Seismic Bracing
TOLCO™Fig. 1001 - Sway Brace Attachment
Size Range: Pipe size to be braced: 1"
* Pipe size used for bracing: 1"
(25mm)
Material: Steel
Function: For bracing pipe against sway and seismic disturbance.
The pipe attachment component of a sway brace system:
Fig. 1001 is used in conjunction with a Fig. 900 Series fitting and joined together
with bracing pipe per NFPA 13, forming a complete sway brace assembly.
Features: Can be used to brace schedules 7 through 40 IPS. Field adjustable,
making critical pre-engineering of bracing pipe length unnecessary. Unique design
requires no threading of bracing pipe. Can be used as a component of a four-way
Seismic Bracing
riser brace. Comes assembled and ready for installation. Fig. 1001 has built-in
visual verification of correct installation. See installation note below.
Installation Note: Position Fig. 1001 over the pipe to be braced and tighten
two hex head cone point set screws until heads bottom out. A minimum of
1"
(25mm)
pipe extension is recommended. Brace pipe can be installed on top or
bottom of pipe to be braced.
Approvals: Underwriters Laboratories Listed in the USA and Canada (cULus).
Approved by Factory Mutual Engineering (FM). Included in our Seismic Restraints
Catalog approved by the State of California Office of Statewide Health Planning
and Development (OSHPD). For additional load, spacing and placement
information relating to OSHPD projects, please refer to the TOLCO Seismic
Restraint Systems Guidelines, OPA-0300-10.
Finish: Plain or Electro-Galvanized. Contact customer service for alternative
finishes and materials.
Order By: Indicate pipe size to be braced followed by pipe size used for bracing,
figure number and finish.
Important Note: Fig. 1001 is precision manufactured to perform its function as
a critical component of a complete bracing assembly. To ensure performance, the
UL Listing requires that Fig. 1001 must be used only with other TOLCO bracing
products.
(25mm)
and 11⁄4"
thru 8"
(32mm)
(200mm)
IPS.
Schedule 40 IPS.
Component of State of
California OSHPD Approved
Seismic Restraints System
Set Screws
Included
Pipe Max. Horizontal Design Load (UL) - Lbs.
Size For Brace Pipe Size 1” / 11/4”
Sch. 7 Sch. 10 Sch. 40
in. (mm) 1” / 1
1
/4” 1” / 11/4” 1” / 11/4”
1” (25) -- / -- 1000 / 1000 1000 / 1000
1
1
/4” (32) 1000 / 1000 1000 / 1000 1000 / 1000
1
1
/2” (40) 1000 / 1000 1500 / 1500 1500 / 1500
2”
(50) 1000 / 1000 2015 / 2015 2015 / 2015
1
2
/2” (65) 1600 / 1600 2015 / 2765 2015 / 2765
3”
(80) 1600 / 1600 2015 / 2765 2015 / 2765
4”
(100) 1600 / 1600 2015 / 2765 2015 / 2765
6”
(150) 1600 / 1600 2015 / 2765 2015 / 2765
(200) 1600 / 1600 2015 / 2765 2015 / 2765
8”
Part Number & Approx. Wt./100 Max. Horizontal
Pipe
Size
in. (mm) Lbs. (kg) Lbs. (kg) Lbs. (kN) Lbs. (kN) Lbs. (kN) Lbs. (kN)
1” (24mm) Brace Pipe 11/4” (32mm) Brace Pipe 30°-44° 45°-59° 60°-74° 75°-90°
For Sch. 7, Sch. 10, & Sch. 40 Pipe
Design Load (FM)
1, 2, 3
1” (25) 1001-1 X 1 100.0 (45.3) 1001-1 X 11/4 118.0 (53.5) 1800 (8.00) 2550 (11.34) 3120 (13.88) 3490 (25.52)
11/4” (32) 1001-11/4 X 1 100.0 (45.3) 1001-11/4 X 11/4 114.0 (51,7) 1230 (5.47) 1740 (7.74) 2140 (9.52) 2380 (10.58)
11/2” (40) 1001-11/2 X 1 100.0 (45.3) 1001-11/2 X 11/4 115.0 (52.1) 1230 (5.47) 1740 (7.74) 2140 (9.52) 2380 (10.58)
2” (50) 1001-2 X 1 108.0 (49.0) 1001-2 X 11/4 121.0 (54.9) 1230 (5.47) 1740 (7.74) 2140 (9.52) 2380 (10.58)
21/2” (65) 1001-21/2 X 1 138.6 (62.8) 1001-21/2 X 11/4 160.4 (72.7) 800 (3.56) 1130 (5.02) 1380 (6.14) 1540 (6.85)
3” (80) 1001-3 X 1 147.2 (66.7) 1001-3 X 11/4 168.7 (76,5) 850 (3.78) 1200 (5.34) 1470 (6.54) 1640 (7.29)
4” (100) 1001-4 X 1 160.9 (73.0) 1001-4 X 11/4 182.4 (82.7) 850 (3.78) 1200 (5.34) 1470 (6.54) 1640 (7.29)
6” (150) 1001-6 X 1 190.0 (86.2) 1001-6 X 11/4 211.4 (95.9) 510 (2.27) 730 (3.25) 890 (3.96) 990 (4.40)
8” (200) 1001-8 X 1 217.4 (98.6) 1001-8 X 11/4 238.8 (108.3) 510 (2.27) 730 (3.25) 890 (3.96) 990 (4.40)
1
FM Approved when used with 1 or 11/4 inch NPS Schedule 40 GB/T 3091,EN 10255H, or JIS G3451 steel pipe as the brace member.
