Cooper Kyle Form 6 Disassembly And Reassembly

Page 1
1
Form 6 Recloser Control Disassembly, Reassembly, and Testing Instructions
Reclosers
Service Information
Safety Information ..................................................... 2
Hazard Statement Definitions ................................ 2
Safety Instructions .................................................. 2
Product Information .................................................. 3
Introduction ............................................................ 3
ANSI Standards ..................................................... 3
Quality Standards ................................................... 3
Acceptance and Initial Inspection .......................... 3
Handling and Storage ............................................ 3
Description ............................................................. 3
Disassembly .............................................................. 4
Disassembly Instructions ....................................... 4
Open the Module ................................................... 5
Remove/Replace CPU Board ................................ 5
Remove/Replace Comms. Accsy. Board Only ....... 6
Remove/Replace I/O Board ................................... 7
Remove/Replace Power Supply or RIF Board ...... 7
Remove/Replace Analog Board ............................. 8
Reassembly ............................................................... 8
Reassembly Instructions ........................................ 8
Place Module in Control ......................................... 8
Before Placing the Control Into Service ................. 9
Installation ................................................................. 9
Initial Programming Prior to Installation ................. 9
Testing ........................................................................10
Testing with Type MET Tester ................................11
Additional Information ..............................................12
Contents
S280-70-11
Printed in USA
1
August 2005 • Supersedes 6/04
Figure 1. Kyle®Form 6 Pole Mount, Yard Mount, and Rack Mount recloser controls.
Page 2
Form 6 Recloser Control Disassembly, Reassembly, and Testing Instructions
2
The instructions in this manual are not intended as a sub­stitute for proper training or adequate experience in the safe operation of the equipment described. Only compe­tent technicians who are familiar with this equipment should install, operate, and service it.
A competent technician has these qualifications:
• Is thoroughly familiar with these instructions.
• Is trained in industry-accepted high- and low-voltage safe operating practices and procedures.
• Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment.
• Is trained in the care and use of protective equipment such as flash clothing, safety glasses, face shield, hard hat, rubber gloves, hotstick, etc.
Following is important safety information. For safe instal­lation and operation of this equipment, be sure to read and understand all cautions and warnings.
Safety Instructions
Following are general caution and warning statements that apply to this equipment. Additional statements, relat­ed to specific tasks and procedures, are located through­out the manual.
SAFETY INFORMATION
SAFETY FOR LIFE
Cooper Power Systems products meet or exceed all applicable industry standards relating to product safety. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Cooper Power Systems employees involved in product design, manufacture, marketing, and service.
We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high voltage lines and equipment and support our “Safety For Life” mission.
This manual may contain four types of hazard statements:
DANGER: Indicates an imminently haz­ardous situation which, if not avoided, will
result in death or serious injury.
WARNING: Indicates a potentially haz­ardous situation which, if not avoided, could
result in death or serious injury.
CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in
minor or moderate injury.
CAUTION: Indicates a potentially hazardous situ­ation which, if not avoided, may result in equip­ment damage only.
Hazard Statement Definitions
WARNING: This equipment is not intended to
protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply can result in death, severe personal injury and equipment dam­age. G102.1
DANGER: Hazardous voltage. Contact with
hazardous voltage will cause death or severe personal injury. Follow all locally approved safety pro­cedures when working around high- and low-voltage lines and equipment.
G103.3
WARNING: Before installing, operating, main-
taining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage.
G101.0
WARNING: Power distribution equipment must
be properly selected for the intended application. It must be installed and serviced by competent person­nel who have been trained and understand proper safe­ty procedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Failure to proper­ly select, install, or maintain power distribution equip­ment can result in death, severe personal injury, and equipment damage. G122.2
!
SAFETY
FOR LIFE
!
SAFETY
FOR LIFE
!
!
!
!
!
!
!
Page 3
Introduction
Service Information S280-70-11 provides disassembly, reassembly, and testing instructions for the Kyle
®
Form 6
recloser control.
