Cooper Instruments DFI-INFINITY User Manual

4
DFI Infinity-Using This Quick Start Manual
Use this Quick Start Manual to get your High Performance Strain Gage Indicator up and running right out of the box. These instructions use the factory default settings of 100mV unipolar input and 10 Vdc sensor excitation. If you have voltage or current input, refer to the main manual. To start your unit:
¥ Wire the sensor
¥ Configure the meter, using the front panel buttons and the
configuration menus
Before You Begin
Your unit should have the following parts:
¥ Meter
¥ Front panel button cover
¥ Panel mounting gaskets
¥ ac Power Connector (orange -P1), Input Connectors (2)
(P3 and P9), and rear protective cover (mounted).
Contact the Customer Service Department using the number listed on the front of this manual if any of these parts are missing, or if you have questions.
In addition to the unit and related parts, you will need the following items to set up your unit:
¥ ac power as listed on meterÕs product/ID label
¥ External sensor (e.g.; load cell)
¥ 1/8Ó Phillips head screwdriver
¥ 1/8Ó flat blade screwdriver
Key Sequences and Menus
MENU key Sub Menu 1
MENU key Submenu 1 Action/Description
(/MIN)
L1CNF
Skip past
L2CNF
Skip past
L3CNF
Skip past
L4CNF
Skip past
INPUT bridge
Select meter input
Sub Menu 1 choice (BRIDGE)
RDG.CNF RDG.1=0
Scaling y = mx+b
RDG.2=0
Active decimal point
RDG.3=0
Normal display brightness
RDG.4=1
Leading zeroes suppressed
RDG.5=0
Not used, skip past
RDG.6=1
Activates RDG SC/OF
RDG.7=0
External hard reset vs peak reset
RDG SC
See previous formula in "Determine Meter Scaling Factor" section.
RDG OF 000000
INCNF INP.1=0
60 Hz ac power
INP.2=0
Slow reading (S1A jumper omitted)
INP.3=0
Unipolor input (S1B jumper omitted)
INP.4=0
Std, for BRIDGE inputs
INP.5=0
Not used, skip past
INP.6=0
Disables IN.SC.OF (Input Scale and Offset)
INP.7=1
Ratiometric input
IN.SC.OF
Skip past
DEC PT FFFF.FF
Select decimal point
CNT BY
Press RESET twice
Now you are in RUN mode. If the meter does not read zero, refer to ÒConfigure Reading OffsetÓ section.
Determine Meter Scaling Factor
Calculate the scaling factor so the meter displays the desired engineering units. Assuming no known load, use the formula:
RDG SC = display span/[(sensorÕs mV/V output) (10,000)]
where: display span = desired display at full scale
sensorÕs output span = mV/V
Configure the Meter
Use the front panel buttons to access the configuration menus, to either verify or set the unit values. The first table that follows describes functions of each button on the front of the meter. The second table summarizes the key sequences you must press and the menus you will see to get your meter running. For a step-by-step procedure of specific tasks, refer to the configuration sections following the tables.
Meter Button Descriptions
Press This Button To:
Access the configuration program menus and move from one menu to the next.
Enter and scroll through a submenu.
Change the value of a submenu.
Move backward one menu (press once), or exit the configurations menus (press twice).
Change the Setpoints.
/MAX
/MIN
MENU
Connect ac Power
1. Remove the rear protective cover and set it aside. The
cover is secured with a Phillips-head screw.
2. Locate connector P1 on the bottom-left-rear of the unit. The connector has three screw-down terminals (see below).
3. Insert the correct wire in each terminal and tighten the lockdown screw. Tug gently on each wire to verify the connection.
Wiring a Millivolt Output Sensor
The following example shows wiring a bridge input to the meter.
1. Locate connectors P3 and P9 on the right-side rear of the unit.
2. Attach the wires and tighten the retaining screws. Tug gently on the wires to verify the connection.
Wiring Example (Factory set at 10Vdc Excitation
3. Apply ac power. The front panel of the unit flashes
RESET2
. If it does not: a. Remove ac power. b. Verify the P1 power and sensor connections. c. Check your power source. d. Apply ac power again.
4. Replace the rear cover. Thread the sensor wires through the slots on the side of the cover. Replace the rear cover retaining screw.
