add-Ons
Add-On Options
FS Special Calibration/Configuration
SPC4 NEMA-4 Splash proof Cover
SPC18 NEMA-4 Splash Proof Cover, NEW
Accessories
TP1A Trimplate panel adaptor - Adapts DIN1A/DIN2A cases to larger panel cutouts
RP18 19-in. Rack Panel for one (1) 1/8 DIN instrument
RP28 19-in. Rack Panel for two (2) 1/8 DIN instruments
DFI INFINITY CS (V- M3598/N/0906) 3 CF 70
RP38 19-in. Rack Panel for three (3) 1/8 DIN instruments
2.4 Front of the Meter
Figure 2-1 shows each part of the front of the three-color programmable “Big” LED display Meter (Version
B).
Digital LED Display:
-1.9.9.9 or 9.9.9.9 4-digit three color programmable, 21 mm (0.83”) high
LED display with programmable decimal point.
Figure 2-1 Front-Panel with Big Display
Figure 2-2 shows each part of the front of the standard LED display meter.
Digital LED Display:
-1.9.9.9 or 9.9.9.9 14 segment, 13.8 mm (0.54”)
high LED display with programmable decimal point.
Figure 2-2 Front-Panel with Standard Display
These meter display windows (both versions) light when appropriate:
1 Setpoint 1 status
2 Setpoint 2 status
5 Pushbuttons for programming the meter.
METER BUTTONS
SETPTS Button
In the Run Mode, this button will sequentially recall the previous setpoint settings. As necessary, use the
S/NT/GRS and X/TARE buttons to alter these settings, and then press the SETPTS button to store new values.
Unless you press the SETPTS, X/TARE, or SNT/GRS button within 20 seconds, the meter will scroll to setpoint 2
and then to the Run Mode.
If the dual relay option is not installed, or if
SETPTS button will display the meter’s firmware version.
S/NT/GRS Button
In the Run Mode, this button will toggle between net/gross readings or peak readings, depending upon setup.
In the Configuration Mode, press this button to change the value of the flashing digit shown on the display and/or
toggle between menu choices, such as
or on menu . When configuring your setpoint
values, press the S/NT/GRS button to advance the flashing digit’s value from 0 to 9 by 1.
X/TARE Button
In the Run Mode press the X/TARE button to tare your reading (zeroing).
In the Configuration Mode, press this button to scroll to the next digit.
is displayed on the menu, pressing the
DFI INFINITY CS (V- M3598/N/0906) 4 CF 70
MENU Button
In the Run Mode, press the MENU button to terminate the current measuring strain and enter you into the
Configuration Mode.
Only if you have not installed the lock out jumpers on the main board.
In the Configuration Mode, press the MENU button to store changes in the nonvolatile memory and then advance
you to the next menu item.
RESET Button
If you hard reset (press the MENU button followed by the RESET button) or power off/on the meter, it shows
followed by
.
In the Run Mode, press the RESET button to reset the latched setpoints. The meter shows
and returns to
the Run Mode.
In the Configuration Mode, press the RESET button once to review the previous menu. Press the RESET button
twice to perform a hard reset and return to the Run Mode.
In the Peak Mode, press the RESET button to reset peak values. The meter shows and returns to the Run
Mode.
In the Setpoint Mode, press the RESET button to reset the latched setpoint. The meter shows
and enters
the Run Mode.
In the Tare Mode, press the RESET to reset. The meter shows
.
When in setpoint or Configuration Mode, if the meter shows 9999 or –1999 with all flashing digits, the
value has overflowed. Press the S/NT/GRS button to start a new value.
2.5 Back of the Meter
,
Figure 2-3 shows the label describing the connectors on the back of the meter. Table 2-2 on the following page
gives a brief description of each connector at the back of the meter.
Figure 2-3 Connectors (AC-Powered and DC-Powered Detail)
J1 (1-2) Remote tare connection with a momentary switch
The DIP switches are located at the S1 position (Refer to Figure 3-2). Use a small instrument such as a paper clip
to change the switches from open to closed. Table 2-3 lists DIP switch settings at the S1 position required to
complete the setup of your meter.
