Cooper Instruments DFI-INFINITY Installation Manual

DFI INFINITY
STRAIN METER/CONTROLLER
USER’S GUIDE
www.cooperinstruments.com
CONTENTS
NOTES, WARNINGS AND CAUTIONS .......................................................................................1
1.0 INTRODUCTION ....................................................................................................................1
1.1 Description ......................................................................................................................................1
1.2 Features ...........................................................................................................................................1
1.3 Available Models.............................................................................................................................1
2.0 UNPACKING ..........................................................................................................................2
3.0 SAFETY CONSIDERATIONS ................................................................................................3
4.0 PARTS OF THE METER........................................................................................................4
4.1 Front Of The Meter..........................................................................................................................4
4.2 Rear Of The Meter ...........................................................................................................................6
5.0 SETUP....................................................................................................................................7
5.1 Conditions Requiring Disassembly...............................................................................................7
5.2 Assembly/Disassembly Opening...................................................................................................8
5.2.1 Safety Precaution/Product Id Label........................................................................................9
5.2.2 Main Board Power Jumpers....................................................................................................9
5.2.3 Printed Circuit Board(s) Installation.....................................................................................10
5.2.4 How To Access Jumpers.......................................................................................................10
5.2.5 Panel Mount Assembly .......................................................................................................... 13
6.0 JUMPER POSITIONS ..........................................................................................................15
6.1 Introduction ...................................................................................................................................15
6.2 S1 Jumper Positions For Readrate And Unipolar Or Bipolar Input(S)..................................... 15
6.3 S2 Jumper Positions For Input Ranges ...................................................................................... 15
6.4 Jumper Setting(s) For Sensor Excitation ...................................................................................16
6.4.1 Jumper Settings for Sensor Excitation –ac Powered Unit .................................................17
6.4.2 Jumper Settings for Sensor Excitation – dc Powered Unit................................................17
7.0 SIGNAL AND POWER INPUT CONNECTIONS..................................................................18
7.1 Introduction ...................................................................................................................................18
7.2 Signal Input Connections............................................................................................................. 18
7.3 AC Wiring Connection.................................................................................................................. 20
8.0 METHODS FOR SCALING THE METER TO DISPLAY IN ENGINEERING UNITS............21
8.1 Introduction ...................................................................................................................................21
8.2 Setup Meter Input Type and Range............................................................................................. 21
8.3 Scaling Your Meter Using 2-Coordinate Input Scale And Offset (IN.SC.OF) With Sensor
Connected To Your Meter ..................................................................................................................22
8.3.1 SETTING INPUT CONFIGURATION (IN CNF) ....................................................................... 23
8.3.2 Scaling Your Meter With Your Sensor Connected .............................................................. 23
8.3.3 To Select Decimal Point Position (DEC PT).........................................................................24
8.3.4 Entering Zero Offset Numbers ..............................................................................................25
8.4 Scaling Your Meter Without Connecting A Sensor Using Calculated Values......................... 26
8.4.1 Preparing Your Meter For Scaling With Input Scale And Offset........................................ 26
8.4.2 Scaling Your Meter................................................................................................................. 27
8.4.3 To Select Decimal Point Position .........................................................................................29
8.4.4 Entering Zero Offset Numbers ..............................................................................................30
9.0 LOCKOUT CONFIGURATIONS AND METER FUNCTION MENUS...................................31
9.1 Individual Lockout Information....................................................................................................31
9.2 Meter Function Menus.................................................................................................................. 34
9.2.1 INPUT ......................................................................................................................................34
CF 67 ii M1291/N/0403 11279ML-02 Rev. A
9.2.2 RDG.CNF (READING CONFIGURATION).............................................................................. 34
9.2.3 RDG SC (Reading Scale) AND RDG OF (Reading Offset)................................................... 35
9.2.4 IN CNF (Input Configuration).................................................................................................36
9.2.5 IN.SC.OF (Input Scale And Offset)........................................................................................37
9.2.6 DEC PT (Decimal Point) ......................................................................................................... 38
9.2.7 CNT BY (Count By).................................................................................................................38
9.2.8 FIL.CNF (Filter Configuration)...............................................................................................39
9.2.9 FIL TI (Filter Time Constant)..................................................................................................40
9.2.10 SP CNF (Setpoints 1 & 2 Configuration) ............................................................................40
9.2.11 AL CNF (Alarm Configuration) ............................................................................................ 41
9.2.12 AL FNC (Alarm Function) ....................................................................................................42
9.2.13 AL RDG (Alarm Readings)...................................................................................................43
9.2.15 AL DB (Alarm Deadband) ....................................................................................................43
9.2.16 OUT.CNF (Output Configuration)........................................................................................ 44
9.2.17 OT.SC.OF (Output Scale And Offset) .................................................................................45
9.2.18 BAUD (Baud Rate)................................................................................................................45
9.2.19 SERCNF (Serial Communication Configuration)............................................................... 46
9.2.20 ADDRESS (Multipoint Communications Device Address) ...............................................46
9.2.21 DAT FT (Data Format) ..........................................................................................................46
9.2.22 BUS FT (Bus Format) ........................................................................................................... 47
9.2.23 SERCNT (Serial Count) ........................................................................................................ 48
9.2.24 Analog Output Calibration Numbers .................................................................................. 49
10.0 SETPOINTS/ALARMS .......................................................................................................49
10.1 Features Overview ......................................................................................................................50
10.2 Unlocking The Features ............................................................................................................. 50
10.3 Selecting SP CNF Setpoint Configuration Features ................................................................ 51
10.4 Deviation Function For Alarms.................................................................................................. 51
10.5 Selecting AL CNF Alarm Configuration Features .................................................................... 52
10.6 Selecting AL FNC Alarm Function Features............................................................................. 53
10.7 AL RDG: Alarm Readings-Select Delay In Alarm Action.........................................................54
