Fig. 800 - Adjustable Sway Brace Attachment to Steel
Size Range: 4" (101.6mm) thru 18" (457.2mm) beam width
Material: Steel
Function: Seismic brace attachment to steel.
es:
Featur
This product’ critical to the performance of structural seismic connections. NFP importance of concentric loading of connections and fasteners. Permits secure connection to steel where drilling and/or welding of brace connection could present structural issues.
Installation Instr
longitudinal or lateral sway brace assembly. It is intended to be combined with a
Seismic Bracing
Cooper B-Line/TOLCO B-Line/TOLCO
"braced pipe" attachment to form a complete bracing assembly.
NFPA 13 and/or OSHPD guidelines should be followed.
To Install: Place the Fig. 800 on the steel beam, tighten the cone point set screws on flange until the heads break off. Tighten hex head bolts into clamp body until lock washers are fully flat. Attach other fitting, Fig. 909, 910, 980 or 986. Transitional fitting attachment can pivot for adjustment to proper brace angle.
Approvals: Underwriters Laboratories Listed in the USA (UL) and Canada (cUL). Approved by Factory Mutual Engineering Catalog approved by the State of California Office of Statewide Health Planning and Development
(OSHPD). For additional load, spacing and placement information relating to OSHPD projects, please refer to the Restraint Systems Guidelines.
Finish: Plain. Contact Cooper B-Line for alternative finishes and materials.
Order By: Figure number, type number and size number.
s design incorporates a concentric attachment point which is
uctions:
Fig. 800 is the structural attachment component of a
transitional attachment, "bracing pipe" and a
Cooper B-Line/TOLCO
transitional attachment
Cooper
(FM). Included in our Seismic Restraints
Cooper B-Line/TOLCO
Seismic
Component of State of
California OSHPD Approved
Seismic Restraints System
Set Screws & Hardware
Included
Fits Beam
Part No. Flange
in. (mm) lbs. / (kN) lbs. / (kN) lbs. / (kN) lbs. / (kN)
Max.Design Loads (cULus) Max.Design Load (FM)* Along Beam Across Beam Along Beam Across Beam
800-1 4”- 6” (101.6-152.4) 800-2 6”-8” (152.4-203.2) 800-3 8”-10” (203.2-254.0) 800-4 10”-12” (254.0-304.8) 800-5 12”-14” (304.8-355.6) 800-6 14”-16” (255.6-406.4)
1265 2015 2800 2800
(5.62) (8.96) (12.45) (12.45)
Shown with Fig. 980
brace fitting to
pipe brace
(Across Beam)
800-7 16”-18” (406.4-457.2)
Flange Thickness
ype Maximum
T
in. (mm) lbs. / (kN) lbs. / (kN) lbs. / (kN) lbs. / (kN)
1
3
/4 (19.0)
2 11/4 (31.7)
Max.Design Loads (cULus) Along Beam
Across Beam Along Beam Across Beam
1265 2015 2800 2800
(5.62) (8.96) (12.45) (12.45)
Max.Design Load (FM)*
* The loads listed are axial loads on the brace. The horizontal load capacity, H, of the brace is: H = F x sin ?, where ? is the installation angle measured from the vertical.
Cooper B-Line, Inc.’s (“Cooper B-Line”) seismic bracing components are designed to be compatible only with other Cooper B-Line bracing components, resulting in a listed seismic bracing assembly. Cooper-B-Line’s warranty for seismic bracing components will be the warranty provided in Cooper B-Line’s standard terms and conditions of sale made available by Cooper B-Line, except that, in addition to the other exclusions from Cooper B-Line’s warranty, Cooper B-line makes no warranty relating to Cooper B-Line’s seismic bracing components that are combined with products not provided by Cooper B-Line.
Shown with Fig. 980 brace
fitting to pipe brace
(Along Beam)
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
170