Read This Manual First
Read and understand the contents of this manual and fol­low all locally approved procedures and safety practices before installing or operating this equipment.
Additional Information
These instructions cannot cover all details or variations in the equipment, procedures, or process described, nor provide directions for meeting every possible contin­gency during installation, operation, or maintenance. For additional information, contact your Cooper Power Systems sales representative.
ANSI Standards
Kyle reclosers are designed and tested in accordance with the following ANSI standards: C37.60 and C37.85 and ANSI Guide C37.61.
Quality Standards
ISO 9001:2000-certified quality management system
Acceptance and Initial Inspection
Each unit is in good condition at the factory and when accepted by the carrier for shipment.
Upon receipt, inspect the carton for signs of damage. Unpack the unit(s) and inspect it thoroughly for damage incurred during shipment. If damage is discovered, file a claim with the carrier immediately.
Handling and Storage
Be careful during handling and storage of the unit to min­imize the possibility of damage. If the unit is to be stored for any length of time prior to installation, provide a clean, dry storage area.
Description
Service Information S280-70-11 provides disassembly, reassembly, and testing instructions for the Form 6 Rack Mount, Yard Mount, Pole Mount, and Triple-Single Pole Mount recloser controls.
For additional information on installing the control, removing the control from service, and control testing procedures, refer to the appropriate instructions:
Service Information S280-70-1 Form 6 Rack Mount
Recloser Control Installation and Operation Instructions
• Service Information S280-70-2 Form 6 Yard Mount Recloser Control Installation and Operation Instructions
• Service Information S280-70-3 Form 6 Pole Mount Recloser Control installation and Operation Instructions
• Service Information S280-70-7 Form 6 Triple-Single Pole Mount Recloser Control Installation and Operation Instructions
S280-70-11
3
!
PRODUCT INFORMATION
SAFETY
FOR LIFE
Page 4
Form 6 Recloser Control Disassembly Instructions
These instructions describe the disassembly of the Form 6 recloser control.
1. Remove the Form 6 Control from Service. Refer to appropriate Service Information Instructions:
Service Information S280-70-1 Form 6 Rack Mount
Control Installation and Operation Instructions
Remove the Control from Service section
Service Information S280-70-2 Form 6 Yard Mount
Control Installation and Operation Instructions
Remove the Control from Service section
Service Information S280-70-3 Form 6 Pole Mount
Control Installation and Operation Instructions
Remove the Control from Service section
Service Information S280-70-7 Form 6 Triple
Single Pole Mount Control Installation and Operation Instructions Remove the Control from
Service section
2. Carefully transport the recloser control to a suitable
service facility.
Note: The entire disassembly, reassembly, and testing
process should be conducted in a clean environ­ment, such as a repair shop.
This step applies to Form 6 Pole and Yard mount controls.
3. Remove module from cabinet as applicable.
A. For complete scheme structure and verification
refer to appropriate instructions:
Service Information S280-70-4 Form 6 Control Schemes section
Service Information S280-70-9 Form 6-TS
Control Schemes section
B. Disconnect SCADA communications to the Form 6
control.
C. Remove all applicable connecting wires from
module.
D. Remove the 7/16 inch grounding nut and lock-
washers located on the bottom of the control mod­ule (Figure 2).
E. Remove the four mounting nuts that secure the
front of the module to the cabinet (Figure 3).
Form 6 Recloser Control Disassembly, Reassembly, and Testing Instructions
4
DISASSEMBLY
CAUTION: Recloser misoperation. The control must
be removed from service prior to performing any main­tenance, testing, or programming changes. Failure to comply can result in misoperation (unintentional oper­ation) of the recloser. T216.2
IMPORTANT: Isolate all power connections to the Form 6 recloser control, i.e., AC voltage sensing and SCADA, before removing control from service.
IMPORTANT: Make sure the power is turned off and the battery is disconnected.
