Cooper GWC Series Installation Instructions Manual

Sectionalizers
Type GWC Installation Instructions

Applicable to serial number 1088 and above

Cooper Power Systems
Service Information
S270-21-1
Figure 1. Kyle®Type GWC Sectionalizer.
Contents
Safety Information.................................................. 2
Hazard Statements.............................................. 2
Safety Instructions ............................................... 2
Additional Information.......................................... 2
Shipment and Acceptance..................................... 2
Handling and Storage ............................................ 2
General................................................................ 2
Control Battery Charging and Storage................. 3
Description.............................................................. 3
Ratings .................................................................... 3
Dimensions and Weights....................................... 4
Operating Controls................................................. 4
Remote Control Switch........................................ 4
115Vac - 5 amp Breaker Switch........................... 4
Manual Control Switch......................................... 4
One Count to Open Switch.................................. 5
Lamp Test Contact Position Switch ..................... 5
Battery Test Terminals ......................................... 5
Battery Load Test................................................. 5
Manual Trip Lever................................................ 5
Indicating Devices.................................................. 5
Settings ................................................................... 5
Minimum Actuating Current ................................. 6
Counts-to-Open ................................................... 6
Count Reset......................................................... 6
Count Restraint.................................................... 6
Inrush-Current Restraint ...................................... 6
Response Time.................................................... 6
88973KMA
Installation............................................................... 7
Preliminary Checks.............................................. 7
Lifting the Sectionalizer........................................ 7
Mounting the Sectionalizer .................................. 9
Mounting the Control ........................................... 9
Grounding the Control ......................................... 9
Control Cable....................................................... 9
Auxiliary Power....................................................... 9
Main Wiring.......................................................... 9
Interconnection Wiring Diagram, Control............12
Accessories ............................................................13
Auxiliary Switch....................................................13
Bushing-Type, Multi-Ratio Current Transformers 14
Operating Instructions...........................................14
Automatic Operation............................................14
Manual Electrical Operation.................................15
Manual Non-Electrical Operation.........................15
Control Battery .......................................................15
Battery Connections ............................................15
Battery Check ......................................................15
Testing.....................................................................16
Test Circuit and Equipment..................................16
Pre-Test Procedures............................................16
Test Procedures...................................................16
Post-Test Procedures ..........................................19
November 1991• Supersedes 12/88
Printed in USA
Type GWC Installation Instructions
SAFETY INFORMATION
Following is important safety information. For safe instal­lation and operation of this equipment, be sure to read and understand all cautions and warnings.
Hazard Statements
This manual contains two types of hazard statements:
WARNING: Refers to hazards or unsafe practices
!
which could result in severe personal injury, or
death, and equipment damage.
CAUTION: Refers to hazards or unsafe practices
!
which could result in damage to equipment or in
personal injury.
Safety Instructions
Following are general caution and warning statements that apply to this equipment. Additional statements, relat­ed to specific tasks and procedures, are located through­out the manual.
WARNING: Before installing, operating, main-
!
taining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage. G101.0
WARNING: This equipment is not intended to
!
protect human life. Follow all locally approved pro­cedures and safety practices when installing or operating this equipment. Failure to comply may result in death, severe personal injury and/or equipment damage. G102.0
WARNING: High voltage. Contact with high volt-
!
age will cause severe personal injury or death. Follow all locally approved safety procedures when work­ing around high voltage lines and equipment. G103.0
WARNING: Do not operate this equipment out
!
of oil. Oil is the electrical insulating medium within this equipment; operation out of oil will result in flashovers that will damage the equipment and may cause severe personal injury. G104.0
WARNING: Follow all locally approved proce-
!
dures and safety practices when installing or operating this equipment. Failure to comply may result in death, severe personal injury, and/or equip­ment damage. G111.0
CAUTION: This equipment requires routine inspec-
!
tion and maintenance to ensure proper operation. If it is not maintained it may fail to operate properly. Improper operation may cause equipment damage and possible personal injury. G105.0
CAUTION: Follow all locally approved safety
!
practices when lifting and mounting the equip­ment. Use the lifting lugs provided. Lift the load smoothly and do not allow the load to shift. Improper lifting may result in equipment damage. G106.0
CAUTION: Radiation. At voltages up to the
specified test voltages, the radiation emitted by the vacuum interrupter is negligible. However, above these voltages, radiation injurious to personnel may be emitted. See
Vacuum Interrupter Radiation Warning
information. G109.0
Service Information S280-90-1,
, for further
Additional Information
These instructions do not claim to cover all details or variations in the equipment, procedures, or process described, nor to provide directions for meeting every possible contingency during installation, operation, or maintenance. When additional information is desired to satisfy a problem not covered sufficiently for the user's purpose, please contact your Cooper Power Systems sales engineer.
