Cooper Controls ONW-D-1001-MV-N-W, ONW-D-1001-MV-N-B, ONW-D-1001-MV-N-V, ONW-D-1001-MV-N-LA, ONW-D-1001-MV-N-G Installation Instructions Manual

Installation Instructions
Cooper Controls 203 Cooper Circle, Peachtree City, GA 30269 800-553-3879 www.coopercontrol.com
LOAD
120 to 277 VAC
BLACK
BLUE
NEUTRAL
GROUND
GREEN
WHITE
,
36
8
,
Minor Motion, IR
Major Motion, IR
20
,
Maximum coverage area may
vary somewhat according to room
shape and the presence of obstacles.
The NEMA WD 7 Guide and robotic
method were utilized to verify
coverage patterns.
Minor Motion, Ultrasonic
Major Motion, Ultrasonic
,
10
8
,
,
15
20
,
General Information
• Read all instructions on both sides of this sheet first.
• Install in accordance with ALL local codes.
Specifications
Technology: Passive Infrared (PIR) and
Ultrasonic (US)
Electrical Ratings
120 VAC:
• Incandescent/Tungsten – Max. load: 6.7 amps, 800W, 50/60 Hz
• Fluorescent/Ballast – Max. load: 10 amps, 1200W, 50/60 Hz
Motor Load: ¼ HP @ 125 VAC 230/277 VAC:
• Fl uo re sc en t/ Ba ll as t – Ma x. lo ad : 9.8 amps,
2700W, 50/60 Hz
Ballast Compatibility: Compatible with magnetic and electronic ballasts
No Minimum Load Requirement Time Delays: Self-Adjusting, 15 seconds/test (10 min
Auto), Selectable 5, 15, 30 minutes
Description
The ONW-D-1001-MV-N Occupancy Sensing Wall Switch is a Passive Infrared (PIR) and Ultrasonic (US) motion
sensing lighting control and conventional Wall Switch all-in-one, used for energy savings and convenience.
The sensor combines PIR and US technologies to monitor a room for occupancy.
PIR Technology
The sensor’s segmented lens divides the field of view into sensor zones, and detects the changes in temperature
that are created when a person, or part of a person as small as a hand, passes into or out of a sensor zone.
US Technology
The sensor produces a low intensity, inaudible sound. It detects occupancy from changes in the acoustic waves caused by motion, such as reaching for a telephone, turning a page in a book, walking into a room, turning in a swiv­el chair, etc. The sensor does not respond to audible sound.
Dual Technology sensors ensure the greatest sensitivity and coverage for tough applications thus saving additional energy. PIR is used to turn the lights ON and then either or both technologies are used to keep the lights ON.
The ONW-D-1001-MV-N allows the control of one load with one occupancy sensor switch.
The sensor can be configured to enhance energy savings by setting the unit for manual ON operation.
In Automatic ON Mode, the lights turn ON automatically when a person enters the room. In Manual ON Mode, the lights are turned ON by pressing the universally recognized light icon Pushbutton. In either mode, the lights stay ON as long as the sensor detects motion in the room. When the room is vacated, the lights turn OFF automatically after a preset Time Delay interval.
The sensor includes self-adaptive technology that continually adjusts to conditions by adjusting sensitivity and Time Delay in Real-time. By adjusting sensitivity and Time Delay automatically, the sensor is maximizing the poten­tial energy savings that are available in the particular application.
The EcoMeter provides a visual indicator of energy usage, increasing end user awareness and reminding individu­als to take control of their lighting to maximize energy savings.
The Daylighting feature prevents lights from turning ON, when the room is adequately illuminated by natural light.
NeoSwitch Dual Technology Single Relay
Mo de l # ON W- D- 10 01 -M V- N- W Mo de l # ON W- D- 10 01 -M V- N- V Mo de l # ON W- D- 10 01 -M V- N- LA
Occupancy Sensing Wall Switch
Mo de l # ON W- D- 10 01 -M V- N- G Mo de l # ON W- D- 10 01 -M V- N- B
(Neutral Required)
EcoMeter Operation
• For indoor use only.
Load 1 EcoMeter LED
FF
O
N
O
N
O
FF
O
Coverage: Major motion – 1000 sq. ft.
Minor motion – 300 sq. ft.
Light Level Sensing: 0 to 200 foot-candles Operating Environment:
• Temperature: 32° F – 104° F (0° C – 40° C)
• Relative Humidity: 20% to 90% Non-condensing
Ho usi ng: Du rab le, inject ion molded hous ing. Polycarbonate resin complies with UL94VO.