CAUTION: Equipment damage. Always wear a grounding wrist strap to control static electricity before handling circuit boards. Failure to use this strap may result in circuit board damage.
T253.1
Figure 2. Location of grounding nut and lockwashers on the rear panel of the Form 6 pole mount control (below SN 10000).
CAUTION: Recloser misoperation. Before
downloading configuration files or settings to the equipment, verify that the files and settings are correct for the location and application. Downloading configu­ration files or settings designed for a different location or application can result in severe personal injury and equipment damage. G133.0
Figure 3. Location of the four mounting nuts on the front of the Form 6 pole mount control.
Hex Nuts
CO4
CI1
CI2 CI3 SS1 CO1
123 5 7 9 11 13 15 17 19
TB1
4681012141618
CI1 CI2 CI3 SS1 CO1 CO2 CO3 CO4
CI4
CI5 CI6 CI7 CI8 CI9 CI10 CI11 CO5 CO6
135 7 91113151719 21
TB3
2
4681012141618
CI4 CI5 CI6 CI7 CI8 CI9 CI10 CI11 CO5
•12•34•56•78•
TB2
I(1-2)
I(3-4) I(5-6) V(1-2)
CO2 CO3
20
CO6
TB5
432
9
10
1
7
5
8
6
910•11 12•13 14•15 16•17 18
I(SEF)
J1 RS232
RS232 DTE
CO7 CO8
135791113
2
CO7 CO8 CO9 CO10 CO11CO12
RECLOSER INTERFACE CONNECTIONS
A 1
2B4C6
V(3-4) V(5-6) V1
J2 IRIG-B
J3 RS485
TTL IRIG-B
2-Wire RS485
CO9 CO10 CO11
4681012
D
F
3
TB6
57
E
19
CO12
TB4
• 20
Grounding Nut and Lockwashers
!
Page 5
Open the Module
1. Discharge internal capacitors using a 10 ohm (5 watt) load across TB6-1 and TB6-7 for five seconds.
2. Use a flat-head screwdriver to unscrew the six front panel screws.
3. Pull the right side of the panel outward toward the left.
Note: Various wire connections will keep the front panel
attached to the control module. This will allow the display panel to be placed next to the control mod­ule while work on internal circuit boards takes place (Figure 4).
4. Disconnect the ribbon wire assembly from the prima­ry connector board by lifting the locking tabs on either side and pulling out the connector.
5. Use a flat-head screwdriver to loosen the five captive screws on the primary connector board.
6. Holding the middle two screws on the primary con­nector board, firmly pull the primary connector board outward working left to right so as not to bend pins.
Removal/Replacement of CPU Board
1. Remove CPU board. Refer to Form 6 Recloser Control Disassembly Instructions section.
2. Remove the TB1 terminal block strip from the back of
the module (Figure 2).
3. Carefully pull CPU board outward so as not to dam­age the capacitor or any of the electrical components on the Bezel tabs (Figure 6).
4. Proceed as appropriate for kit contents:
If mounting plate is included with the kit proceed to
step 5.
If mounting plate is not included with the kit contin­ue with this step.
A. Unscrew the five captive screws on top of the
CPU board to release it from the mounting plate.
B. Flip the mounting plate over and remove the two
mounting screws from the bottom of the mount­ing plate.
C. Lift the CPU from the mounting plate.
D. Install new CPU onto mounting plate and
replace the five captive screws.
E. Flip mounting plate over and replace the mount-
ing screws on the bottom of the mounting plate.
5. If a new back plate is included with the kit, unscrew the six back plate screws using a Phillips-head screwdriver and replace the back plate (Figure 5).
6. Slide mounting plate into card guide and carefully line up terminal strip to opening on the back plate.
7. Replace all of the terminal block strips.
8. Attach the new back plate over the communications
port on the back panel using two screws and washers provided with kit.
9. Configure communications board with applicable switches and program as necessary.
S280-70-11
5
!
Figure 4. Form 6 control internal ribbon wire.
