Th e Wheel oc k S er ies P S-6 a nd PS -8 ar e 24VDC, fi ltered and
regulated, supervised remote power supply/battery chargers are
used for supervision and expanded power driving capability of Fire
Alarm Notification Appliance Circuits. The PS-6 provides 6 amps of
power distributed across 4 outputs, while the PS-8 provides 8 Amps
across 4 output. In addition the PS-8 provides additional room in
the chassis for accessories like an Addressable Control Module, with
mounting studs.
The Power Supplies may be connected to any 12V or 24V (FWR or
DC) Fire Alarm Control Panel (FACP) by using a Notication Appliance
Circuit (NAC) or a “Dry Contact”. Primary applications include NAC
expansion (supports ADA requirements) and auxiliary power to
support system accessories. This unit provides ltered and regulated
24VDC, up to four (4) Class “B”, two (2) Class “A”, or two (2) Class
“B” and one (1) Class “A” Notification Appliance Circuits. With the
optional plug-in PS-EXP module the unit supports (8) Class “B” or
(4) Class “A” Notification Appliance Circuits. Additionally, an auxiliary
power output of 2.5 Amps (disconnected upon AC power loss or an
alarm condition) or up to 0.240 A of constant power on the PS-8 and
0.075 A of constant power on the PS-6.
The Wheelock Power Supplies can accommodate 7 or 12 AH batteries
inside its lockable chassis. Using an external battery cabinet it can
charge up to 33 AH batteries (pending UL testing). Two FACP NAC
circuits or two “Dry” contact initiating circuits can be connected to the
inputs. These inputs can then be directed to control supervision and
power delivery to any combination of the four (4) outputs. Each output
is rated at 3.0 Amps (Class “B”) or (Class “A”) and can be programmed
to generate a steady or Code 3 Temporal Horn sound and a strobe
output under alarm condition. Total load for the PS-6 and PS-8 NAC
circuits must not exceed the power supplies rated output.
The Power Suppliesunder non-alarm condition provides independent
supervision for Class “A” and Class “B” FACP NAC circuits. In the
event of circuit trouble, the FACP will be notied via the POWERPATH
steered input (IN1 or IN2). In addition there are two sets of trouble
reporting terminals, one used for AC power loss reporting and the
other for all troubles. The AC power loss reporting, on the common
trouble terminals and on IN1 or IN2, can be delayed for either 30
seconds or 170 minutes. The AC power loss terminals will always
report the trouble within 1 second after loss of AC power.
PS-6
The PS-6 and PS -8 Power Supplies are UL Listed under UL
Standard 864, 9th Edition to be used with any 24 volt Listed
Regulated notification appliances. They include the capability
to synchronize Wheelock strobes and horns and to silence the
horn signal when horn/strobes are operating on two wires.
Approvals
• Approvals Include: UL Standard 864, 1481, California State
Fire Marshal (CSFM), Factory Mutual (FM)
• Compliant with NFPA 72
Inputs
• 120VAC, 50/60Hz, 4.25 Amps (PS-6/8) and 5.32 Amps
• Two (2), 12V or 24V NAC Initiating Circuits (8-33V at 5mA)
FWR or DC
• Two (2) “Dry” Contact initiating Circuits
• Accepts two (2) Class “A” or two (2) Class “B” circuit inputs
• Built in battery charger for sealed lead acid or gel type
batteries
Outputs
• NAC outputs are 24VDC, 3.0 Amps each, power limited
• 8 Amps on PS-8 and 6 Amps on the PS-6 total alarm current
PS-8
...Features continued on next page
• Capable of four (4), Class “B” circuits
• Capable of two (2) Class “A” circuits
• Capable of one (1) Class “A” circuit and two (2) Class “B” circuits
• Capable of (8) Class “B” or four (4) Class “A” circuits with optional PS-EXP module
• Temporal (Code 3), constant voltage output, Wheelock Sync output or True input to output follower mode
• Built-in Wheelock synchronization mode that can be fed to any or all of the output circuits
• Input and output can be synchronized with “IN>OUT SYNC” mode (DSM, 2nd POWERPATH™ or FACP with
synchronization protocol is required)
• Audible silence capability
• Filtered and electronically regulated output
• 2.5 Amp auxiliary power limited output with reset capability. (Removed upon AC loss or alarm. Automatic reset 30 seconds after
AC power returns or the alarm condition is over) or 0.075 Amps (PS-6) or 0.240 Amps (PS-8) of auxiliary power limited output
which remains on during AC loss or an alarm condition when congured for 24 hour battery backup
Supervision
• Compatible with 12V or 24V (FWR or DC) FACP
• Signaling appliance circuits are supervised and steered to either IN1 or IN2
• 10K Ohm, 1 Watt (Wheelock Model #MPEOL) End of Line Resistor (EOLR) for supervision of all outputs
• 37 distinguishable trouble diagnostics
• AC loss trouble reported over a separate set of contacts (delay of 1 second)
• All troubles are reported over the common trouble contacts (AC loss can have a delay of 30 seconds or 170 minutes)
• Automatic switchover to standby battery when AC fails
• Thermal and short circuit protection with auto reset
• Input and output status LED indicators
• AC fail supervision
• Battery presence and low battery supervision
• Ground Fault Detection, with diagnostics to indicate which circuit fault is on
• Latching LED’s for NAC trouble annunciation and Diagnostic trouble LED’s (latching can be disabled)
Power
• Not Battery Dependent
• Automatic switch over to standby batteries when AC fails
• Supports sealed lead acid or gel type batteries
• Fused battery protection
• Thermal and short circuit protection with auto reset
• Supports both 7AH or 12AH batteries in the same cabinet
POWERPATH™ Operating Modes (refer to Installation Manual):
Normal Mode: Provides constant 24 VDC output upon initiation by a voltage to input IN1 or IN2 or by a contact opening
on DRY1 or DRY2. The unit returns to standby mode when the input is deactivated.
