Cooper F6-PA-LS, F6-PB-LS Installation And Operation Instructions Manual

Reclosers
Form 6-LS Microprocessor-Based Pole Mount Recloser Control Installation and Operation Instructions
For Type F6-PA-LS Control and Type F6-PB-LS Control.
 •F6-PA-LSappliestoForm6-LS
control for use with W, VS, and auxiliary-powered NOVA reclosers.
 •F6-PB-LSappliestoControl-Powered
NOVA Form 6-LS control for use with control-powered reclosers.
Figure 1. Form 6-LS microprocessor-based pole-mount recloser control.
Contents
Service Information
S280-70-10
Safety Information ..................................................... 2
Product Information .................................................. 3
Introduction ............................................................ 3
ANSI Standards ..................................................... 3
Quality Standards ................................................... 3
Acceptance and Initial Inspection ........................... 3
Handling and Storage ............................................ 3
Control Power ........................................................ 3
Battery Replacement and Disposal ........................ 3
Operation Upon Loss of AC Power ........................ 4
Form 6-LS Recloser Control Description ................. 4
Description ............................................................. 4
Theory of Operation ............................................... 5
Control Front Panel ................................................ 6
Installation Procedure ............................................... 16
Mounting the Control .............................................. 18
Locking the Control ................................................ 18
October 2012 • Supersedes 10/04
Before Placing Control and Recloser into Service .... 31
Radio Mounting Accessory ..................................... 34
Testing with Type MET Tester ................................. 38
Recloser VTC Interface ............................................. 45
Control VTC Interface ............................................... 46
Additional Information ............................................... 47
1
1
Form 6-LS Pole Mount Recloser Control Installation and Operation Instructions
SAFETY FOR LIFE
Cooper Power Systems products meet or exceed all applicable industry standards relating to product safety. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Cooper Power Systems employees involved in product design, manufacture, marketing, and service.
We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high voltage lines and equipment and support our “Safety For Life” mission.
SAFETY INFORMATION
The instructions in this manual are not intended as a substitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians who are familiar with this equipment should install, operate, and service it.
A competent technician has these qualifications:
 •Isthoroughlyfamiliarwiththeseinstructions.
 •Is trained in industry-accepted high- and low-voltage
safeoperatingpracticesandprocedures.
 •Is trained and authorized to energize, de-energize,
clear,andgroundpowerdistributionequipment.
 •Is trained in the careanduseofprotectiveequipment
suchasflashclothing,safetyglasses,faceshield,hard hat,rubbergloves,hotstick,etc.
Following is important safety information. For safe installation and operation of this equipment, be sure to read and under stand all cautions and warnings.
Safety Instructions
Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual.
DANGER:
Hazardous voltage. Contact with hazardous voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around high­and low-voltage lines and equipment. G103.3
WARNING:
Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling, or maintenance can result in death, severe personal injury, and equipment damage. G101.0
Hazard Statement Definitions
This manual may contain four types of hazard statements:
DANGER: Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING: Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
CAUTION: Indicates a potentially hazardous situa­tion which, if not avoided, may result in equipment damage only.
2
WARNING:
This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply may result in death, severe personal injury, and equipment damage. G102.1
WARNING:
Power distribution and transmission equipment must be properly selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety proce­dures. These instructions are written for such personnel and are not a substitute for adequate training and expe­rience in safety procedures. Failure to properly select, install, or maintain power distribution and transmission equipment can result in death, severe personal injury, and equipment damage. G122.3
PRODUCT INFORMATION
S280-70-10
Introduction
Service Information S280-70-10 provides installation and operation instructions for the Form 6-LS pole mount recloser control with loop scheme accessory.
Refer to the following information as appropriate for your version of ProView software:
• Service Information S280-70-4 Form 6 Recloser ControlProgrammingGuide:ProView4.X.Xsoftware
• Service Information S280-70-21 Form 6 Recloser ControlProgrammingGuide:ProView5.X.Xsoftware
Read This Manual First
Read and understand the contents of this manual and follow all locally approved procedures and safety practices before installing or operating this equipment.
Additional Information
These instructions cannot cover all details or vari ations in the equipment, procedures, or process described, nor provide directions for meeting every possible contin gency during installation, operation, or maintenance. When additional information is desired to satisfy a problem not cov ered sufficiently for the user's purpose, contact your Cooper Power Systems sales representative.
ANSI Standards
Kyle reclosers are designed and tested in accordance with the following ANSI standards: C37.60 and C37.85 and ANSI Guide C37.61.
Quality Standards
ISO 9001-Certified Quality Management System
Acceptance and Initial Inspection
Each Form 6 recloser control is completely assembled, tested, and inspected at the factory. It is carefully calibrated, adjusted and in good condition when accepted by the carrier for shipment.