10.8 SP DB: Select “SP 1” and “SP 2” Deadband (Hysteresis) ...................................................... 54
10.9 AL DB: Select Alarm 1 (SP 3) and Alarm 2 (SP 4) Deadband (Hysteresis) ............................ 54
10.10 OUT .CNF: Control Flashing Of The Display .......................................................................... 54
10.11 Entering Setpoint Levels (In Run Mode) ................................................................................. 55
11.0 PEAK AND VALLEY READINGS ......................................................................................55
12.0 ANALOG OUTPUT OPTION..............................................................................................55
12.1 Features Overview ......................................................................................................................56
12.2 Unlocking..................................................................................................................................... 56
12.3 OUT.CNF: Configuring The Output ...........................................................................................56
12.4 OT.SC.OF: Setting Output Scale And Offset ............................................................................ 56
12.5 Board Installation: Entering The Trim Data .............................................................................. 57
12.6 Filter Configuration FIL.CNF Value To Be Transmitted On Analog Output........................... 58
12.7 Wiring/Connections ....................................................................................................................58
13.0 BCD OPTION .....................................................................................................................58
13.1 Features Overview ......................................................................................................................58
13.2 BCD Card Jumper Table............................................................................................................. 59
13.3 Interconnect Board .....................................................................................................................59
13.4 50-Line Cable Compatibility.......................................................................................................59
13.5 Selecting The Source Of BCD Data: “OUT .CNF” .................................................................... 60
13.6 Hold Control ................................................................................................................................ 60
13.7 Data Ready Timing Pulses .........................................................................................................60
CF 67 iii M1291/N/0403 11279ML-02 Rev. A
13.8 Bringing Out The BCD Overflow Line ....................................................................................... 60
13.9 3 Digit At A Time Multiplex......................................................................................................... 60
13.10 6 Digit At A Time Card Address...............................................................................................60
13.11 Select Data Polarity: Jumper S8..............................................................................................61
13.12 Decimal Point Address Code................................................................................................... 61
13.13 Applying Non-Isolated/Isolated Power....................................................................................61
13.14 Driving A Printer .......................................................................................................................61
14. RELAY OPTIONS ................................................................................................................61
14.1 Features Overview ......................................................................................................................61
14.2 Wiring/Connections ....................................................................................................................63
15.0 RS-232 OR RS-485 OPTION BOARD ...............................................................................64
15.1 Features Overview ......................................................................................................................64
15.2 Front-Panel Pushbutton Configuration..................................................................................... 65
16.0 EXTERNAL CONTROL LINES ..........................................................................................65
16.1 Tare (PIN 1) ..................................................................................................................................66
16.2 Peak (PIN 2) .................................................................................................................................66
16.3 Valley (PIN 3) ...............................................................................................................................66
16.4 SWLIN2 (PIN 4) ............................................................................................................................66
16.5 Peak & Valley Or External Reset (PIN 5) ...................................................................................66
16.6 Push To CAL (PIN 6) ...................................................................................................................66
16.7 Digital Ground (PIN 7)................................................................................................................. 66
16.8 +5 V (PIN 8) ..................................................................................................................................66
16.9 Display Hold (PIN 9)....................................................................................................................66
16.10 Lockout EEPROM (And ‘MENU’ Button) (PIN 10)................................................................... 66
16.11 Print Command And/Or Reset Of Alarms (PIN 11).................................................................67
16.12 Nonstandard RX (PIN 12) And Nonstandard TX (PIN 13) ......................................................67
16.13 Push to CAL (PIN 14) ................................................................................................................67
16.14 +V EXT (PIN 15) .........................................................................................................................67
16.15 SP1 (PIN 16)...............................................................................................................................67
16.16 SP2 (PIN 17)...............................................................................................................................67
16.17 AL1 (PIN 18)...............................................................................................................................67
16.18 AL2 (PIN 19)...............................................................................................................................67
16.19 RTN EXT (PIN 20) ......................................................................................................................67
17.0 TROUBLESHOOTING - DISPLAY MESSAGES AND TROUBLESHOOTING GUIDE .....67
17.1 Error Mode Messages.................................................................................................................68
17.1.1 Flashing 999999 (Numerical Overflow) ..............................................................................68
17.1.2 Flashing ERR O1 (Offset Overflow) .................................................................................... 68
17.1.3 Flashing ERR O2 (Setpoint Overflow) ................................................................................ 68
17.1.4 NOSTOR & STORED (Programming Entries In EEPROM)................................................ 68
17.1.5 Flashing +OVLD (Positive Input Overload)........................................................................ 68
17.1.6 Flashing +OPEN (Open Sensor Indication) .......................................................................68
17.1.7 Flashing -OPEN (Open Sensor Indication) ........................................................................68
17.1.8 Flashing I OVSC (Input Overscale) ..................................................................................... 68
17.1.9 Flashing R OVSC (Reading Overscale) .............................................................................. 68
17.1.10 Flashing CB OVF (Count By Overflow) ............................................................................ 68
17.1.11 Flashing UOM.OVF (Unit Of Measure Overflow) .............................................................68
17.2 Troubleshooting Guide...............................................................................................................69
18.0 SPECIFICATIONS..............................................................................................................70
18.1 Current Input ...............................................................................................................................70
18.2 Voltage Input ...............................................................................................................................70
CF 67 iv M1291/N/0403 11279ML-02 Rev. A
18.3 Potentiometer Input ....................................................................................................................70
18.4 General......................................................................................................................................... 70
19.0 FACTORY PRESET VALUES............................................................................................73
20.0 RECORD YOUR SETUP VALUES ....................................................................................74
WARRANTY REPAIR POLICY..................................................................................................76
CF 67 v M1291/N/0403 11279ML-02 Rev. A