START HERE
2
3
GASKET
P1
L
1
N
2
©
3
1 2
P9
3
1 2
P3
3
~AC LINE ~AC NEUTRAL ~AC EARTH GROUND
P1
L
1
N
2 3
+
EXC
+
SIG
SIG
EXC
NC NC
+
E
1
+
S
S
E
P9
2 3
1 2 3
METER
P3
RESET
SETPTS
56
7 8
To Configure Scaling Factor:
1. Press /MIN to display and to select the digit (or decimal point) you want to change.
2. Press /MAX to increase the value of the selected digit.
3. Repeat steps 1 and 2 until each digit is the desired value (your calculated scaling factor).
4. Press MENU. The meter displays:
To Configure Meter Inputs:
1. Press MENU until the meter displays:
2. Press /MIN to display:
3. Press /MAX, if necessary to change the configuration value.
4. Repeat steps 2 and 3 for
INP.2
through
INP.7
5. Press MENU. The meter displays:
To Configure Type of Input:
1. Press MENU until the meter displays:
2. Press
/MIN to display a flashing input type.
3. Press MENU.
The meter displays:
4. Press MENU and
bridge
stops flashing.
5. Press MENU.
The meter displays:
To Configure Meter Display Readings:
1. Press /MIN to display:
2. Press /MAX, if necessary to change the configuration value to 0or 1.
3. Repeat steps 1 and 2 for
RDG.2
through
RDG.7
4. Press MENU.
The meter displays:
To Set Decimal Point Position:
1. Press MENU until the meter displays:
2. Press /MIN to display: Press /MAX to move the decimal point to the desired location.
3. Press MENU. The meter displays:
4. Press RESET twice. The meter flashes and displays an output reading.
The meter is now in RUN mode.
Configure Reading Offset
Now that you are in the run mode with a transducer connected to the meter, do the following:
1. Simulate a load on the transducer (leave the pressure port open).
2. Note the display reading. LetÕs assume the display shows 43.5.
3. To make the display show zeroes, press MENU until the meter displays:
4. Press /MIN to display the previous reading offset value.
5. Using /MIN to scroll through the digits and /MAX to change the value, enter the value -0043.5.
6. Press MENU. The meter displays:
7. Press RESET twice. The meter flashes and then displays a value.
Your meter is now in RUN mode and operational.
If You Have Bipolar Input ±50mV
The typical setting for your meter is unipolar. If, however, you have bipolar input ±50mV, you must install jumper S1B. Remove the outer panel mounting sleeve to expose the jumper.
S1 Jumper Location on Signal Input Board
In addition, you must set configuration menu value INP.3=1 (under IN CNF menu). Refer to the Configuration sections of this Quick Start manual.
MQS1291/N/0401 12458ML-01 Rev. D
input1
䊱䊳
/MAX
SETPTS /MIN MENU RESET
stored
䊱䊳
SETPTS /MIN MENU RESET
/MAX
bridge
䊱䊳
/MAX
SETPTS /MIN MENU RESET
stored
䊱䊳
/MAX
SETPTS /MIN MENU RESET
rdg.cnf
䊱䊳
/MAX
SETPTS /MIN MENU RESET
rdg.1=0
䊱䊳
/MAX
SETPTS /MIN MENU RESET
SETPTS /MIN MENU RESET
stored
䊱䊳
/MAX
rdg SC
䊱䊳
/MAX
SETPTS /MIN MENU RESET
0.00000
䊱䊳
/MAX
SETPTS /MIN MENU RESET
stored
䊱䊳
/MAX
SETPTS /MIN MENU RESET
rdg of
䊱䊳
/MAX
SETPTS /MIN MENU RESET
in cnf
䊱䊳
/MAX
SETPTS /MIN MENU RESET
inp.1=0
䊱䊳
/MAX
SETPTS /MIN MENU RESET
SETPTS /MIN MENU RESET
stored
䊱䊳
/MAX
in.sc.of
䊱䊳
/MAX
SETPTS /MIN MENU RESET
DeC pt
䊱䊳
/MAX
SETPTS /MIN MENU RESET
FFFF.FF
䊱䊳
/MAX
SETPTS /MIN MENU RESET
stored
䊱䊳
/MAX
SETPTS /MIN MENU RESET
cntby
䊱䊳
/MAX
SETPTS /MIN MENU RESET
reset2
䊱䊳
/MAX
SETPTS /MIN MENU RESET
rdg of
䊱䊳
/MAX
SETPTS /MIN MENU RESET
-0043.5
䊱䊳
/MAX
SETPTS /MIN MENU RESET
reset2
䊱䊳
/MAX
SETPTS /MIN MENU RESET
R
M
S1
A
C
A
B
B
K
E
H
G
D
F
P
L
Q
N
J
STU
V
S2
J9
J3
stored
䊱䊳
/MAX
SETPTS /MIN MENU RESET
in cnf
䊱䊳
/MAX
SETPTS /MIN MENU RESET
Loading...