Cooper HS4-241575, HS4-24MCWH, HS4-24MCW Service Manual

THE CITY OF NEW YORK
DEPARTMENT OF BUILDINGS
U
L
®
Series HS Horn and Horn Strobe Appliances
SERIES HS4
Description Features
The Series HS4 Horn Strobe and HS Horn Appliances are an ideal choice for retrofit applications as well as new installations. They satisfy virtually all requirements for indoor, wall mount applications.
The Series HS Horn and the horn portion of the Series HS4 include a selectable continuous horn tone or temporal pattern (Code 3) with three selectable dBA settings for each tone.
Strobe options include 1575cd or the Wheelock patented MCW Multi-Candela strobe with field selectable candela settings of 15/30/75/110cd or the high intensity MCWH strobe with field selectable 135/185cd.
The Series HS4 horn and strobe inputs are electrically isolated to allow for independent operation of the strobe circuit and the horn circuit. The horn and strobe may also be wired in parallel to operate on a single circuit.
These versatile Horn and Horn Strobe Appliances may be synchronized using Wheelock SM, DSM Sync Modules or the PS-24-8MC Power Supplies with Wheelock patented Sync Protocol.
All models are designed for maximum performance, reliability and cost-effectiveness while meeting or exceeding the latest requirements of NFPA 72/ANSI
117.1/UFC and UL Standards 1971 and 464 as well as meeting ADA requirements concerning photosensitive epilepsy.
Approvals include: UL Standard 1971, UL Standard 464, New York City (MEA), California State Fire Marshal (CSFM) and Factory Mutual (FM) and Chicago (BFP) See approvals by model in Specifications and Ordering Information
ADA/NFPA/UFC/ANSI compliant
Complies with OSHA 29, Part 1910.165
Field Selectable Candela Settings: 15/30/75/110cd or 135/185cd (Multi-Candela models) or 1575cd (single candela model)
Selectable Continuous Horn or Temporal (Code 3)
3 Selectable dBA settings of 90/95/99 dBA in both tones
4-Wire Horn Strobe Appliance allows for separate operation of the horn and strobe circuits
24 VDC models with 16 to 33 VDC UL “Regulated Voltage” using filtered DC or unfiltered VRMS input voltage
Wall mount flush to standard 4-inch square or
double-gang boxes or surface mount to IOB backbox
Synchronize with Wheelock Sync Modules or Power Supplies with built-in sync protocol
Fast installation with IN/OUT screw terminals using #12 to #18 AWG wires
SERIES HS
S5391
151-92-E
7125-0785:161
NOTE: All CAUTIONS and WARNINGS are identified by the symbol . All warnings are printed in bold capital letters.
WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR
APPLYING THIS PRODUCT. VISIT WWW.COOPERWHEELOCK.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
General Notes:
Strobes are designed to flash at 1 flash per second minimum over their “Regulated Voltage Range”. Note that NFPA-72 specifies a flash rate of 1
to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second.
All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971.
Series NS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32°F to 120°F (0°C to 49°C) and maximum humidity of 93% (± 2%).
Series NH horns are listed under UL Standard 464 for audible signal appliances (Indoor use only).
“Regulated Voltage Range” is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the
terminology “Listed Voltage Range”.
Table 1: Ratings Per UL Standard 1971
Model
Number
Input
Voltage
VDC
Regulated
Voltage Range
VDC/FWR
Strobe
Candela (CD)
HS4-24MCW 24 16.0 - 33.0 15/30/75/110
HS4-241575W 24 16.0 - 33.0 15 (75 on Axis)
HS4-24MCWH 24 16.0 - 33.0 135/185
HS-24 24 16.0 - 33.0 -
Table 2: dBA Ratings for Horn
Description Volume
Reverberant dBA
@ 10ft per UL 464
Anechoic dBA
@ 10 ft
24VDC 24VDC
High 91 99
Continuous
Horn
Med 88 95
Low 83 90
High 87 99
Code 3
Horn
Med 84 95
Low 79 90
Table 3: Average RMS Current*
Audible Current Strobe Current
HS/HS4
Series
HS and HS4 HS4-241575W HS4-24MCW HS4-24MCWH
High (99) dBA Med (95) dBA Low (90) dBA 1575cd 15cd 30cd 75cd 110cd 135cd 185cd
24 vdc 0.098 0.052 0.024 0.060 0.041 0.063 0.109 0.140 0.195 0.270
UL max* 0.110 0.068 0.027 0.090 0.060 0.092 0.165 0.220 0.300 0.420
* RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16-33v for 24v units). For strobes the UL max current is usually at the minimum listed voltage (16v for 24v units). For audibles the max current is usually at the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, see installation instructions.
Loading...