NOTES, WARNINGS AND CAUTIONS

Information that is especially important to note is identified by these labels:
NOTE
WARNING
CAUTION
IMPORTANT
NOTE: provides you with information that is important to successfully set up and use the Programmable digital meter.
CAUTION or WARNING: tells you about the risk of electric shock.
CAUTION, WARNING or IMPORTANT: tells you of circumstances or practices that can affect the meter’s functionality and must refer to accompanying documents.

1.0 INTRODUCTION

1.1 Description

The INFINITY series is a complete line of process indicators/controllers, offering exceptional performance.
The DFI INFINITY strain gauge meter is front panel configurable to accept 0-20 and 4-20 mA dc current inputs, unipolar and bipolar DC voltage inputs and potentiometer inputs. The DFI INFINITY meter will accept inputs from most of the process sensors in use today such as transmitters, pressure transducers, and potentiometers. Configuring the INFS is accomplished through the 5 front panel buttons. If the optional RS-232 or RS-485 communications are installed, the user may remotely set the display parameters.
Options for the INFINITY include analog and BCD outputs, relay outputs, and RS-232 or RS-485 communications.

1.2 Features

The following is a list of features of the DFI INFINITY.
6-digit LED display in red or green
0.005% accuracy of reading
12 DC input ranges: 0-100 mV, 0-1 V, 0-5 V, 1-5 V, 0-10 V, 0-100 V, ±50 mV, ±500 mV, ±5 V, ±50 V, 0-20
mA, or 4-20 mA.
1.5 to 11 or 24 V dc sensor excitation
Peak & Valley detection and memory
TARE
Up to 13 readings per second
4 isolated open collector outputs (standard) and optional isolated relay or isolated BCD and isolated analog
outputs
Optional isolated RS-232 or RS-485 communications
NEMA 4 Front Panel/IP65
Non-volatile memory without battery back-up
115 Vac, 50/60 Hz, 230 Vac, 50/60 Hz power supply

1.3 Available Models

The following INFINITY options are available from Cooper Instruments & Systems.
NOTE: The following options are available installed at the time of purchase or as separate items installed by the user after purchase: Analog Output Board, BCD Output Board, Relay Output Board, RS-232 Communications Board, and RS-485 Communications Board.
CF 67 1 M1291/N/0403 11279ML-02 Rev. A
INF-1 ANALOG OUTPUT CARD W/ 4-20 MA/0-10V OUTPUT INF-2 RS-232 CARD INF-3 DUAL RELAY CARD INF-4 BCD ISOLATED PARALLEL OUTPUT INF-5 10-32 Vdc POWER INF-6 IO CAL INF-7 RS-485 CARD INF-12 4 RELAY BOARD INF-16 BUMPER BAND

2.0 UNPACKING

Remove the Packing List and verify that all equipment has been received. If there are any questions about the shipment, please call the Cooper Instruments & Systems Customer Service Department at 1-800-344-3921 or 540­349-4746. Upon receipt of shipment, inspect the container and equipment for any signs of damage. Take particular note of any evidence of rough handling in transit. Immediately report any damage to the shipping agent.
NOTE: The carrier will not honor any claims unless all shipping material is saved for their examination. After examining and removing contents, save packing material and carton in the event reshipment is necessary.
When you order your DFI INFINITY strain gauge meter, you will receive the following items in the shipping box:
QTY DESCRIPTION ILLUSTRATION
1 Basic Meter in a Mounting
Sleeve with Gasket
1 Front-Panel Button Cover
1 AC Power Connector
(orange - P1)
2 Input Connectors
(gray - P3 and P9)
CF 67 2 M1291/N/0403 11279ML-02 Rev. A
1 Rear Protective Cover with Screw
1 20-Socket Ribbon Connector
(P2 Connector)
2 Panel-Mounting Gaskets
(1 Spare)
1 Strain Gauge Owner’s Guide 1 Quick Start Manual
Other items may also be in the box depending on the options ordered. Refer to specific options described previously.