Wheelock Sync Mode: Provides signals for synchronization of patented Wheelock audible and strobe notification
appliances. Audibles can also be silenced in this mode while the strobes continue to ash.
In>Out Sync Mode: Accepts a synchronization signal on the input to provide a coded output or synchronized output. This signal
may come from a FACP, another POWERPATH or a Wheelock DSM synchronization module. Caution: Do not use strobes on coded
output circuits.
True Input Follower Mode: Accepts a coded signal on the input to provide a coded output with the same timing as the
input. The signal may come from a FACP, another POWERPATH or other coded source. Caution: Do not use strobes
on coded output circuits.
Temporal Mode: Codes the output voltage in a code-3 temporal pattern to drive audible appliances such as horns,
bells or chimes. Caution: Do not use strobes on coded output circuits.
Specications and Ordering Information
Model Number
PS-61055306 amp, red enclosureXXX
PS-6B1002576 amp, black enclosureXXX
PS-81055318 amp, red enclosureXXX
PS-8B1058308 amp, black enclosureXXX
PS-6EXP1050836 amp power supply with preinstalled expansion moduleXXX
PS-8EXP1050848 amp power supply with preinstalled expansion moduleXXX
PS-EXP1055344 class B or 2 class A expansion moduleXXX
PS-EXP-RETRO105527Field upgrade kit for models prior to January 2010
Input Circuit Input Voltage and Current
Input voltage Range8 to 33 VDC
Input Current @ 12 VDC0.005 amps
Input Current @ 24 VDC0.005 amps
Output CircuitOutput Voltage and Current
Four (4) Class B or
Two (2) Class A or
One (1) Class A and Two (2) Class “B” or
8 Class B or 4 Class A
(optional PS-EXP module necessary)
Continuous duty up to 3 Amps per circuit, up to 4 Amps maximum per panel
Secondary Power Charging Capacity32 Amp hours @ 0.750 Amps per hour
Enclosure can house up to two 12 AH batteries
Aux Output
CP ModePS-6 up to 75 mAPS-8 up to 250 mA
MP Mode2.5A during non alarm
ModelDimensionsWeightComments
PS-6/PS-6B17”H x 13”W x 3.5”D11.5lbs. (Ship) 9.4lbs (Unit)Small prole
PS-8/PS-8B17”H x 15”W x 5.5”D17.7lbs (Ship) 15.6lbs (Unit)Additional room for modules
PS-EXP4.3”H x 3.7”W x 1”D1lb. (Ship & Unit)
Order
Code
Input Voltage/Current
#
24 VDC @ up to 3 amps per curcuit
Plugs into main pcb on all
models
Approvals
ULCSFM FM
XXX
X= Approved
*= Pending
#=Contact Technical
Support for additional
inforamation on upgrade
options
Architects and Engineers Specications
The power supply shall be Wheelock POWERPATH™ Series PS-8, or equivalent. The unit shall be stand alone power supply intended
for powering fire alarm notification appliances via its own Notification Appliance Circuit(s) (NAC). The unit shall be UL 864 Listed for
power limited operation of outputs and comply with NFPA 70 (NEC), article 760.
The power supply shall support a full 8A of notification power even if the battery is in a degraded mode and only AC power is
connected.
The power supply shall be activated by a standard Notication Appliance Circuit (NAC) from any Fire Alarm Control Panel (FACP) or a
“Dry contact” opening. The units shall be 8 ampere, 24 VDC, regulated and filtered, supervised remote power supply/charger. It shall
operate over the voltage range of 8 to 33 VDC or FWR. The primary application of the unit shall be able to expand re alarm system
capabilities for additional NAC circuits to support ADA requirements and to provide auxiliary power to support system accessories
or functions. The power supply shall provide four Class “B”, two Class “A”, or two Class “B” and one Class “A” NAC circuit(s). Eight
Class “B” or Four Class “A” circuits shall be available with an optional PS-EXP module. The PS-8 unit shall supply up to 240 mA of
auxiliary power that is available during both non-alarm and alarm or auxiliary power of not less than 2.5A at 24 VDC during non-alarm.