Internal ribbon wire
Primary Connector Board
CAUTION: Equipment damage. Always wear a grounding wrist strap to control static electricity before handling circuit boards. Failure to use this strap may result in circuit board damage. T253.1
Figure 5. Form 6 control back plate.
CAUTION: Equipment misoperation. Do not
connect this control to an energized recloser until all control settings have been properly programmed and verified. Refer to the programming information for this control. Failure to comply can result in control and recloser misoperation, equipment damage, and per­sonal injury. G110.3
SAFETY
FOR LIFE
!
Communications
Back Panel
CO2 CO3
CI1
CI2 CI3 SS1 CO1
123 5 7 9 11 13 15 17 19
TB1
4681012141618
CI1 CI2 CI3 SS1 CO1 CO2 CO3 CO4
CI5 CI6 CI7 CI8 CI9 CI10 CI11 CO5 CO6
CI4
13579111315171921
TB3
2
4681012141618
CI4 CI5 CI6 CI7 CI8 CI9 CI10 CI11 CO5
TB5
9
10
8
•12•34•56•78•
TB2
I(1-2)
I(3-4) I(5-6) V(1-2)
CO4
RS-232 DTE
20
CO6
432
1
7
5
6
910•11 12•13 14•15 16•17 18
I(SEF)
V(3-4) V(5-6) V1
J1-RS-232
CO7 CO8
CO9 CO10 CO11
135791113
2
4681012
CO7 CO8 CO9 CO10 CO11CO12
RECLOSER INTERFACE CONNECTIONS
A
D
F
1
3
7
5
2B4C6
E
IRIG-B
CO12
TB4
TB6
20
19
Page 6
Removal/Replacement of Communications Accessory Board Only
The Form 6 control is equipped with a Communication Board Accessory (expansion bay) offering versatile sup­port for modern communication media. Seven distinct communication options are available, providing two-way, real time digital communications with a remote terminal unit (RTU), wireless, telephone modem, Ethernet net­work, or other communication devices. The following options are available:
No auxiliary communication card installed (standard)
RS485 (isolated) Serial Communication Card (KME6-
3839-1S)
Fiber-optic-based Serial Communication Card (ST) (KME6-3839-2S)
10/100 Base-T dual Ethernet Communication Card (2*RJ-45) (KME6-3839-5S)
100 Base-FX dual Ethernet Communication Card (2*MT-RJ) (KME6-3839-3S)
10/100 Base-T, 100 Base-FX Ethernet Communication Card (RJ-45 + MT-RJ) Multi-mode (KME6-3839-4S)
100 Base FX dual Ethernet Communication Card (2 SC) Single-Mode (KME6-3839-6S)
Additional accessories are being continuously devel­oped. Contact your Cooper Power Systems representa­tive for the latest information regarding particular media and communication protocol support.
Note: Form 6 Rack Mount Controls with serial numbers below
20,000 and Form 6 Pole and Yard Mount Controls with serial numbers below 10,000 will need an additional CPU replacement kit to upgrade a communications board. Refer to KME6-3837-3S (pole mount) or KME6­3837-4S (rack/yard mount).
This procedure will be used when changing communica­tions accessory board:
1. Remove the CPU circuit board. Refer to Form 6 Removal/Replacement of CPU Board section.
2. Remove the TB1 terminal block strip from the back of
the module (Figure 2).
3. Carefully pull the CPU board outward so as not to damage the capacitor or any of the electrical compo­nents on the Bezel tabs (Figure 6).
4. Install two standoffs with copper washers into the holes on the left side of the CPU board (Figure 7).
5. Carefully install the communication board onto the CPU board so as to not bend any connections.
6. Install two screws with lock washers onto the com­munications board.
Note: Use 10 in-lbs. of torque. Do not overtighten
standoffs.
Form 6 Recloser Control Disassembly, Reassembly, and Testing Instructions
6
Figure 6. Internal view of the Form 6 pole mount recloser control module.