3.0 SAFETY CONSIDERATIONS

This device is marked with the international caution symbol. It is important to read this manual before installing or commissioning this device as it contains important information relating to Safety and EMC (Electromagnetic Compatibility).
Unpacking and Inspection Unpack the instrument and inspect for obvious shipping damage. Do not attempt to operate if the unit is damaged.
This instrument is a panel mount device protected in accordance with Class I of EN 61010 (115/230 AC power connections), Class II for the DC power option (10-32 Vdc). Installation of this instrument should be done by qualified personnel. In order to ensure safe operation, the following instructions should be followed.
This instrument has no power-on switch. An external switch or circuit breaker shall be included in the building installation as a disconnecting device. It shall be marked to indicate this function and it shall be in close proximity to the equipment with easy reach of the operator. The switch or circuit breaker shall not interrupt the Protective Conductor (Earth wire) and it shall meet the relevant requirements of IEC 947-1 and IEC 947-3. The switch shall not be incorporated in the mains supply cord.
Furthermore, to provide protection against excessive energy being drawn from the mains supply in case of a fault in the equipment, and overcurrent protection device shall be installed.
The protective conductor must be connected for safety reasons. Check that the power cable has the proper Earth wire, and it is properly connected. It is not safe to operate this unit without the protective conductor terminal connected.
Do not exceed voltage rating on the label located on the top of the instrument housing.
Always disconnect power before changing signal and power connections.
Do not use this instrument on a workbench without its case for safety reasons.
Do not operate this instrument in flammable or explosive atmospheres.
Do not expose this instrument to rain or moisture.
CF 67 3 M1291/N/0403 11279ML-02 Rev. A
Unit mounting should allow for adequate ventilation to ensure instrument does not exceed operating temperature rating.
Use electrical wires with adequate size to handle mechanical strain and power requirements. Install without exposing bare wire outside the connector to minimize electrical shock hazards.
EMC Considerations
Whenever EMC is an issue, always use shielded cables.
Never run signal and power wires in the same conduit.
Use signal wire connections with twisted-pair cables.
Install Ferrite Bead(s) on signal wires close to the instrument if EMC problems persist.
Failure to follow all instructions and warnings may result in injury!