SHIPMENT AND ACCEPTANCE
Each sectionalizer is completely assembled, inspected, tested, and adjusted at the factory and is filled to the cor­rect level with insulating oil. It is in good condition when accepted by the carrier for shipment. Upon receipt of a sectionalizer:
1. Inspect the sectionalizer thoroughly for damage and loss of parts or oil incurred during shipment. If dam­age or loss is discovered, file a claim with the carrier immediately.
2. Check for oil leakage and tighten all bolts that may have been loosened during shipment, especially the bolts attaching the head to the tank.
2
HANDLING AND STORAGE
General
If the sectionalizer is to be stored for an appreciable time before installation, provide a clean, dry storage area. Locate the sectionalizer so as to minimize the possibility of mechanical damage. In particular, protect the bushings and keep the operator cabinet closed to protect the electronic control components.
S270-21-1
Control Battery Charging and Storage
The control battery is fully charged just prior to shipment and is ready for use. However, storage for the length of time will cause the battery to gradually lose its storage. Loss of charge accelerates with increase in ambient temperature.
For trouble-free performance, it is highly recommended that the battery be kept on trickle charge (approximately 15mA) until the control is put into service, especially if it is to be in transit and/or storage for more than 30 days. The battery can tolerate a continuous trickle charge of 15mA indefinitely with­out damage.
Unless the battery is known to be fully charged, it is recom­mended that it be charged 50mA for 48 hours and then maintained at 15mA until the control is out of service.
Like the control cabinet heater, the battery can be kept charged by energizing the battery charger in the control with 120Vac applied to Terminals 5 and 6 of the input terminal strip.
NOTE: When shipped from the factory, the battery is discon-
nected and the output plug is taped to the side of the battery, Connect the battery plug into the mating recep­tacle below the battery to complete the battery circuit.
CAUTION: Electrical shock hazard. Be sure
!
the grounded side of the 120 Vac auxiliary power circuit is connected to the terminal labeled COMMON AC GND (usually terminal 5). A 120 Vac short-to-ground will exist if the input connections are reversed. Failure to comply could result in personal injury and equipment damage. T219.0
If it is not convenient to apply 120Vac power to a stored control, the battery can be removed from the control cabi­net and charged on the bench with a dc source which supplies approximately 15mA charging current to the bat­tery. A dual-rate portable trickle charger, Catalog No. KA1142ME3, is available for this purpose. It provides a selectable output of either 15mA for maintaining a charged battery. This unit plugs into a standard 120Vac receptacle and has an output plug at the end of a 4-foot cord which mates with the battery plug.
val of the backup device. For this reason, it must always be used in series with a fault-interrupting backup protective reclosing device. Also, it will reset counts that do not reach the counts-to-open setting within the selected reset time due to clearing of temporary faults.
A minimum of 0.5 amps of load current flowing through the sectionalizer will block the generation of a count pulse. This “count-restraint” feature prevents the sectionalizer from counting overcurrents interrupted by down-line devices.
The sectionalizers are also equipped with an inrush-cur­rent restraint feature which distinguishes between inrush currents and fault currents. If it is determined that the over­current through the sectionalizer is inrush current, the phase and ground current levels of the sectionalizer are blocked for a duration of 3 seconds upon current detection.
Ratings
Tables 1 and 2 show rating information for the Type GWC sectionalizer.
Table 1 Basic Sectionalizer Ratings
Type GWC
Nominal Voltage (kV)........................................................ 34.5
Rated Maximum Voltage (kV)........................................... 38.0
Impulse Withstand 1.2 x 5.0 microsecond wave
BIL (kV) .............................................................................. 150
60 hertz withstand
Dry, 1 minute (kV)............................................................ 70
Wet, 10 seconds (kV)...................................................... 60
Continuous Current Rating (amps) ....................................400
Rated symmetrical interrupting current (amps rms)........... 880
Rated making current, asymmetrical (amps rms) .......... 15000
DESCRIPTION
The sectionalizer is a self-contained, circuit-opening device used in conjunction with source-side protective devices such as reclosers or circuit breakers, to automatically iso­late faulted sections of electrical distribution systems. The sectionalizer senses current flow above a preset level, and when the source-side protective device opens to de-ener­gize the circuit, the sectionalizer counts the overcurrent interruption. Depending upon the coordination scheme, the sectionalizer will open during the first, second, and third open interval of the fault interrupting device to isolate per­manent faults and confine outages to smaller sections of line.