CPU and Communications Board
Input/Output Board
Power Supply and RIF Board
Analog Board
Capacitor
Bezel Tabs
Shield Tabs
Page 7
7. Slide mounting plate into card guide and carefully push the assembly into the module.
8. Replace the TB1 terminal block strip.
9. Attach fiber/wire cover plate over the communications
port on the back panel using two screws and washers.
10. Configure communications board with applicable switches, and program as necessary.
Removal/Replacement of I/O Board
1. Remove the I/O circuit board. Refer to Form 6 Recloser Control Disassembly Instructions section.
2. Remove the TB3 and TB4 terminal block strips or
cover plate from the back of the control module (Figure 2).
3. Carefully pull I/O board outward so as not to damage any of the electrical components.
4. Unscrew the five screws on top of the I/O board using a Phillips-head screwdriver to release it from the mounting plate.
5. Lift I/O board from shield.
6. Install new I/O board onto mounting plate and replace
the five screws.
7. Slide mounting plate into card guide and carefully line up terminal strip to opening on the back plate.
8. Replace the TB3 and TB4 terminal block strips.
Removal/Replacement of Power Supply or Recloser Interface Board (RIF)
Note: The Form 6 pole mount control will not contain an inter-
nal power supply board.
1. Remove the power supply or RIF circuit board. Refer to Form 6 Recloser Control Disassembly
Instructions section.
2. Remove the TB5 and TB6 terminal block strips from
back of the control module (Figure 2).
3. Carefully pull power supply and RIF board mounting plate outward (Figure 4). Disconnect wire assembly from the display assembly.
4. Unscrew the four screws on top of the power supply or RIF board using a Phillips-head screwdriver.
5. Lift power supply board off of mounting plate and carefully separate the board to board connector between the RIF and the power supply board.
6. Install new power supply board onto mounting plate and replace the four screws.
7. Slide mounting plate into card guide and carefully line up terminal block strip to opening on the back plate.
8. Replace the TB5 and TB6 terminal block strips.
S280-70-11
7
!
CAUTION: Equipment misoperation. Do not
connect this control to an energized recloser until all control settings have been properly programmed and verified. Refer to the programming information for this control. Failure to comply can result in control and recloser misoperation, equipment damage, and per­sonal injury. G110.3
Figure 7. Location of standoffs on CPU board.
IMPORTANT: Do not damage the capacitor or any other electrical components on the Bezel tabs (Figure 6).
Standoff
Standoff
SAFETY
FOR LIFE
!
Page 8
Removal/Replacement of Analog Board
1. Remove the analog circuit board. Refer to Form 6 Recloser Control Disassembly Instructions section.
2. Remove the bottom two screws on the outside of the
right panel, left panel, and back plate of the module.
3. Remove the two screws on the bottom panel located under the TB2 terminal block strip (Figure 6).
4. If applicable disconnect each wire connector from the TB2 terminal block strip.
5. Remove bottom panel carefully so as not to remove grounding strip.
6. Unscrew the five screws on top of the analog board using a Phillips-head screwdriver.
7. Install new analog board onto mounting plate and replace the five screws.
8. Reconnect each of the wire connectors to the TB2 terminal block strip (Table 1).
9. Slide mounting plate into card guide and replace each of the two screws on the right panel, left panel, back panel, and bottom of the control housing.
REASSEMBLY
Form 6 Recloser Control Reassembly Instructions
These instructions describe the reassembly of the Form 6 recloser control.
1. Ensure that the board that was serviced or replaced is seated firmly and has been aligned properly.
Note: All connections must be made carefully to ensure
proper alignment.
2. Carefully seat the primary connector board at each of the five captive screws sites using gentle pressure so as not to bend any connection pins.
3. Using a flat-head screwdriver tighten the five captive screws.
4. Carefully attach ribbon cable to the ribbon wire con­nector and secure locking tabs.
5. Replace the front panel.
6. Carefully thread each of the six front panel screws
into place.
