D & D0 LOW VOLTAGE FUSE SYSTEM
For more information visit our website at www.bussmann.com
2
Single-pole fuse bases D0
D0 FUSE BASES
Application
The D0 fuse bases are designed for use in distribution boxes in domestic
and public buildings. Total security against live parts is achieved by installing
D0 fuse bases into the distribution boxes.
Advantages
- modular construction-module 9 mm
- smaller weight and smaller height (66 mm) provide installation into the
flush-mounting distribution boxes, the depth of which is 80 mm only
- by the aid of gauge-piece key it is possible to change the gauge rings
- the possibility of simple substitution of base D0 1 with D0 2.
Technical data:
Rated voltage U
N
400 V
Rated current I
N
DO1 16 A, DO2 63 A
Cross-section of connecting lead D01 1-4 mm 2 D02 1,5-25 mm 2
Standards IEC 60269, EN 60269,
DIN VDE 0636, SIST EN 60269
type part No. IN(A) screw with without click-on screw cross-section of dimens. weight packaging
protection protection mounting mounting connections connecting lead A (mm) (g) (pcs)
cover cover outlet supply (mm
2
)
D01N - K FRN01C 16 E14 x X 1.5 - 4 53 68 15/300
D01V - K FN01C 16 E14 x X 1.5 - 4 53 66 15/300
D02N - K FRN02C 63 E18 x X 2.5 - 25 57 87 15/300
D02V - K FN02C 63 E18 x X 2.5 - 25 57 80 15/300
D02N M6 - K FRN02C-A 63 E18 x X 2.5 - 25 57 82 15/300
D02V M6 - K FRN02C-SA 63 E18 x X 2.5 - 25 57 80 15/300
D01N FRN01-B 16 E14 x X 1.5 - 4 53 56 15/300
D01V FRN01-SB 16 E14 x X 1.5 - 4 53 59 15/300
D02N FRN02-D 63 E18 x X 2.5 - 25 57 80 15/300
D02V FRN02-SD 63 E18 x X 2.5 - 25 57 77 15/300
D02N M6 FRN02-E 63 E18 x X 2.5 - 25 57 75 15/300
D02V M6 FRN02-SE 63 E18 x X 2.5 - 25 57 72 15/300
Three-pole fuse bases D0
type part No. IN(A) screw with without click-on screw cross-section of dimens. weight packaging
protection protection mounting mounting connections connecting lead A (mm) (g) (pcs)
cover cover outlet supply (mm 2)
D01N/3 - K TFRN01C 16 E14 x X 1.5 - 4 53 216 5/100
D01V/3 - K TFN01C 16 E14 x X 1.5 - 4 53 187 5/100
D02N/3 - K TFRN02C 63 E18 x X 2.5 - 25 57 252 5/100
D02V/3 - K TFN02C 63 E18 x X 2.5 - 25 57 246 5/100
D02N/3 M6 - K TFRN02C-A 63 E18 x X 2.5 - 25 57 237 5/100
D02V/3 M6 - K TFRN02C-SA 63 E18 x X 2.5 - 25 57 231 5/100
D01N/3 TFRN01-B 16 E14 x X 1.5 - 4 53 176 5/100
D01V/3 TFRN01-SB 16 E14 x X 1.5 - 4 53 170 5/100
D02N/3 TFRN02-D 63 E18 x X 2.5 - 25 57 235 5/100
D02V/3 TFRN02-SD 63 E18 x X 2.5 - 25 57 229 5/100
D02N/3 M6 TFRN02-E 63 E18 x X 2.5 - 25 57 220 5/100
D02V/3 M6 TFRN02-SE 63 E18 x X 2.5 - 25 57 214 5/100