Cooper MENVIER MF200, MENVIER MF400, MENVIER MF400-72, MENVIER MF200-72 User Manual

PLEASE PASS THIS BOOKLET TO THE USER,
AFTER INSTALLATION KEEP WITH PANEL.
MENVIER FIRE SYSTEM
MF200/400 MF200-72/400-72
For service Tel: please call:
Service agreement number
123
4
ZONE
POWER FAULT
SYSTEM FAULT
EARTH FAULT
ALARMS
SUPERVISOR MODE
DISABLE MOD E
DISABLE TEST
TEST M OD E
REMOTE SIGNAL DISABLE
POW ER
FI RE
FAULT
FAULT
SUPERVISOR MODE SILENCE/SOUND L AM P TEST/EXIT
SILENCE BUZZERRESET
SELECT
SUPERVISOR
DISABLE
TEST
MF400
Cooper Lighting and Security Ltd.
Wheatley Hall Road, Doncaster, South Yorkshire, DN2 4NB, United Kingdom
Sales General Export
Tel: +44 (0)1302 - 303303 +44 (0)1302 - 321541 +44 (0)1302 - 303250 Fax: +44 (0)1302 - 367155 +44 (0)1302 - 303220 +44 (0)1302 - 303251 E-mail: sales@cooper-ls.com technical@cooper-ls.com export@cooper-ls.com
Lighting and Security
PINST MF4/V
www.cooper-ls.com
SERVICE SUPPORT NUMBER .........................................................................................................1
SYSTEM INFORMATION ...................................................................................................................2
PANEL CONTROLS AND INDICAT ORS ............................................................................................3
PANEL OPERATION ...........................................................................................................................4
GENERAL .................................................................................................................................... 4
NORMAL OPERATION ................................................................................................................4
SUPERVISOR MODE ..................................................................................................................4
PANEL INTERFACE CONNECTIONS AND PANEL CONTROLS ...................................................6
INPUTS ........................................................................................................................................6
OUTPUTS ....................................................................................................................................6
FIRE CONDITION ..............................................................................................................................6
WIRING DIAGRAMS ..........................................................................................................................7
INSTALLATION INSTRUCTIONS ......................................................................................................8
GENERAL .................................................................................................................................... 8
ADDITIONAL NOTES ON INSTALLATION FOR ELECTROMAGNETIC
COMPATIBILITY (EMC) ..............................................................................................................8
INSTALLING THE PANEL ............................................................................................................9
ROUTINE TESTING ...........................................................................................................................9
FAULTS .............................................................................................................................................10
FUSES ........................................................................................................................................10
TECHNICAL SPECIFICATION .........................................................................................................11
FIRE ALARM SYSTEM LOG MASTER SHEET ...............................................................................12
THIS SYSTEM HAS BEEN INSTALLED IN ACCORDANCE WITH THE
REQUIREMENTS OF ..................................................STANDARD
SIGNED ..................................................................... DATE ..............................
FOR...........................................................................................................................
THIS SYSTEM HAS BEEN COMMISSIONED IN ACCORDANCE WITH THE
REQUIREMENTS OF ..................................................STANDARD
SIGNED ..................................................................... DATE ..............................
FOR...........................................................................................................................
PAGE 2
CONTENTS
Zone No. of Call No. of Smoke No. of Heat Location
No Points Detectors Detectors 1 2 3* 4*
TOTAL ALARM LOAD Current No of Sounders, Bells
Electronic
Other
Details of system expansion:
* MF400 only
Audible
Piezo buzzer integral within panel, common to fire and fault.
Keys
The controls of the panel are via a 5 key keyboard on the front of the panel. A key press is acknowledged by a vlip of the internal panel buzzer and in the normal mode the Supervisor Mode LED will flash. Keys labelled 1, 2 and 3 have more than one function these are described below.
KEY Normal Operation Supervisor Mode
Primary function Secondary function Tertiary function
1 Code Entry Toggle for Supervisor Mode Toggle for Supervisor Mode
Disable Mode and Test Mode Disable Mode and Test Mode 2 Code Entry Silence/Re-Sound Alarms Select Function-Disable or Test 3 Code Entry Lamp Test/Exit (Toggle through Functions)
Disable or Test
4 NONE RESET RESET
PAGE 3
PANEL CONTROLS AND INDICATORS
POWER FAULTPOWER FAULT
POWERPOWER
DESIGNED TO EN54 PART 2&4 1997DESIGNED TO EN54 PART 2&4 1997
FIREFIRE
11 22 33
ZONE
FAULTFAULT
FAULT DISABLE/TEST
SYSTEM FAULTSYSTEM FAULT
EARTH FAULTEARTH FAULT
ALARMSALARMS
SUPERVISOR
DISABLE
TEST
SUPERVISOR MODE SILENCE/SOUND LAMP TEST/EXIT
RESET
SELECT
SILENCE BUZZER
SUPERVISOR MODE
SUPERVISOR MODE
DISABLE MODEDISABLE MODE
TEST MODETEST MODE
REMOTE SIGNAL DISABLE
REMOTE SIGNAL DISABLE
...................................... ...................
MF400
11 22 33 44 55
Note Zones 3 & 4
are not provided
on MF200
Visual
General
The panel has 2 levels of operation. Normal Mode and Supervisor Mode.
Normal Operation
Silence Buzzer (key 5) The user can silence the PANEL buzzer by pressing the 'SILENCE BUZZER' key (at any time), the
buzzer will then give a beep approximately every 10 seconds. Note:- This does not silence the alarms only the panel buzzer.
Supervisor Mode Entry (key 1, key 2, key 3) By entering a 4 digit access code the user will enter the Supervisor Mode. The access code is 2113.
By pressing the keys in the correct order the user will see the Supervisor LED flash indicating the panel is in Supervisor Mode.
Supervisor Mode Operation -Enter supervisor mode using access code 2113 prior to carrying out any of the following operations.
Auto time-out of supervisor mode will occur 2 minutes after last action. RESET (key 4) Pressing 'RESET' at any time while in Supervisor Mode will reset the panel, clearing any fire, fault or
Test Mode information. If a fire or fault exists the panel will re-enter the fire condition. Note:- Operating RESET will not clear disable information.
Lamp Test/Exit supervisor Mode (key 3) While the supervisor LED is flashing the user can perform a lamp and buzzer test. All LED's will light
and the buzzer will sound. This also exits the Supervisor Mode. Silence/Sound Alarms (key 2) While the Supervisor LED is flashing pressing 'SOUND/SILENCE' will silence or sound the alarms. If
a fire is detected on another zone the alarms will re-sound. Note:- If the alarms are silenced and fire condition exists the panel buzzer will sound continuously.
Disable Mode (key 1, key 2, key 3) The panel allows the supervisor to disable individual zones, both alarm lines together or the remote
signal output. When any of these functions are disabled the buzzer will beep. Zones, when disabled will not be monitored for fires or faults. Alarms, when disabled will not be monitored for faults, or be activated by a fire condition. Remote signal, when disabled will not be activated by a fire condition.
To disable/re-enable any of the above functions the following procedure should be followed:-
1. Press 'key 1' to toggle the flashing LED from 'Supervisor Mode' to 'Disable Mode'.
PAGE 4
PANEL OPERATION