Cooper Bussmann EMN IF677 User Manual

APPLICATION
EMN Series Manual Line Starters and Enclosures are used to provide motor starting protection and manual across-the-line starting and stopping of single and poly-phase AC motors.
EMN Series Manual Line Starters and Enclosures are suitable for use in Class I, Groups C, D; Class II, Groups E, F, G and Class III hazardous (classified) locations, as defined by the National Electric Code® as well as in damp, wet or corrosive locations.
EMN Series Manual Line Starters and Enclosures should be installed, inspected, maintained, and operated by qualified and competent personnel.
INSTALLATION
1. Select a mounting location that will provide suitable strength and rigidity for supporting all contained wiring and control devices. Figure 1 shows the mounting dimensions of EMN Series enclosures. Drill two 7/16 inch mounting holes.
2. Securely fasten enclosure to the mounting surface then attach into conduit system.
3. Remove the six cover bolts then lift cover off and carefully set it aside to prevent damage to the ground joint.
4. EMN Enclosure furnished with starter: Remove starter from enclosure then pull wires into enclosure making sure that they are long enough to make the required connections.
Note: EMN Manual Motor Starter Enclosures ordered complete with starter are furnished with heaters. One heater is furnished with two-pole AC or DC starters and three heaters with three-pole starters.
EMN Enclosure furnished without starter: Select starter from Table 1 on page 2 (ordered separately). Install heaters on starter (ordered separately). Refer to heater selector listings. Pull wires into enclosure.
5. Mount starter into enclosure and make electrical connections utilizing the wiring scheme established for the starter.
CAUTION
Hazardous location information specifying class and group listing of each device is marked on the nameplate of each enclosure. Also note that:
No conduit openings are to be added in the field.
All unused conduit openings must be plugged and these plugs must be a minimum of 1/8 in. thick and have a minimum of five threads engaged.
All conduits entering and leaving the enclosure must be sealed with explosion-proof seals within 18 in. of the enclosure.
Motor Starter EMN Series Manual Line Starters and Enclosures
Installation & Maintenance Information
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
IF677
WARNING
To provide protection against fire or shock hazard, the electrical power must be OFF before and during instal­lation and maintenance.
CAUTION
Hammers or prying tools must not be allowed to damage the flat ground-joint surfaces. Do not handle the covers roughly, or place them on surfaces that might damage or scratch the flat ground-joint surfaces.
Figure 1 - Dimensions
IF 677 • 03/03 Copyright © 2003, Cooper Industries, Inc. Page 1
National Electrical Code ®is a registered Trademark of the National Fire Protection Association.
All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy or completeness thereof are not guaranteed. In accordance with Crouse-Hinds "Terms and Conditions of Sale", and since conditions of use are outside our control, the purchaser should determine the suitability of the product for the intended use and assumes all risk and liability whatsoever in connection therewith.
Cooper Industries Inc. IF 677 Crouse-Hinds Division Revision 2 PO Box 4999, Syracuse, New York 13221 • U.S.A. Revised 03/03 Copyright© 2003, Cooper Industries, Inc. Supercedes 04/02
6. Test for wiring correctness with continuity checks and also for unwanted grounds with insulation resistance tester.
7. Place starter handle in OFF position making sure that the internal mechanism of the cover will properly engage the starter.
8. Install cover. Securely tighten all cover bolts making certain that no cover bolts are omitted. Use only bolts supplied with the enclosure.
9. Pour sealing compound into sealing fittings in accordance with the instructions supplied with each of the approved fittings and sealing compound package labels.
MAINTENANCE
1. Frequent inspection should be made. Aschedule for main­tenance check should be determined by the envi­ronment and frequency of use. It is recommended that it should be at least once a year.
2. If necessary to open enclosure for inspection or service, always disconnect primary power source before opening enclosure.
3. Perform visual, electrical, and mechanical checks on all components on a regular basis.
Visually check for undue heating evidenced by discoloration of wires or other components, damaged or worn parts, or leakage evidenced by water or corrosion in the interior.
Electrically check to make sure that all connections are clean and tight, and that contacts in the components make or break as required.
Mechanically check that all parts are properly assembled, and operating mechanisms move freely.
CAUTION
Clean both ground-joint surfaces of body and cover before installing. Dirt or foreign material must not accumulate on flat ground-joint surfaces. Surfaces must seat fully against each other to provide a proper explosionproof seal.
EMN Enclosure NEMA
Catalog No. Size Poles (Phase) Catalog Number
M-0
2 (1 Ph) 3 (3 Ph)
B100M0BX B100M0CX
M-1
2 (1 Ph) 3 (3 Ph)
B100M1BX B100M1CX
M-1P 2 (1 Ph) B100MDBX
1.
Two-pole starters require on heater, three-pole starters require
three heaters. These should be selected in accordance with t
he manufacturer's
recommendations. Most explosionproof motors are rated at 55oC, heaters should be selected accordingly.
Table 1
EMN24
Cutler-Hammer - B100 Series
Manaul Motor Line Starters
1
Loading...
+ 4 hidden pages