Note: Use 5-7 in-lbs. of torque. Do not cross thread or
overtighten.
7. Tighten each screw in an alternating manner.
8. Check all fasteners for tightness and assure that all
connections are properly made before applying power.
Place Module in Control
For Yard and Pole mount modules, rewire TB2 terminal block strip per Table 1.
1. Place the module into the control,
2. Secure the module with the four mounting screws.
3. Replace the 7/16 inch nut (with appropriate lock-
washers) located below the TB2 terminal block strip.
4. Connect all wires.
5. Place the control in service. Refer to the Before Placing the Recloser Control into Service section.
6. Apply local procedures to enable an electronic reclos-
er control.
7. Reconnect SCADA communications to the Form 6.
Form 6 Recloser Control Disassembly, Reassembly, and Testing Instructions
8
CAUTION: Equipment damage. Use care to properly align and seat connection pins to the terminal block strips. Failure to comply can result in equipment dam­age and protective device misoperation. T317.0
TB2 Wire Color
1 White/BlacK
2* Black*
3 Red/Black
4* Black*
5 Green/Black
6* Black*
7* Black*
8 Orange/Black
9 White/Red RW
10 White/Brown RW
11 Black RW
12 White RW
13 Gray RW
14 Violet RW
15 Blue RW
16 Green RW
17 Yellow RW
18 Orange RW
19 Red RW
20 Brown RW
TABLE 1 Form 6 Yard and Pole Mount (below S/N 10000) Control TB2 Wiring Connections
* = Wire connected together RW = Ribbon wire
Page 9
Before Placing the Recloser Control into Service
Prior to placing the Form 6 recloser control into service, installation procedures must be properly completed and verified.
For information on placing the control into service refer to the appropriate instructions:
Service Information S280-70-1 Form 6 Rack Mount Control Installation and Operation Instructions
• Service Information S280-70-2 Form 6 Yard Mount Control Installation and Operation Instructions
• Service Information S280-70-3 Form 6 Pole Mount Control installation and Operation Instructions
• Service Information S280-70-7 Form 6 Triple-Single Pole Mount Control Installation and Operation Instructions
INSTALLATION
Initial Programming Prior to Installation
The control must be programmed with all necessary operating settings, all alternate profiles, and parameters prior to operation with an energized recloser.
Note: Initial programming of the control is the responsibility of
a qualified technician or engineer familiar with control functions and programming parameters required for the specific recloser installation.
The control must be programmed with the Form 6 ProView interface software. Refer to the appropriate con­trol programming guide for information:
• S280-70-4 Form 6 Control Programming Guide
• S280-70-9 Form 6 Triple-Single Pole Mount Control Programming Guide
S280-70-11
9
!
CAUTION: Equipment misoperation. Do not
connect this control to an energized recloser until all control settings have been properly programmed and verified. Refer to the programming information for this control. Failure to comply can result in control and recloser misoperation, equipment damage, and per­sonal injury. G110.3
CAUTION: Equipment misoperation. Do not
connect this control to an energized recloser until all control settings have been properly programmed and verified. Refer to the programming information for this control. Failure to comply can result in control and recloser misoperation, equipment damage, and per­sonal injury.
G110.3
IMPORTANT: Program all protection profiles. Unused alternate profiles should be programmed with the same settings as one of the applicable profiles. Default settings on unused alternate profiles can cause unnecessary outages if they are below normal system requirements.
CAUTION: Equipment misoperation. Check mini­mum trip values prior to changing an alternate profile. Failure to do so may cause misoperation of the control under load conditions. T280.0
SAFETY
FOR LIFE
!
!
Page 10
Form 6 Recloser Control Testing Instructions
These instructions describe the testing of the Form 6 recloser control.
Communication Ports
Verify that the communication settings have been appropri­ately configured for your selected communication protocol.