4.0 PARTS OF THE METER

4.1 Front Of The Meter

The following is a brief description of each part of the front of the meter.
ITEM DESCRIPTION
.8.8.8.8.8. or 8.8.8.8.8.8.
1
6-digit, 14 segment, alphanumeric 0.54" high LED display with programmable decimal point.
SETPOINT LED
2
These LEDs, labeled 1 through 4, display the status of setpoints 1, 2, 3 (Alarm 1), and 4 (Alarm 2).
SETPTS BUTTON
3
This button functions only in the run mode. When the Setpoint/Alarm features are unlocked, pressing this button sequentially recalls the previous setpoint settings to the display. After the ‘ /MIN’ and ‘_/MAX’ buttons are used to alter those values as desired, pressing the ‘SETPTS’ button, again, stores these new values.
Unless the ‘SETPTS’ button is pressed, each of the four setpoint values is displayed for approximately 10 seconds after the last press of the ‘SETPTS’ button. Holding the ‘SETPTS’ button depressed stalls this automatic sequence, retaining the most recent setpoint number on the display.
Figure 4-1. Front Detail
CF 67 4 M1291/N/0403 11279ML-02 Rev. A
S /MAX BUTTON
4
During run mode, pressing this button displays the “HI RDG” (peak reading) value that has occurred up to the moment the ‘MAX’ button is pressed. This peak reading flashes, to distinguish its value from the current readings. Since this is a dynamic peak reading, the value will change if the value increases while reviewing it.
To return to display of the current readings without resetting the peak-value memory to zero (0), press the ‘MAX’ button once again.
To reset the peak-value memory (start a new peak determining period), press the ‘RESET’ button once.
During the configuration mode, the ‘MAX’ button is used to change the numerical value of the flashing digit displayed. For submenu items, such as “L1C.1=0”, pressing the ‘MAX’ button toggles the choice from “0” to “1”.
The meter allows rapid changes of a displayed numerical value by making “0” the first value to occur when the ‘MAX’ button is pressed. After that, the numbers increase to “9” and then roll over to “0” again. A negative (“–”) symbol may be displayed in the most significant digit (i.e. the digit at the far left such as shown here “–.8.8.8.8.8.”)
In the SETPT (SETPOINT) mode (SP1, SP2, etc), pressing the ‘MAX’ button causes the flashing digit to increment by 1 from 0 to 9.
X /MIN BUTTON
5
During run mode, pressing the ‘MIN’ button recalls the “LO RDG” (valley reading) measured since the last press of the ‘RESET’ button. This lowest value flashes, to distinguish it from the current process display. Since this is a dynamic valley reading, the value will change if the value decreases while reviewing it.
To return to the actual process display, without resetting the low-value memory, press the ‘MIN’ button once again.
To reset the memory for current-value readings (start a new observation period), press the ‘RESET’ button once and the meter will return to the run mode.
In the configuration mode, once in a submenu (like input type) the ‘MIN’ button allows you scroll through the available choices such as, 0-20 mA or 4-20 mA, etc. In the SETPT mode, the ‘MIN’ button advances the flashing digit to the right.
MENU BUTTON
6
In the run mode, this button terminates the measurement process and allows you to enter the configuration mode, advancing through the configuration menus. In the configuration mode, this button will store changes in the non-volatile memory at the same time advancing the display to the next menu item.
RESET BUTTON
7
In the run mode, pressing the ‘RESET’ button once erases the memories of peak (“HI RDG”), valley (“LO RDG”), and ALARM latches. The display then returns to the run mode.
WARNING: Pressing the ‘RESET’ button two (2) times will result in a hard reset of the meter. This will clear the Peak & Valley, Alarm latches and meter reading and immediately begin a new measurement.
In the configuration mode, pressing the ‘RESET’ button once, displays the previous selection. For example, if you were in “IN CNF” then pressed the ‘RESET’ button once, the display will then show “RD.SC.OF”. Press the ‘RESET’ button two times to return to the run mode.
CF 67 5 M1291/N/0403 11279ML-02 Rev. A

4.2 Rear Of The Meter

The following is a brief description of each part of the rear of the meter. The label on the top of the mounting sleeve (not the case) identifies the location of the connectors found at the rear of the meter.
Figure 4-2A. AC Power - Connector Label for Rear Connectors
Figure 4-3 shows the rear of the meter with the optional relay output board and a serial communications board installed.
Figure 4-2B. DC Power - Connector Label for Rear Connectors
CF 67 6 M1291/N/0403 11279ML-02 Rev. A
Figure 4-3 Rear View
Figure 4-4 shows the rear of the meter with the optional BCD output board and a serial communications output board installed.
Figure 4-4. Rear View
TABLE 4-1
REAR CONNECTOR DESCRIPTIONS
CONNECTOR# DESCRIPTION
P1 AC Power Connector P2 External I/O Connector P3 Input Connector, –E, +R, –R
J4 Optional RS-232 or RS-485 Phone Jack Connector P5 Optional Analog Out Connector P6 Optional Form-C Relay #1 Connector P7 Optional Form-C Relay #2 Connector P8 Optional BCD Connector P9 Input Connector, +E, +S, –S
P18 Optional Form-C Relay #3 and #4 Connector

5.0 SETUP

5.1 Conditions Requiring Disassembly

You may need to remove the sleeve or open the meter for several reasons:
1. To inspect the rating label on the case (not the same label as on the sleeve) (Section 5.2.1).
2. To check or change the 115 V ac or 230 V ac or main board jumpers (Sections 5.2.2 and 5.2.4).
CF 67 7 M1291/N/0403 11279ML-02 Rev. A
3. To install optional output board(s) (Section 5.2.3).
4. To mount the meter in a panel (Section 5.2.5).

5.2 Assembly/Disassembly Opening

Opening the Meter Your meter is fully assembled, but not wired. See Section 7 for wiring connection for power and sensor inputs. In most cases, if you have ordered optional boards with the meter, these boards will already be installed.
You will need to remove only the rear cover to complete wiring, but you will have to open the meter to do one or more of the following:
WARNING! You must disconnect and turn off the power and connector signals before accessing the unit and installing optional boards. Failure to do so may result in injury!
a. Check or reconfigure the transformer jumpers on the main board so that they correspond to your line voltage
(W1 and W2 for t115 V ac, or W3 for 230 V ac). See Section 5.2.2 b. Install optional boards. c. Access jumpers on the main and optional boards. See Section 5.2.4
Figure 5-1. Meter Exploded View
Using Figures 5-1 as a guide, follow these simple instructions to open the meter:
IMPORTANT! Turn off the power and input signals from the unit before proceeding. Failure to do so may result in injury!
1. Remove the cover mounting screw that secures the rear protective cover to the meter, and remove the rear protective cover. If you are simply wiring the meter – but not checking jumpers or installing or removing boards – this is as far as the meter needs to be disassembled. Go to Section 5.2.1.
2. Remove all wiring connectors from the rear of the meter.
3. Remove the two thumbnuts that secure the case to the sleeve.
4. Remove the sleeve completely by sliding it back form the front bezel.
5. Using Figure 5-2 as a guide, bend the side-panel detents on the case outward and pull the board assembly out of the case by the mounting screw stem.
NOTE: From this point forward, these 5 steps are referred to as “Reveal the main board”.
CF 67 8 M1291/N/0403 11279ML-02 Rev. A
Figure 5-2. Board Assembly Removing/Installing Detail
The meter is now disassembled to the point where you can check and configure jumpers and install boards.
Reinserting the Main Board Assembly into the Case
Reinsert the main board into the case once jumper s and optional boards have been configured and installed.
Spread the side-panel detents of the case and carefully slide the main board all the way in.