Size:
• Mounting Plate/Strap Dimensions:
4.195" H x 1.732" W (106.553 mm x 44 mm)
• Product Housing Dimensions: 2.618" H x 1.752" W x 1.9" D (66.5 mm x 44.5 mm x 48.26 mm)
LED Indicators: Red LED indicates PIR detection; Green LED indicates Ultrasonic detection; Green LED acts as EcoMeter or night light locator.
Walk-Through feature maximizes energy savings by not leaving the lights ON after a momentary occupancy. The sensor will switch the lights ON when it detects a person entering the area. If the sensor does not continue to detect motion 20 seconds following the initial activation, it will automatically go to a shorter 2 minute Time Delay.
Coverage
The ONW-D-1001-MV-N is designed for offices up to 300 square feet. Coverage testing has been performed accord­ing to the NEMA WD7 Guideline.
Location
When installing the ONW-D-1001-MV-N in a new junction box, choose the switch location carefully to provide opti­mum coverage of the occupied area. When replacing an existing Wall Switch, bear in mind that there must be a clear Line-of-sight between the sensor and the area to be covered. Avoid pointing the ONW-D-1001-MV-N directly into the hallway where it may detect passers-by.
Action EcoMeter Benefit
person enters the space and
A
one of the loads is activated
he area is vacated and the
T ights turn OFF automatically
l
A person turns the lights OFF
manually upon exiting an area
The daylighting feature prevents
he lights from automatically
t
urning ON when a person
t
enters an area
OFF
ON
O
ON
N
ncreased awareness of energy savings;
I
cts as a night light locator
A
Increased awareness of energy savings and
reminds individuals to take control of their
lighting for additional savings; Acts as
a night light locator.
Increased awareness of energy savings and
lets the individual know that the
daylighting feature is working
Installation
The ONW-D-1001-MV-N can be installed in any standard single gang box. It may be installed in the same manner as an ordinary Wall Switch.
• Wire the ONW-D-1001-MV-N as described in the wiring section.
• Mount the ONW-D-1001-MV-N in the junction box.
Wiring
CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned OFF at the branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the main switch for a fluorescent lighting circuit, the circuit breaker should be marked “SWD.” All installations should be in compliance with the National Electric Code and all state and local codes.
NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is shortened by frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the effects of cycling.
1. Make sure power is turned OFF at the branch circuit breaker.
2. Wire units as shown in wiring diagrams per applicable voltage requirements.
3. Mount unit to Wall Box.
4. Turn power back ON at the branch circuit breaker and wait 2 minutes for the unit to stabilize.
5. Make necessary adjustments. (See Checkout and Adjustments section)
6. Install Wall Switch plate.
Wiring Diagram 1:
120 to 277 VAC single level single circuit wiring diagram
Cooper Controls 203 Cooper Circle, Peachtree City, GA 30269 800-553-3879 www.coopercontrol.com
L
OAD 1
120 to 277 VAC
BLACK
B
LUE
NEUTRAL
GROUND
GREEN
W
HITE
L
OAD 2
A/B SWITCHING USING TOGGLE SWITCH TO TURN OFF SECOND LOAD
L
OAD 1
BLACK
BLUE
N
EUTRAL
THREE-WAY WIRING DIAGRAM: LIGHTS WILL TURN OFF, WHEN UNIT THAT WAS TURNED ON LAST AND/OR DETECTED MOTION LAST TIMES-OUT.