For information on configuring communications refer to the appropriate instructions:
• S280-70-4 Form 6 Control Programming Guide
• S280-70-9 Form 6 Triple-Single Control Programming Guide
Contact Input/Outputs
Standard Default Supervisory Input Control and Output Status Contacts
Test inputs/outputs by asserting appropriate alarms per the ProViewsoftware to verify that all contact outputs operate (open and close). Figures 8 and 9 show the loca­tion of the controls module manufacturing numbers. Refer to Tables 2 and 3 for Operating Voltage Requirements for Standard and Optional Supervisory Inputs.
For information on testing refer to the appropriate instructions:
• Service Information S280-70-1 Form 6 Rack Mount Control Installation and Operation Instructions
• Service Information S280-70-2 Form 6 Yard Mount Control Installation and Operation Instructions
• Service Information S280-70-3 Form 6 Pole Mount Control Installation and Operation Instructions
• Service Information S280-70-7 Form 6 Triple-Single Pole Mount Control Installation and Operation Instructions
Form 6 Recloser Control Disassembly, Reassembly, and Testing Instructions
10
TESTING
CAUTION: Equipment damage; misoperation.
External leads must be shielded and the shield must be grounded at both ends. Terminate each lead with a 320 Vac, 160 Joules metal oxide resistor (MOV), or equiva­lent, at the remote end. Attach MOVs between the leads and ground. Failure to properly shield and protect leads can result in equipment damage and/or uninten­tional operation. G117.3
Figure 8. Module Mfg. No. location on back of Form 6 pole mount control.
Minimum Module Nominal Operating Mfg. No.* Input Voltage Current Time
6A00160101 12 Vdc – 48 Vdc 5 mA 5 milliseconds
through
6A00160104
6A00160105 48 Vdc – 125 Vdc, 5 mA 5 milliseconds
through 120 Vac
6A00160108
6A00160161 12 Vdc – 250 Vdc, 5 mA 5 milliseconds
6A00160160 120 Vac-240 Vac (Triple-Single)
TABLE 2 Operating Voltage Requirements for Standard and Optional Supervisory Inputs for Form 6 Pole Mount Recloser Control
Refer to Figure 6 for location of Module Mfg. No.
CO2 CO3
*Location of
Module Mfg. No.
Refer to Table 2
CI1
123 5 7 9 11 13 15 17 19
TB1
CI1 CI2 CI3 SS1 CO1 CO2 CO3 CO4
CI4
CI5 CI6 CI7 CI8 CI9 CI10 CI11 CO5 CO6
135 7 91113151719 21
TB3
2 CI4 CI5 CI6 CI7 CI8 CI9 CI10 CI11CO5
Mfg. No. 6A0016010XX
•12•34•56•78•
TB2
I(1-2)
CI2 CI3 SS1 CO1
4681012141618
4681012141618
TB5
432
9
7
10
5
6
8
910•11 12•13 14•15 16•17 18
I(SEF)
I(3-4) I(5-6) V(1-2)
CO4
20
CO6
1
V(3-4) V(5-6) V1
J2 IRIG-B
J1 RS232
TTL IRIG-B
RS232 DTE
CO7 CO8
CO9 CO10 CO11
135791113
2
4681012
CO7 CO8 CO9CO10 CO11CO12
RECLOSER INTERFACE CONNECTIONS
A
D
F
1
3
TB6
7
5
2B4C6
E
J3 RS485
2-Wire RS485
CO12
TB4
20
19
43
2
1
109
1211
8
7
43
2
65
1
Power Connections
Page 11
Testing with Type MET Tester
Use the Kyle®Type MET electronic recloser control tester (Figure 10) to test the following functions of the Form 6 recloser control:
Overcurrent Timing
Reclose Time
Operating Sequence
Reset Time
The MET Tester is completely self-contained, capable of performing all required checks and tests to verify over­current protection parameters.
Refer to Service Information S280-76-1 Type MET
Electronic Recloser Control Tester Operating Instructions
for proper setup and use of the MET Tester.
Additional Testing Required
Apply and verify source side voltage levels per your local standard utility procedures.