5.2.1 Safety Precaution/Product Id Label

To look at the Rating/Product ID label on the case, you must follow the first step as described in Section 5-2. Refer to Figure 5-2 for the location of the Product Identification Label.
The meter is protected in accordance with Class I of EN61010. Refer to Safety Considerations page.
WARNING! If your meter is to be wired to sensors to control inputs that could be hazardous potentials, these potentials will be carried to the 20-pin output connector (P2) at the rear. They will also be present on the meter’s circuit boards. Follow all instructions carefully BEFORE connecting the meter to any source of power.
DO NOT contact any exposed metal parts, install options board(s), change jumpers, or in any way disassemble or assemble the meter while it is connected to AC voltage.
Note the following information and guidelines for safe operation of your meter.
Power Voltage Your power source voltage rating should agree with the voltage under which the meter has been configured to operate. The first thing you should do is verify this.
The meter’s operating voltage is shown in VOLTS: entry of the Product Identification and Serial Number label. It is located on the case as shown in Figure 5-2, and is clearly visible on the meter packing box.

5.2.2 Main Board Power Jumpers

To check voltage jumpers or to change from 115 V ac to 230 V ac:
CAUTION! The meter has no power-on switch. It will be in operation as soon as you apply power. To change the factory presser jumper, disconnect the power from the init. Failure to do so may result in injury. The jumpers must be changed by specifically trained personnel.
1. “Reveal the Main Board” (refer to Section 5.2, Disassembly).
2. Locate the main board assembly and position it in front of you the same way as shown in Figure 5-3.
3. On the main board, locate the transformer jumpers W1, W2, and W3 near the transformer T1. If your power requirement is 115 V ac, jumpers W1 and W2 should be installed. (DO NOT INSTALL W3). If your power requirement is 230 V ac, jumper W3 should be installed. (DO NOT INSTALL W1 OR W2)
CF 67 9 M1291/N/0403 11279ML-02 Rev. A
Figure 5-3. Transformer Jumpers

5.2.3 Printed Circuit Board(s) Installation

To install optional printed circuit board(s):
1. “Reveal the Main Board” (refer to Section 5.2, Disassembly).
2. Using Figure 5-4 as a reference, insert option board(s) into the corresponding slot(s) on the main board. Each circuit board is keyed to fit in it’s own position.
Figure 5-4. Optional Printed Circuit Board Locations

5.2.4 How To Access Jumpers

To gain access to jumper S1 and S2 used to configure input type remove the mounting sleeve. The jumpers may be accessed through the slot in the case.
To gain access to jumpers on the main board for power, excitation and lockout selection:
1. “Reveal the main board” (refer to Section 5.2, Disassembly).
NOTE: To access the S1 and S2 jumpers on the Signal Input Board, you only need to remove the mounting
sleeve.
2. To re-assemble the meter, follow the steps in reverse order.
CF 67 10 M1291/N/0403 11279ML-02 Rev. A
Figures 5-5 through 5-13 show the layout of the seven (7) printed circuit boards with respective jumper blocks, where applicable, used in the meter. Figures 5-7 through 5-13 show the optional boards.
Figure 5-5. Signal Input Board
Figure 5-6. AC-Powered Main Board
Figure 5-7. DC-Powered Main Board
CF 67 11 M1291/N/0403 11279ML-02 Rev. A
p
Figure 5-8. Relay Option Board
Figure 5-9. 4-Relay Option Board
The Analog option board has been updated. The figure shown is the latest version.
Some older versions of the analog output cards are not compatible with dc-powered meters.
S1-A does not need to be
installed.
Figure 5-10. Analog Output Option Board
Check the J12 connector on the main board to ensure it has a 10
osition connector.
CF 67 12 M1291/N/0403 11279ML-02 Rev. A
The RS-232 option board has been updated. The figure shown is the latest version.
Some older versions of the RS-232 cards are not compatible with dc­powered meters.
Check the J11 connector on the main board to ensure it has a 12 position connector.
Figure 5-11. RS-232 Option Board
The RS-485 option board has been updated. The figure shown is an older version, the newer version is the same figure as the RS-232 option card shown above.
Figure 5-12. RS-485 Option Board
Figure 5-13. BCD Option Board