The power supply shall be capable of charging batteries of up to 33 ampere hours per NFPA 72 at maximum rate of 0.750 Amps per
hour.
Input activation options shall be from not less than two NAC circuits or Dry Contact closures. These inputs shall have the capability of
being directed to any combination of the four NAC circuit outputs. Each NAC circuit output shall be rated at 3 amperes for Class “B”
applications or 3 amperes each for Class “A”. The outputs shall be programmable to generate a steady or Temporal (Code 3) output
and or a synchronized strobe or horn output. The power supply shall provide independent loop supervision for either Class “A” or Class
“B” FACP NAC circuits and shall have the capability to “steer” all alarm or trouble conditions to either incoming NAC circuit. The units
shall have common trouble terminals. The power supply shall be powered from a 120 VAC source with a current consumption of xx
amperes max. The unit shall incorporate short circuit protection with auto reset. The power supply shall incorporate a built in battery
charger for lead acid or gel type batteries with automatic switchover to battery back up in the event of AC power failure. The charger
shall incorporate fused protection for the batteries and have the ability to report low battery and/or no battery condition(s). Standby
current for battery back up shall be 0.129 Amps max. The power supply shall have the ability to latch trouble LED’s so the circuit in
trouble can be identied. The cabinet dimensions shall be 17” H x 15” W x 5.5” D.
The power supply shall be Wheelock POWERPATH™ Series PS-6, or equivalent. The unit shall be stand alone power supply intended
for powering fire alarm notification appliances via its own Notification Appliance Circuit(s) (NAC). The unit shall be UL 864 Listed for
power limited operation of outputs and comply with NFPA 70 (NEC), article 760.
The power supply shall support a full 6A of notification power even if the battery is in a degraded mode and only AC power is
connected.
The power supply shall be activated by a standard Notication Appliance Circuit (NAC) from any Fire Alarm Control Panel (FACP) or a
“Dry contact” opening. The units shall be 6 ampere, 24 VDC, regulated and filtered, supervised remote power supply/charger. It shall
operate over the voltage range of 8 to 33 VDC or FWR. The primary application of the unit shall be able to expand re alarm system
capabilities for additional NAC circuits to support ADA requirements and to provide auxiliary power to support system accessories
or functions. The power supply shall provide four Class “B”, two Class “A”, or two Class “B” and one Class “A” NAC circuit(s). Eight
Class “B” or Four Class “A” circuits shall be available with an optional PS-EXP module. The PS-6 unit shall supply up to 200 mA of
auxiliary power that is available during both non-alarm and alarm or auxiliary power of not less than 2.5A at 24 VDC during non-alarm.
The power supply shall be capable of charging batteries of up to 33 ampere hours per NFPA 72 at a maximum rate of 0.750 Amps
per hour.
Input activation options shall be from not less than two NAC circuits or Dry Contact closures. These inputs shall have the capability of
being directed to any combination of the four NAC circuit outputs. Each NAC circuit output shall be rated at 3 amperes for Class “B”
applications or 3 amperes each for Class “A”. The outputs shall be programmable to generate a steady or Temporal (Code 3) output
and or a synchronized strobe or horn output. The power supply shall provide independent loop supervision for either Class “A” or Class
“B” FACP NAC circuits and shall have the capability to “steer” all alarm or trouble conditions to either incoming NAC circuit. The units
shall have common trouble terminals. The power supply shall be powered from a 120 VAC source with a current consumption of xx
amperes max. The unit shall incorporate short circuit protection with auto reset. The power supply shall incorporate a built in battery
charger for lead acid or gel type batteries with automatic switchover to battery back up in the event of AC power failure. The charger
shall incorporate fused protection for the batteries and have the ability to report low battery and/or no battery condition(s). Standby
current for battery back up shall be 0.130 Amps max. The power supply shall have the ability to latch trouble LED’s so the circuit in
trouble can be identied. The cabinet dimensions shall be 17” H x 13” W x 3.5” D.
WARNING: PLEASE READ THESE SPECIFICATIONS AND INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS
PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR
DEATH TO YOU AND/OR OTHERS.
NOTE: Due to continuous development of our products, specications and oerings are subject to change without notice in accor-
dance with Wheelock Inc. standard terms and conditions.
WE ENCOURAGE AND SUPPORT NICET CERTIFICATION
1 YEAR WARRANTY
S9100 PS-6 & 8 06/11
NJ Location
273 Branchport Ave.
Long Branch, NJ 07740
P: 800-631-2148
F: 732-222-8707
www.coopernotification.com
Cooper Notication is
Notication
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.