2
Load rating for LW above refers to FM Approved Lightwall Pipe commonly referred to as “Schedule 7”. These ratings may
also be applied when EN 10220 and GB/T 8163 steel pipe.
3
Load rating for Schedule 10 above may be applied to GB/T 3092,EN 10255M and H, or JIS G3454, FM Approved Thinwall,
or Schedule 40 steel pipes.
Note: See UL load ratings in UL Listed Design Load chart shown under drawing.
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
193
B-Line series Pipe Hangers & SupportsEaton
Seismic Bracing
TOLCO™Fig. 2002 - Sway Brace Attachment
Size Range: Pipe size to be braced: 21⁄2"
steel schedules, copper, plastic, FRP, cast iron and ductile iron.
Consult factory when bracing other than steel. The Fig. 2002
accepts brace pipes sizes 1
1
⁄2"
(40mm)
through schedule 40.
Material: Steel
Function: For bracing pipe against sway and seismic disturbance.
The pipe attachment component of a sway brace system:
Fig. 2002 is used in conjunction with a TOLCO 900 Series sway brace
attachments and joined together with bracing pipe. Install per NFPA 13
and/or TOLCO State of California OSHPD Approved Seismic Restrain Manual.
Features: Unique design will not damage thin wall, plastic,
copper or ductile iron pipe. Easy verification of proper installation
by tightening bolts until ears touch.
Installation: Place Fig. 2002 over pipe to be braced. Slide
bracing pipe through attachment and tighten hex nuts until ears
touch.
Approvals: Underwriters Laboratories Listed in the USA (UL) and
Canada (cUL). Included in our Seismic Restraints Catalog approved
by the State of California Office of Statewide Health Planning and
Development (OSHPD). For additional load, spacing and placement
information relating to OSHPD projects, please refer to the TOLCO
Seismic Restraint Systems Guidelines.
Finish: Plain. Contact customer service for alternative finishes and materials.
Order By: Figure number, pipe size to be braced, pipe size
used for bracing (1
1
⁄2"
(40mm)
or 2"
Important Note: Fig. 2002 is precision manufactured
to perform its function as a critical component of a complete
bracing assembly. To ensure performance, the UL Listing
requires that the Fig. 2002 must be used only with other
TOLCO bracing products.
and 2"
(50mm)
(65mm)
thru 8"
(50mm)
) and finish.
(200mm)
all
steel schedule 10
Component of State of
California OSHPD Approved
Seismic Restraints System
Hardware
Included
UL Listed Design Load
1”
2015 lbs.
(25.4mm)
Min.
(8.96kN)
Seismic Bracing
Shown with
Fig. 980
Pipe Part Number & Approx. Wt./100 Max. Horizontal
Size
in. (mm) Lbs. (kg) Lbs. (kg) Lbs. (kg)
11/2” (32mm) Brace Pipe 2” (50mm) Brace Pipe Design Load (UL)
21/2” (65) 2002-21/2 X 11/2 224.9 (102.0) 2002-21/2 X 2 283.3 (128.6) 2015 (8.96)
3” (80) 2002-3 X 11/2 241.0 (109.3) 2002-3 X 2 299.4 (135.8) 2015 (8.96)
4” (100) 2002-4 X 11/2 268.4 (121.7) 2002-4 X 2 326.8 (148.2) 2015 (8.96)
6” (150) 2002-6 X 11/2 326.6 (148.1) 2002-6 X 2 385.0 (174.6) 2015 (8.96)
8” (200) 2002-8 X 11/2 381.3 (172.9) 2002-8 X 2 439.7 (199.4) 2015 (8.96)
** See load ratings in UL Listed Design Load chart.
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Pipe Hangers & Supports
194
Eaton