5.2.5 Panel Mount Assembly

The meter can be mounted in a panel so that the front of the meter is flush with the vertical panel surface. Panel mounting can be seen as simply “sandwiching” the panel between the inner case and the outer sleeve in the last phases of assembly. Figure 5-14 shows the panel cutout dimensions, and the dimensions for the panel thickness. It requires that the following already be done:
1. Your line voltage rating has been checked against the meter rating on the Product ID and serial number label on the meter case. See Section 5.2.1.
CF 67 13 M1291/N/0403 11279ML-02 Rev. A
2. You have configured all jumpers – those on the main board as well as those on any optional boards. See Section 5.2.2 for main board jumper configuration and the appropriate sections for optional board jumper configuration.
3. You have installed all optional boards and inserted the main board assembly back into the case. See Section
5.2.3.
4. You have wired P1, the AC power connector, and P2 the input output control connector; connectors are not installed in the meter, but are ready to be installed. See Section 7.
5. You have wired all connectors for optional boards; connectors are not connected to the meter, but are ready to be installed.
If all of these steps are done, use Figure 5-14 as a guide:
CAUTION: Connectors with the wiring connections will be installed after mounting the unit.
Figure 5-14. Panel Mounting Assembly
6. Punch or cut a hole in the panel using the panel cutout dimensions in Figure 5-14. Remove burrs and paint the panel as required
7. Insert the panel-mount gasket around the rear of the case and slide it forward to the bezel (if it’s not already in place).
8. Working from the front of the panel, insert the case assembly, rear end first, all the way into the panel cutout such that the gasket firmly backs the panel surface.
9. Working from the rear of the panel, slide the sleeve forward over the case and up to the panel surface. The panel should now be sandwiched between the bezel-backed gasket in front and the sleeve in back.
10. Replace the thumbnuts that secure the sleeve tabs to the case.
WARNING: Do not “turn-on” the ac power and input signals until all connections are connected to the meter.
11. Set P1, the AC power connector, aside and connect or reconnect all other connectors to the back of the meter using Figures 4-3 and 4-4 in Section 4.2 as guides. Connect P1 last.
NOTE: The P1 connector is “keyed”; it is shaped in such a way that it fits only the J1 male pins.
Your meter is now ready for operation and you can turn-on the power.
CF 67 14 M1291/N/0403 11279ML-02 Rev. A
The meter display should light, and pass through “RESET 2” to run or display mode. If the meter flashes an overscale or overload message, press the ‘MENU’ button to advance to the configuration mode. Do not be concerned about overloads (the +S input can stand 120 V continuously and current inputs can handle ten times rated current).

6.0 JUMPER POSITIONS

6.1 Introduction

This section is for the configuration and setup of your jumper positions for readrate, unipolar or bipolar signal input, sensor input signal jumpers, sensor excitation jumpers, pushbutton lockouts and lockout of lockout configuration menus.

6.2 S1 Jumper Positions For Readrate And Unipolar Or Bipolar Input(S)

The typical readrate for your meter is 3/per second. This requires that no jumper has been installed in the S1A position and Input Configuration (“IN CNF”) bit “INP.2” has been set to equal “0”. Your meter is capable of a fast readrate of 13/per second. This requires that you install a jumper in the S1A position and the Input Configuration (“IN CNF”) bit “INP.2” has been set to equal “1”. Refer to Figure 6-1 for the location of the S1 jumpers.
The typical setting for your meter is unipolar. For unipolar input, no jumper is installed in the S2B position and Input Configuration (“IN CNF”) bit “INP.3” must be set to equal “0”. For bipolar inputs, install a jumper in S1B and set Input Configuration (“IN CNF”) bit “INP.3” to equal “1”.

6.3 S2 Jumper Positions For Input Ranges

The following are the input signal jumper positions required to be installed in the “S2” position on your meter for the current or voltage input ranges you require. These jumper positions include those that are required for sensor excitation. Jumpers S2-N & S2-T are for either 1.5 to 11 Vdc or 24 Vdc sensor excitation. To select desired excitation see Section 6.4. Refer to Figure 6-1 for the location of the S2 jumpers.
Figure 6-1. S1 and S2 Jumper Locations on Signal Input Board
BRIDGE – UNIPOLAR
Jumpers for 0 to 100 mV range: (meter supplied excitation)
Jumpers for 0 to 1 V range: (meter supplied excitation)
CF 67 15 M1291/N/0403 11279ML-02 Rev. A
Jumpers for 0 to 10 V range: (meter supplied excitation)
Jumpers for 0 to 100 V range: (meter supplied excitation)
BRIDGE – BIPOLAR
Jumpers for –50 to +50 mV range: (meter supplied excitation)
Jumpers for –500 to +500 mV range: (meter supplied excitation)
Jumpers for –5 to +5 V range: (meter supplied excitation)
Jumpers for –50 to +50 V range: (meter supplied excitation)
Voltage (Non-Ratiometric) – Unipolar/Bipolar similar to Bridge inputs above except substitute jumper M for L.
CURRENT
Jumpers for 0-20 mA or 4-20 mA: (meter supplied excitation)
POTENTIOMETER
Jumpers for 0 to 10 V range: (using 10 Vdc drive)
NOTE: Remove S2T jumper when you use external sensor excitation.