Setpoint 1: Normally open (N.O.1) connection
Setpoint 1: Normally closed (N.C.1) connection
Setpoint 1: Common (COM1) connection
Setpoint 2: Normally open (N.O.2) connection
Setpoint 2: Normally closed (N.C.2) connection
Setpoint 2: Common (COM2) connection
AC line connection (no connections on DC-powered units)
AC neutral connection (+ Input on DC-powered units)
AC earth ground (DC-power return on DC-powered units)
Analog voltage output
Analog current output
Analog return
-E: Negative excitation connection from meter (5,10,12 V)
+E: Positive excitation connection from meter (5,10,12 V)
+20 mA connection for analog input
+R (Not used)
+24 V output connection
+S: Positive signal input
-S: Negative signal input and return for +20 mA or +24 V
-R (Not used)
Isolated Analog Voltage Output
Isolated Analog Current Output
Isolated Analog Output Return
Table 2-3 DIP Switch Positions/Input Range & Excitation
S1 DIP Switch Positions
1 2 3 4 5 6 7 8
Settings for Excitation Voltage
C - - - - - - O - - - - O O C - - - - O O C - - - - C O C - - - - C C -
Settings for Input Ranges
-
-
-
-
-
O
O
C
C
O
C
C
O
O
C
O
O
O
O
C
O
C
C
O
O
-
-
-
-
-
-
-
-
-
-
O
O
C
C
O
The display must also be configured to the selected input type after setting the DIP switches (see Section
4.1, Selecting the Input Type)
2.6 Disassembly
You may need to open up the meter for one of the following reasons:
DFI INFINITY CS (V- M3598/N/0906) 6 CF 70
• To check or change the 115 or 230 Vac power jumpers.
• To install or remove jumpers on the main board.
Disconnect the power supply before proceeding.
To remove and access the main board, follow these steps:
• Disconnect main power from the meter.
• Remove the back case cover.
• Lift the back of the main board upwards and let it slide out of the case.
3.0 GETTING STARTED
Caution: The meter has no power-on switch, so it will be in operation as soon as you apply power.
If you power off/on the meter, or perform a hard reset (press the RESET button twice), the meter shows
followed by
.
3.1 Rating/Product Label
This label is located on top of the meter housing (refer to Figure 3-4).
3.2 Main Board Power Jumpers (Refer To Figure 3-1)
Important: If you want to change the Factory preset jumpers, do the following steps, otherwise go to
Section 3.3.
Warning: Disconnect the power from the unit before proceeding. This device must only be reconfigured
by a specially trained electrician with corresponding qualifications. Failure to follow all instructions and
warnings may result in injury!
1. Remove the main board from the case. Refer to Section 2.6.
2. Locate the solder jumpers W1, W2, and W3 (located near the edge of the main board alongside the
transformer).
3. If your power requirement is 115 Vac, solder jumpers W1 and W3 should be wired, but jumper W2 should
not. If your power requirement is 230 V ac, solder jumper W2 should be wired, but jumpers W1 and W3
should not.
Note: W4 jumper is not used.
Figure 3-1 shows the location of solder jumpers W1 through W3.
Figure 3-1 Main Board Power Jumpers
Figure 3-2 shows the location jumper positions on the main board.
DFI INFINITY CS (V- M3598/N/0906) 7 CF 70
Figure 3-2 Main Board Jumper Positions
Figure 3-3 Upper Isolated Analog Output Option Board Installation
S2 jumpers are used for testing purposes. Do not use as reading errors may result.
S3 jumpers are used for the following (refer to Figure 3-2):
• To enable or disable the front panel push-buttons
• To allow for an extremely low resistance load button for analog output
• To disable the MENU button
• To perform factory calibration procedure
Test pins TP1 – TP11 are for testing purposes. Do not use as reading errors may result.
S4-A factory default jumper is removed.
DFI INFINITY CS (V- M3598/N/0906) 8 CF 70
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.