Cooper HS-24 INSTALLATION INSTRUCTIONS

273 Branchport Avenue Long Branch, NJ 07740 Thank you for using our products. (800) 631-2148 www.wheelockinc.com INSTALLATION INSTRUCTIONS

HS-24 APPLIANCE

Use this product according to this instruction manual. Please keep this instruction manual for future reference.
The HS-24 Appliance can be field set to provide either Continuous Horn or Code 3 Horn. It can provide a continuous horn tone when connected directly to the Fire Alarm Control Panel (FACP), or synchronized Code 3 Horn when used in conjunction with the Sync Module (SM), Dual Sync Module (DSM) or Wheelock’s Power Supplies. Audible Horn Appliance can be field set to provide either High (HI) dBA, Medium (MED) dBA or Low (LO) dBA sound output and can be used on coded systems in which the applied voltage is cycled on and off. The HS-24 Appliance is UL Listed under Standard 464 for Audible Signal Appliances and also ULC Listed under Standard CAN/ULC-S525-99 for Audible Signaling Appliances for Fire Alarm Systems. It is listed for
indoor use only and can be mounted to double-gang, 4” backbox, 100mm European backbox or SHBB surface
backbox (See Mounting Options).
The HS-24 is designed for use with either filtered DC or unfiltered Full-Wave-Rectified (FWR) input voltage. All inputs are polarized for compatibility with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP).
NOTE: All CAUTIONS and WARNINGS are identified by the symbol
. All warnings are printed in bold capital letters.
WARNING: PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, CANDELA SETTING, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
WARNING: THE HS-24 APPLIANCE IS A “FIRE ALARM DEVICE – DO NOT PAINT.” SPECIFICATIONS:

Table 1: UL Listed Models and Ratings

Regulated
Model
Voltage
(VDC/VRMS)
HS-24 24
Voltage Range Limit
Per UL 464
DC 16-33VDC 0.027 0.068 0.110 FWR 16-33VRMS 0.041 0.050 0.094
Maximum RMS Current (AMPS)
Lo Med Hi

Table 1A: ULC Current Ratings (AMPS)

Model
ULC
Voltage
MEAN RMS MEAN RMS MEAN RMS
Lo Med Hi
20.0VDC 0.014 0.018 0.020 0.033 0.035 0.067
24.0VDC 0.017 0.024 0.026 0.052 0.055 0.098
HS-24
31.0VDC 0.021 0.027 0.035 0.068 0.069 0.110
20.0VRMS ------ 0.016 ------ 0.028 ------ 0.052
24.0VRMS ------ 0.031 ------ 0.043 ------ 0.075
31.0VRMS ------ 0.041 ------ 0.050 ------ 0.094
Copyright 2006 Cooper Wheelock, Inc. All rights reserved.
P84432 H
Sheet 1 of 6

Table 2: dBA Sound Output for 24VDC Models

Description Volume Reverberant Per UL 464 Anechoic dBA @ 10 Feet
16.0VDC 24VDC 33.0VDC 20.0VDC 24VDC 31.0VDC
Continuous
Horn
Low 80 83 86 86 90 92 Medium 85 88 91 91 95 98 High 88 91 93 95 99 101
Low 75 79 82 86 90 92
Code 3 Horn Medium 80 84 86 91 95 98
High 84 87 89 95 99 101
WARNING: CHECK THE MINIMUM AND MAXIMUM OUTPUT OF THE POWER SUPPLY AND STANDBY BATTERY AND SUBTRACT THE VOLTAGE DROP FROM THE CIRCUIT WIRING RESISTANCE TO DETERMINE THE APPPLIED VOLTAGE TO THE APPLIANCES.
Figure 1: ULC Directional Characteristics
-6dB
-3dB
95dB
-3dB
30°
60°
27°
-6dB
48°
81dB83dB
95dB
-3dB
-6dB
20°
30°
85dB
80°
-3dB
-6dB
NOTES:
1. The HS-24 is UL Listed for indoor use with a temperature range of +32°F to +120°F (0°C to +49°C) an d maximum humidity of 93% ± 2% RH.
WARNING: FOR UL APPLICATIONS THIS APPLIANCE WAS TESTED TO THE OPERATING VOLTAGE LIMITS OF 16-33 VOLTS USING FILTERED (DC) OR UNFILTERED FULL-WAVE-RECTIFIED (FWR). DO NOT APPLY 80% AND 110% OF THESE VOLTAGE VALUES FOR SYSTEM OPERATION.
WARNING: FOR ULC APPLICATIONS THIS APPLIANCE WAS TESTED TO THE OPERATING VOLTAGE LIMITS OF 20-31 VOLTS USING FILTERED (DC) OR UNFILTERED FULL-WAVE-RECTIFIED (FWR). APPLY 80% AND 110% OF THESE VOLTAGE VALUES FOR SYSTEM OPERATION.
WARNING: MAKE SURE THAT THE TOTAL RMS CURRENT AND TOTAL AVERAGE CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE SYSTEM’S PRIMARY AND SECONDARY POWER SOURCES, SIGNALING CIRCUITS, SM, DSM SYNC MODULES AND WHEELOCK’S POWER SUPPLIES DO NOT EXCEED THE POWER SOURCES’ RATED CAPACITY OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS TO WHICH THIS APPLIANCE IS WIRED. OVERLOADING POWER SOURCES OR EXCEEDING FUSE RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.