G
ROUND
GREEN
W
HITE
1
20 to 277 VAC
BLACK
BLUE
GROUND
G
REEN
W
HITE
T
RAVELER
W
IRES
Wiring Diagram 2:
12345678
9 10 11 12
Not Used
5 Minutes
Auto*
*Self-Adjusts to
10 min. user mode
Time Delay
DIP Switch
Activation PIR Sensitivity Override
Relay 1
EcoMeter
Walk-Through Mode
Default =
30 Minutes
15 Minutes
12
D
IP Switch Legend
6
q
p
Disable
Enable
3
qqqq
q
pp
pp
p
Auto
Manual
5
q
p
Full
50%
8
q
pp
q
7
Enable
Disable
4
Disable
Enable
Not Used Maintain Lights On Not Used
12119 10
q
p
Either
Both
ON/OFF Button
PIR Lens
DIP Switches
Ultrasonic Detection
Daylight
Sensor Level
Adjustment
Ultrasonic Sensitivity
Adjustment
Red (PIR) & Green (US)
Detection LEDs
12345678
9
10 11 12
1 and 2
123456789 10
11
12
120 to 277 VAC single level switch dual level wiring using a toggle switch wiring diagram
Wiring Diagram 3: 120 to 277 VAC single level single circuit three-way wiring diagram
each motion. (If LEDs do not turn ON, go to Installer Adjustments – Sensitivity Adjustment Section)
3. Stand still three to four feet away from sensor for five seconds. LEDs should not turn ON. (If any LED turns ON, note LED and go to Installer Adjustments – Sensitivity Adjustments section)
4. Walk outside the room and wait 15 seconds for the lights to turn OFF. (If lights do not turn OFF go to Installer Adjustments Section)
5. Re-enter the room to activate sensor. (If lights do not turn ON go to Troubleshooting Section)
6. At this point you can exit the room and let the sensor Time-out. When the sensor times-out and is inactive for five minutes, the unit will go to a 10 minute Time Delay user mode setting.
Note:
o place into Test Mode, toggle DIP Switch 12 out of its current position, wait 3 seconds, and then back in to its original position.
T
Installer Adjustments
Sensitivity Adjustments
Ultrasonic Sensitivity (Green LED) – Using a small flathead screw driver turn the green potentiometer so that the arrow points UP.
1. Stand in different areas of the room and wave your hands.
2. If the Green LED does not turn ON, increase the US sensitivity by turning the green potentiometer clockwise in small increments. Repeat Step 1.
3. Stand still three to four feet away from sensor for five seconds. LED should not turn ON.
4. If Green LED turns ON without motion or is constantly ON decrease the US sensitivity by turning green potentiometer counter-clockwise in small decrements. Repeat Step 3.
Note:
Do Not adjust sensitivity higher than necessary.
as the self-adjusting feature is enabled, the switch will respond to each pair of False-offs with no normal off in between by alternately making slight adjustments to either Time Delay (by 2 minute increments) or sensitivity, so there should be no need for manual adjustment. If manual adjustment is desired, refer to Time Delay settings in DIP Switch legend. Reset sensor Time Delay to factory settings by moving DIP Switches 1 and 2 down. (If DIP Switches 1 and 2 are already down, toggle DIP Switch 1 out of its current position, wait 3 seconds, and then back to its original position)
Override
The override setting allows the sensor to operate as a service switch in the unlikely event of failure.
1. Move DIP Switch 8 up.
2. The Pushbutton can be used to manually turn lights ON or OFF.
Troubleshooting
Issue Possible Causes Suggestions
Press Pushbutton. If Auto Mode
is desired change Activation Mode to Auto.
Check EcoMeter LED. If LED is ON this is
Press the Pushbutton to turn the lights back ON.
If all lights are required to turn ON
adjust daylight potentiometer.
Lights Will Not Turn ON
automatically
Sensor is in Manual ON mode
Sensor was turned OFF manually. If the Sensor was turned OFF manually before the Time Delay
expired, lights will remain OFF for the remainder
of the Time Delay.
Daylight Feature Enabled
an indication that the lights were turned OFF manually.
CAUTION: If a room is wired for two circuits using two separate hot leads, it is very important to connect only one circuit per relay. Both circuits must be fed from the same phase.
DIP Switch Settings
Checkout and Adjustment
flow on the operation of the ONW-D-1001-MV-N. Use only insulated tools to make adjustments.
and stabilize.
Self-Adjust Mode
Time Delay, US and PIR sensitivity. In preparation for the Installer Test, the Time Delay is set to 15 seconds, after the sensor is installed, powered ON and has stabilized, the unit will Time-out 15 seconds after the last motion detected. Coverage and sensitivity can be confirmed by watching the Green (US) and Red (PIR) indicator LEDs on the front of the sensor, while moving around the room.
1. Walk around the room and monitor LEDs.
2. Stand in different parts of the room and wave your
Adjustments should be made with the HVAC system on so that the installer will be able to detect the effect of air-
Immediately after applying power to the lighting circuit, wait approximately two minutes for the switch to power up
Sensor is shipped in self-adjust mode. This applies to
hands. LEDs should only turn ON for one second with
PIR Sensitivity
1. Stand in different areas of the room and wave your hands.
2. If the Red LED does not turn ON, check for any obstructions.
3. Stand still three to four feet away from sensor for five seconds. LED should not turn ON.
4. If Red LED turns ON without motion or is constantly on adjust PIR sensitivity to 50 % by moving DIP Switch 5 up.
ON/OFF Disabled Feature
1. ON/OFF Button Disable Option – When selected this option disables the ON/OFF button and sensor becomes automatic only control regardless of the setting for automatic or manual activation. This feature will not allow someone to turn light(s) OFF via the Pushbutton while people are in common areas such as restroom, break room, and copy room areas.