6.4 Jumper Setting(s) For Sensor Excitation

24 Vdc meter excitation (S2N, S2T & S4B)
10 Vdc meter excitation (S2N, S2T, & S4A, S4C)
1.25 Vdc meter excitation (S2Q)
160 µA meter excitation (S2P)
CF 67 16 M1291/N/0403 11279ML-02 Rev. A
1.6 mA meter excitation (S2P, S2V)
NOTES: 1) Maximum excitation for “Ratiometric” measurement is 10 Vdc.
2) Remove the “S2T” jumper when you use external sensor excitation.
6.4.1 Jumper Settings for Sensor Excitation –ac Powered Unit
Your ac-powered meter is capable of supplying either 1.5 to 11 Vdc or 24 Vdc sensor excitation. (refer to Figure 6-
2).
For 1.5 to 11 Vdc, install S4A and C jumpers, then adjust the potentiometer (R39) for proper voltage.
For 24 Vdc excitation, remove S4A and C jumpers and install S4B.
Figure 6-2. ac-Powered Main Board Jumper positions S3 and S4
S4 On ac-powered units, main board S4A & S4C Installed For 1.5 to 11 Vdc excitation S4B Installed For 24 Vdc excitation
S3 On ac-powered units, main board S3A Installed Unlocks “MENU” button for programming S3B Omit S3C Installed Unlocks lockout menu
NOTE: S3B (the middle jumper) should NOT be installed. This jumper is only used when recalibrating the meter (e.g. an annual, careful performance by the calibration lab). When this jumper is installed, calibration coefficients can be changed via digital communications.
6.4.2 Jumper Settings for Sensor Excitation – dc Powered Unit
Your dc-powered meter is capable of supplying either 1.25 to 12 Vdc or 24 Vdc sensor excitation. (Refer to Figure
6.3)
For 1.25 to 12 Vdc excitation, install SA and S4A jumpers, then adjust the potentiometer (R34) for proper
voltage.
For 24 Vdc, remove the S4A jumper s and install S1B.
CF 67 17 M1291/N/0403 11279ML-02 Rev. A
Figure 6.3. dc-Powered Main Board Jumper Positions S3 and S4
S1 On dc-powered units, side power board
S1A Installed For 1.25 to 12 Vdc excitation at 120 mA S1B Installed For 24 Vdc excitation at 35 mA
S3, S4, S5 On dc-powered unit, main board
S3A Installed To store data and setup parameters in nonvolatile memory S3B Omit See note in previous section 6.4.1 S3C Installed Unlocks lockout menu (L1 through L4) S3D Installed Unlocks Front pushbuttons S4A Installed Along with the S1 jumper to program the excitation output.
Adjust excitation with R34 surface mount pot from 1.25 to 12
volts, with an output current up to 120 mA. S4A Removed For 24 Vdc excitation. (S4A located in storage position). S5A Installed To enable the RESET front panel pushbutton. S5A Removed To secure against unauthorized meter reset.

7.0 SIGNAL AND POWER INPUT CONNECTIONS

7.1 Introduction

The following describes how to connect your sensors to your meter with and without sensor excitation and how to connect the AC power to your meter. Prior to wiring the sensor to the meter, check with a multimeter that a proper excitation exists.

7.2 Signal Input Connections

The following figures (7-1 through 7-5) show the connections for voltage, current and potentiometer inputs:
Figure 7-1. Current Input Without Sensor Excitation
CF 67 18 M1291/N/0403 11279ML-02 Rev. A
Figure 7-2. Current Input With Sensor Excitation
Figure 7-3 Voltage Input Without Sensor Excitation
Figure 7-4 3-Wire Voltage Input With Sensor Excitation
Figure 7-5 4-Wire Voltage/Bridge Input With Sensor Excitation
CF 67 19 M1291/N/0403 11279ML-02 Rev. A
Figure 7-6 Bridge Input With External Sensor Excitation
Figure 7-7 Potentiometer Connections with Internal Power Supply & Ratio Measurement
Figure 7-8 Potentiometer Connections with External Power Supply & Ratio Measurement (Remove jumper
S2-T)

7.3 AC Wiring Connection

The orange (power) connector must be wired according to the following table (also refer to Figure 7-9).
USA WIRING CODE
Black Brown ~AC LINE (L) 1 White Blue ~AC Neutral(N) 2
Green Green/Yellow ~AC Protective Earth Ground 3
EUROPE WIRING CODE
CONNECTION
PIN # ON ORANGE CONNECTOR
CF 67 20 M1291/N/0403 11279ML-02 Rev. A
Loading...
+ 56 hidden pages