The sectionalizer does not interrupt fault current but can
be closed into a faulted line. It opens during the open inter-
Short-time ratings (amps rms)
10-seconds symmetrical ............................................ 3500
1-second symmetrical................................................ 10000
Momentary maximum, asymmetrical (amps rms) .......... 15000
Table 2 Operating Data
Phase-minimum-actuating 16, 24, 40, 56, 80, 112, 160,
current (amps) 224, 256, 296, 320, 448, 480, 640
Ground-minimum-actuating 3.5, 7, 16, 20, 28, 40, 56, 80
current (amps) 112, 160, 224, 320, BLOCK
Number of counts to open 1, 2, 3
Count reset (seconds) 15, 30, 60, 90, 120, 180
3
Type GWC Installation Instructions
Dimensions and Weights
Figure 2 shows essential dimensional information for a Type GWC sectionalizer, along with its weight and oil capacity.
Operating Controls
The operating controls of the sectionalizer are located on the front panel, within the control cabinet, as shown in Figure 3.
Remote Control Switch
In the ON position, this switch permits the sectionalizer to be operated by remotely located “dry” contacts which are wired to a terminal block in the control cabinet. Separate normally-open contacts are required for the open and close operation.
In the OFF position, this switch disables remote con­trol but means of the control panel switches).
An extra set of contacts on this switch can provide switch position information to the remote location.
does not
prevent automatic operations (by
115Vac - 5amp Breaker Switch
In the ON position, this switch energizes all 115Vac power to the control cabinet and the operating housing of the sectionalizer.
Manual Control Switch
While in the TRIP position, the sectionalizer main con­tacts are open and the closing circuit is disabled.
When placed in the CLOSE position, the sectionalizer closing circuit is energized, the closing solenoid will be momentarily energized and the sectionalizer will close.
Figure 2. Type GWC Sectionalizer.
4
S270-21-1
One Count-to-Open Switch
When set to the ONE COUNT TO OPEN position, the section­alizer will open on the completion of the first overcurrent count. This feature provides added safety during downline hot-line work. The operation of this switch also cancels out any accu­mulated memory time and resets the count to zero.
Lamp Test Contact Position Switch
When set to CONTACT POSITION, this momentary con­tact, center-off switch energizes the appropriate lamp to indi­cate the position of the main contacts in the sectionalizer; green lamp indicates open, the red lamp indicates closed.
In the LAMP TEST position, both lamps are energized to check their condition.
Battery Test Terminals
The battery test terminals enable convenient checking of the battery voltage, charging rate and battery quiescent drain current.
Battery Load Test
This switch is used in conjunction with the BATTERY TEST TERMINALS. While checking battery voltage, pressing this button connects a 10 ohm load resistor over the battery, allowing measurement of loaded battery voltage.
Manual Trip Lever
In addition to the controls described above, a manually operated trip lever is located on the underside of the operator cabinet. Capable of being operated with a hook­stick, this lever will mechanically trip the operating mech­anism to open the sectionalizer.
Once pulled down, the lever stays down and disables the closing circuit to block closing of the sectionalizer. The lever must be returned manually to its “UP” position to re-activate the closing circuit.
INDICATING DEVICES
In addition to the contact position indicator lamps on the con­trol panel; a contact position indicator and an operations counter are located under the sleet hood, on the mechanism operator cabinet.
The yellow contact position indicator is pinned to the main operating shaft of the sectionalizer to indicate the OPEN and CLOSED condition of the main contacts.
The operations counter gives a visual indication of the cumulative number of openings of the unit.
SETTINGS
The operating characteristics are preset to customer specifications and tested prior to shipment from the facto­ry. However, if the sectionalizer is relocated or the coordi­nation scheme is modified, the operating characteristics can be easily changed in the field. The settings should be checked before the unit is put into service. All settings are located on the printed circuit board mounted on the control front panel. See Figure 3.
NOTE: Before changing the trip resistor settings, the section-
alizer must be bypassed and de-energized.