Field-of-view outside the space
1. Adjust PIR sensitivity to 50 % by moving DIP Switch 5 up.
2. Use non-reflective tape strips to cover the portions of the sensor lens that view outside the space.
3. Adjust Ultrasonic Sensitivity.
Daylight Adjustments
The daylighting feature prevents the lights from turning ON when the room is adequately illuminated by natural light. If there is enough light in the room regardless of occupancy, the sensor will hold the lights OFF. If there is not enough light in the room, the sensor will allow the lights to turn ON when occupied. The sensor will not allow the daylighting feature to turn the load OFF until the space is vacant or the light level rises above the setpoint and the Time Delay expires. While in Manual Activation Mode, if someone attempts to turn the load ON and there is sufficient daylight available the Daylighting feature will hold the lights OFF.
• Set the light level when the ambient light is at the level where no artificial light is needed. If this feature is not needed, leave the light level at maximum (fully CW).
1. With the load(s) ON, put the sensor into Test Mode. To place into Test Mode, toggle DIP Switch 12 out of its current position, wait 3 seconds and then back in to its original position.
2. Set the Light level to minimum (fully CCW).
3. Let the sensor Time-out so lights are OFF. Enter the space and lights should remain OFF.
4. Make sure not to block the sensor from the daylight source and adjust the light level potentiometer CW in small incre­ments. (Pause 5 seconds between each adjustment)
5. Once the lights are ON, the load connected to the sensor will not turn ON if light levels are above the current illumination.
Time Delay Adjustments
People who remain very still for long periods of time may need a
longer Time Delay than the default setting of 10 minutes. As long
Power interruption Check incoming voltage and/or wiring.
Lights
Will Not
Daylight Feature Enabled
If all lights are required to turn ON
adjust daylight potentiometer.
Turn ON
manually
Power interruption Check incoming voltage and/or wiring.
If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879
Override Make sure sensor is not in Override Mode (DIP Switch 8 up).
If sensor is in Self-Adjust Mode, it may be possible for the
Self-Adjust
unit to have increased the Time Delay to a 30 minute delay.
If the lights do not turn OFF after 30 minutes follow next step.
Lights
Will Not
Turn OFF
automatically
30 Minute Delay
Ultrasonic Sensitivity set High
Maximum Time Delay is 30 Minutes. Check DIP Switches
to verify DIP Switch settings. If lights do not turn OFF at the
set Time Delay, check next step.
Lower sensitivity by turning green
potentiometer CCW in small decrements.
PIR activated by heat source other than occupant Move DIP Switch 5 up.
Lights
Will Not
Turn OFF
Call Technical Services
manually
If lights will still not turn OFF, call Technical Services at 1-800-553-3879
Limited Warranty
All products manufactured by Cooper Controls and identified with the Greengate brand are warranted to be free from defects in material and workmanship and shall conform to and perform in accordance with Seller’s written specifications for a period of: Five (5) years from date of shipment for all occupancy sensors and Three (3) years from date of factory invoice for our hardware and software on Lighting Control Panels. We warranty all our standard relays for a period of 10 years from date of factory invoice. We guarantee the performance of our system to specifications or your money back. This warranty will be limited to the repair or replacement, at Seller’s discretion, of any such goods found to be defective, upon their authorized return to Seller. This limited warranty does not apply if the goods have been damaged by accident, abuse, misuse, modification or misapplication, by damage during shipment or by improper service. There are no warranties, which extend beyond the hereinabove-limited warranty, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE IMPLIED WARRANTY OF FITNESS. No employee, agent, dealer, or other person is authorized to give any warranties on behalf of the Seller or to assume for the Seller any other liability in connection with any of its goods except in writing and signed by the Seller. The Seller makes no representa­tion that the goods comply with any present or future federal, state or local regulation or ordinance. Compliance is the Buyer’s responsibility. The use of the Seller’s goods should be in accordance with the provision of the National Electrical Code, UL and/or other industry or military standards that are pertinent to the particular end use. Installation or use not in accordance with these codes and standards could be hazardous.
Printed in Malaysia
P/N 910-0539 REV B
Loading...