S280-70-11
11
!
Figure 9. Module Mfg. No. location on back of Form 6 rack and yard mount control.
Module Input Nominal Minimum Mfg. No.* Voltage Current Operating Time
6A00160121 12 Vdc – 48 Vdc 5 mA 5 milliseconds through 6A00160128 6A00160129 48 Vdc – 125 Vdc, 5 mA 5 milliseconds through 120 Vac 6A00160136 6A00160170 12 Vdc – 250 Vdc 5 mA 5 milliseconds
120 Vac – 240 Vac
TABLE 3 Operating Voltage Requirements for Standard and Optional Supervisory Inputs for Form 6 Rack and Yard Mount Recloser Controls
*Refer to Figure 7 for location of Module Mfg. No.
Figure 10. Kyle®Type MET electronic recloser control tester.
010028KM
SAFETY
FOR LIFE
CO4
INPUT POWER AUXILIARY POWER
FUSE
TB5
+ 1
CO2 CO3
CO6
­5
J1 RS232
RS232 DTE
CO7 CO8
20
RECLOSER INTERFACE CONNECTIONS
J2 IRIG-B
J3 RS485
TTL IRIG-B
2-Wire RS485
CO9 CO10 CO11
1357 9 11 13
2
4681012
CO7 CO8 CO9 CO10 CO11CO12
A
D
F
1
3
TB6
57
CO12
*Location of
Module Mfg. No.
Refer to Table 3
CI1
CI2 CI3 SS1 CO1
123 5 7 9 11 13 15 17 19
TB1
4681012141618
CI1 CI2 CI3 SS1 CO1 CO2 CO3 CO4
CI4
CI5 CI6 CI7 CI8 CI9 CI10 CI11 CO5 CO6
135 7 9 1113151719 21
TB3
2
4681012141618
CI4 CI5 CI6 CI7 CI8 CI9 CI10 CI11 CO5
Mfg. No. 6A0016010XX
FUSE
TB4
(10 AMP)
(10 AMP)
•12•34•56•78•
TB2
I(1-2)
I(3-4) I(5-6) V(1-2)
28 VDC
2
4
-
+
910•11 12•13 14•15 16•17 18
I(SEF)
2B4C6
V(3-4) V(5-6) V1
E
19
20
Page 12
Replacement Kits
Replacement kits for the Kyle Form 6 recloser controls are available through the factory Service Department. To order these kits, refer to the Replacement Parts price list S260-01 through S280-01 for catalog numbers and pric­ing. Contact your Cooper Power Systems representative for additional information and order procedures.
Factory-Authorized Service Centers
Factory-authorized service centers are located through­out the continental United States to provide mainte­nance, repair and testing services for Kyle controls and reclosers. For further information, contact your Cooper Power Systems representative.
Factory Testing and Troubleshooting Classes
The factory service department offers a basic testing and troubleshooting course for the Form 6 microprocessor­based recloser control. This course, taught by experi­enced service technicians, is held at the factorys in­house training facility. For additional information, contact your Cooper Power Systems representative.
Type MET Recloser Control Tester
A 30-minute video cassette program KSPV7 Kyle®Type MET Electronic Recloser Control Tester Operation and Testing Procedures is available as a supplemental train-
ing aid for service personnel.
Form 6 Recloser Control Disassembly, Reassembly, and Testing Instructions
12
ADDITIONAL INFORMATION
CAUTION: This equipment requires routine
inspection and maintenance to ensure proper operation. If it is not maintained, it can fail to operate properly. Improper operation can cause equipment damage and possible personal injury. G105.1
!
©2005 Cooper Power Systems or its affiliates. Kyle®is a registered trademark of Cooper Power Systems or its affiliates. ProViewTMis a trademark of Cooper Power Systems or its affiliates.
KA2048-637 Rev: 01
KDL
8/05
1045 Hickory Street Pewaukee, WI 53072 www.cooperpower.com
!
SAFETY
FOR LIFE
Loading...