GROUND MINIMUM
ACTUATING CURRENT
RESISTOR
PHASE MINIMUM
ACTUATING CURRENT
RESISTOR
COUNT-TO-OPEN
SELECTOR
Figure 3. Operator Control Panel.
COUNT RESET SELECTOR
115VAC BREAKER SWITCH
ONE-COUNT-TO­OPEN SWITCH
REMOTE CONTROL SWITCH
LAMP TEST, CONTACT POSITION SWITCH
MANUAL CONTROL SWITCH
BATTERY LOAD TEST SWITCH
BATTERY TEST TERMINALS
911042KMA
5
Type GWC Installation Instructions
Minimum Actuating Current
The minimum actuating current levels for both phase and ground are determined by the selection of the proper plug-in resistors. (Normally these settings are approximately 80 percent of the minimum trip settings of the backup protective device.)
NOTE: If the backup device is not equipped for ground fault
sensing and tripping, the ground current sensing cir­cuits of the sectionalizer can be de-activated by using a shorting resistor labeled “BLOCK”.
Phase current resistors are identified with the phase sym­bol (ø) and the actuating current value in amps. Catalog numbers for the available phase current resistors are listed in Table 3.
Table 3 Minimum Actuating Resistor (Phase)
Label Value Resistance (ohms)
(amps) Minimum Maximum Catalog Number
16 264 270 KA176GV16 24 172 176 KA176GV24 40 94.3 96.3 KA176GV40 56 66.3 67.7 KA176GV56
80 47 48 KA176GV80 112 32.6 33.4 KA176GV112 160 22.9 23.5 KA176GV160 224 16.3 16.7 KA176GV224 256 13.8 14.2 KA176GV256 296 11.9 12.3 KA176GV296 320 11.1 11.5 KA176GV320 448 8.1 8.3 KA176GV448 480 7.4 7.6 KA176GV480 640 5.5 5.7 KA176GV640
Table 4 Minimum Actuating Resistor (Ground)
Label Value Resistance (ohms)
(amps) Minimum Maximum Catalog Number
3.5 6.91K 7.05K KA177GV3
7 1.168K 1.192K KA177GV7 16 379.0 387.0 KA177GV16 20 298.0 304.0 KA177GV20 28 200.0 204.0 KA177GV28 40 135.63 138.37 KA177GV40 56 94.3 96.3 KA177GV56 80 66.3 67.7 KA177GV80
112 47.0 48.0 KA177GV112 160 32.6 33.4 KA177GV160 224 22.9 23.5 KA177GV224 320 15.8 16.2 KA177GV320
BLOCK 0 0.1 KA177GVBLO
Ground current resistors are identified with the ground sym­bol ( ) and the actuating current value in amps. Catalog numbers for the available ground current resistors are listed in Table 4.
The minimum actuating current of the sectionalizer for both phase and ground can be changed by merely changing the appropriate plug-in resistor.
Counts-to-Open
The counts-to-open setting is determined by the position of the COUNTS-TO-OPEN SELECTOR switch. Switch positions 1, 2, and 3 correspond to 1, 2, or 3 counts to open. Normally this setting is one less than the number of operations to lockout of the backup protective device. To change the number of counts-to-open setting, merely change the position of the rotary switch.
Count Reset
The reset setting is determined by the position of the COUNT RESET switch. Reset times of 15, 30, 60, 90, 120, and 180 seconds are available. This feature resets to zero, and any accumulated counts are cancelled whenever current, below the minimum actuation level, flows through the sectionalizer without interruption for longer than the time programmed.
The reset feature will operate with any current flow from minimum load (5 amps) to values below phase or ground pickup levels.
Count Restraint
The count-restraint feature blocks the sectionalizer from generating a count pulse as long as 0.5 amps of load current flows through the sectionalizer.
Inrush-Current Restraint
The inrush-current restraint feature blocks the phase and ground actuating levels for three seconds after current flow through the sectionalizer has been restored and the overcurrent has been determined to be inrush current.
The three-second time interval allows for system inrush parameters to stabilize prior to allowing the sensitivity of the sectionalizer to return to its programmed state.
Response Time
For backfed motor contribution and unsymmetrical clear­ing of upline faults, a response time is built into the sec­tionalizer control to eliminate unwanted counting of these situations. Upon detection of any current above the phase or ground actuating setting, the current must exceed the response time characteristics as illustrated in Figure 4. Total clearing time of reclosers and breakers must exceed the response time characteristics of the sectionalizer.
6
Loading...
+ 14 hidden pages