Cooper&Hunter CH-HRV1.5KDC, CH-HRV5KDC, CH-HRV6.5KDC, CH-HRV8KDC, CH-HRV2.5KDC User Manual

...
USER’S MANUAL
ENERGY RECOVERY
VENTILATION SYSTEM
MODELS:
Attention
For proper operation, please read and keep this manual carefully Designed by Cooper&Hunter International Corporation, Oregon, USA
www.cooperandhunter.com
Contents
Safety Considerations------------------------------------------------------------3,4
Unit Specifications--------------------------------------------------------------- 5,6
Dimensioned Drawings----------------------------------------------------------7,8
Installation Considerations--------------------------------------------------9,10,11
Electrical Installation--------------------------------------------------------------12
Wiring Diagrams---------------------------------------------------------------13,14
Commissioning Information------------------------------------------------------15
Intelligent Controller-------------------------------------------------------16 to 19
Dia Switch ------------------------------------------------------------------------20
Modbus Table --------------------------------------------------------------------21
Maintenance ----------------------------------------------------------------------22
Safety Considerations
Please read the following safety instructions before installation. And ensure that the unit is installed correctly.
Please observe all instruction in order to avoid any injury or damage to equipment or property.
Safety attentions
The following symbols indicate potential levels of caution.
The following symbols indicate compliance which must be observed
Situations with a risk or death or serious injure.
Not allowed or Stop
Situations with a risk of injury or equipment/property damage.
Must follow or obliged
Installation to be carried out by qualified person, End Users must not install, move or re-install this equipment by themselves
Installation engineers must follow this man­ual strictly. Improper action can create a health hazard and reduce efficiency of the unit
Unit must be installed strictly following this manual and mounted to a weight bearing surface for the weight of the unit
During maintenance or repair, the unit and circuit breaker must be switched off. Other­wise electric shock could occur.
An anti-bird net or similar device should be installed to outside vents. Ensure there are no obstructions to or in the ducts
Fresh air vent must be far enough away from any flue gas discharge or areas where hazardous vapors are present
Electric engineering must follow national regulations and the manual, use special ca­bles. Less capacity cables and improper en­gineering can cause electric shock or fire.
Ground wire cannot be connected to gas pipe, water pipe, lighting rod or telephone line etc. Incorrect grounding can cause electric shock.
Power cable and wires must be installed by a qualified electrical engineer. Improper
3
connection can cause over heating. Fire and loss of efficiency.
Insulation between the metal ducting and wall penetration must be installed if the ducting penetrates metal wall cladding, to avoid risk of electric shock or current leak­age.
Use only approved installation hardware and accessories. Failure to observe can re­sult in fire risk, electric shock and equip­ment failure
The outdoor ducts must be installed facing downwards to avoid rain water entering. Improper installation can cause water leak­age.
To avoid condensation, insulation should be fitted to fresh air ducts. Other ducting may also require insulation depending on dew point conditions.
The cover of wiring box must be pressed down and closed to avoid dust and dirt en­tering. Excess dust and dirt can cause over­heating of terminals and result in fire or electric shock.
Where the unit is positioned, at high level in a hot humid situation. Please ensure suffi­cient ventilation is available
Correctly sized MCB must be fitted to the unit suitable earth leakage protection should also be installed to avoid risk of elec­tric shock or fire.
Safety Considerations
Safety Considerations
Do not install the unit in an extremely hu­mid conditions, as it may result in electric shock and pose a fire risk.
Don not install the unit in areas there any poisonous or caustic gases are present.
Do not use the units as the primary kitchen extract grease and fatty deposits can block the heat exchanger, filter and pose a fire risk.
Do not install the unit near open flame as it may result in over heating and pose a fire risk
Acidic or alkali environments can cause poisoning or a fire
Rated supply voltage must be maintained, otherwise this may cause fire.
4
Specifications
Model
Performance
Airflow (m3/h) 150 250 350 500
Airflow (l/s) 43 71 100 143
Enth. Eff (%)
Temp. Eff (%) 75 75 75 75
Noise Db(A) 23 24 28 30
Power Supply 220V/1Ph/50Hz
Input Power (W) 51 81 112 143
Power Cable 2x1.5mm
Control Cable 2x0.5mm
Control
Fan Type DC Fan Motors
Fan Speeds (Supply) 10 Speed Fan Control
Fan Speeds (Exhaust) 10 Speed Fan Control
Summer Bypass Yes (Automatic with adjustable range)
Defrost Yes (Automatic with adjustable range)
CO2 Control Optional controller available (On / Off control with adjustable range)
Heating 70 70 69 67
Cooling 63 63 66 62
Standard Yes (7-Day Time-clock)
(BMS)
Modbus
CH-HRV1.5KDC CH-HRV2.5KDC CH-HRV3.5KDC CH-HRV5KDC
2
2
Yes
Fan Boost Contacts Yes (3x available connections to Contacts: Closed = Boost to High Speed)
Fire Shutdown Yes (1x available connection to Contact: Closed = Shutdown)
Weight (Kg) 25 29 37 43
Size (WxHxD) 580x264x808 599x264x882 804x270x882 904x270x962
Duct Size 150 150 150 200
5
Specifications
Model
Performance
Airflow(m3/h) 650 800 1000 1500 2000
Airflow (l/s) 186 229 286 429 571
Enth. Eff (%)
Temp. Eff (%) 75 75 75 75 75
Noise Db(A) 32 35 35 38 38
Power Supply 220V/1Ph/50Hz
Input Power (W) 205 290 305 580 610
Power Cable 2x1.5mm
Control Cable 2x0.5mm
Control
Fan Type DC Fan Motors
Fan Speeds (Supply) 10 Speed Fan Control
Fan Speeds (Exhaust) 10 Speed Fan Control
Summer Bypass Yes (Automatic with adjustable range)
Defrost Yes (Automatic with adjustable range)
CO2 Control Optional controller available (On / Off control with adjustable range)
Fan Boost Contacts Yes (3x available connections to Contacts: Closed = Boost to High Speed)
Fire Shutdown Yes (1x available connection to Contact: Closed = Shutdown)
Weight (Kg) 64 71 83 165 189
Size (WxHxD) 884x340x1222 884x388x1322 1134x388x1322 884x785x1322 1134x785x1322
Duct Size 200 250 250 300 300
Heating 68 71 71 71 71
Cooling 62 65 65 65 65
Standard Yes (7-Day Time-clock)
(BMS)
Modbus
CH-HRV6.5KDC CH-HRV8KDC CH-HRV10KDC CH-HRV15KDC CH-HRV20KDC
2
2
Yes No
6
Dimensioned Drawings
CH-HRV1.5KDC to HRV5KDC Models
CH-HRV6.5KDC to HRV10KDC Models
7