Upon receipt, inspect the carton for signs of damage. Unpack the control and inspect it thoroughly for damage incurred during shipment. If damage is discovered, file a claim with the carrier immediately.
Handling and Storage
Be careful during handling and storage of the control to minimize the possibility of damage. If the control is to be stored for any length of time prior to installation, provide a clean, dry storage area. If storage is in a humid atmosphere, make provisions to keep the control circuitry energized.
Note: To energize the control, apply AC power to the AC supply
input terminal block located in the lower right hand corner of the back panel of the control. Refer to the Customer Connections for AC Power section in this manual.
Control Battery Storage and Charging
The 24 VDC control battery in the Form 6 recloser control is
fully charged prior to shipment and is ready for use.
IMPORTANT: To maintain sufficient charge to operate the control and prevent battery cell damage, the sealed lead-acid batteries should be charged after no more than three months of storage.
Temperature has an effect on battery life. Sealed lead acid batteries should be stored, fully charged, at room temperature. Never store lead acid batteries at temperatures
exceeding 47°C (117°F), as damage can result in
approximately one month.
The batteries must be tested and charged for 24 hours
following every three months of storage from the last test date. A separate portable charger accessory is available.
Catalog Number KA43ME7001 provides a 120 Volt battery
charger to power individual batteries.
IMPORTANT: Connect the control battery before AC power is connected to the control’s AC supply Input Terminal Block. The battery must be disconnected prior to shipping or storing the control.
Note: When shipped from the factory, the battery source is
disconnected and its output plugs are taped to the cabinet. Connect the battery plugs into the mating connectors to complete the battery circuit.
Control Power
CAUTION: Equipment misoperation. Verify that
the 120/240 VAC selector switch is correctly set
for incoming voltage. Failure to comply may cause
misoperation (unintentional operation) of the control and/
or equipment damage resulting in personal injury. T278.0
CAUTION: Equipment damage Form 6-LS (Loop Scheme). Do not connect 240 VAC to B or Y phases on terminal blocks TB7 or TB8. 240 Volts will damage
internal components and cause control misoperation. T314.0
The Form 6-LS control is powered from 120 VAC. The selector switch on the power supply board must be set to the 115V position.
Battery Replacement and Disposal
The 24 VDC control battery has a life expectancy of four
years. It is recommended that the battery be replaced after four years or if the battery fails a battery test - whichever occurs first.
Note: Battery life is decreased at higher temperatures.
Dispose expired batteries in an environmentally responsible manner. Consult local regulations for proper battery disposal.
3
Form 6-LS Pole Mount Recloser Control Installation and Operation Instructions
Operation Upon Loss of AC Power
The control is equipped with a 13 Amp-Hour 24 VDC lead
acid battery for operation upon loss of AC power. The control maintains full operation from the battery for a period
of time — 24 hour maximum (20°C)
In the event that the AC power has not returned within the times listed above, the control will disconnect the battery from the circuit.
Note: The control continuously monitors the battery voltage. To
prevent battery damage, the control shuts down automatically upon detection of low battery voltage
(below 22 VDC) for 60 seconds.
Control programming settings and parameters—including event recorder—are stored in non-volatile memory and retained upon loss of control power. The time/date clock will continue to operate for approximately 30 days after loss of control power.
Phase B and Y inputs are the factory default connections for powering the control. If B and Y phases lose AC power,
the red ALARM indicator LED will illuminate, the green CONTROL OK indicator LED will not be illuminated, and the ALARM log on the LCD display will indicate NO AC PRESENT.
IMPORTANT: If the the control shuts down due to low battery voltage before AC power is restored, and the connected energized recloser is CLOSED; it will only TRIP and LOCKOUT via front panel pushbutton command.
A control that has shut down due to low battery voltage before AC power is restored will have a blank LCD
display (no text message shown) and none of the LEDs
will be illuminated.
The control clock may require resetting if the operating power has been disconnected for more than thirty days. Refer to ServiceInformationS280-70-4(ProView4.X.X)or
S280-70-21 (ProView 5.X.X) Form 6 Microprocessor­BasedRecloserControlProgrammingGuide for information
on setting the control clock.
Note: When AC power is present, the control will operate
regardless of back-up battery presence.
Note: In the event of loss of AC control power to the control
(without battery back-up power), the LS control will be
disabled when power is restored to the control:
• In the TIE Mode, once voltage is restored, the LS is
disabled until locally or remotely enabled. This is to ensure that the TIE recloser will not close automatically upon restoration of voltage from one source.
• In the SECTIONALIZING mode, once voltage is
restored, the LS is disabled until locally or remotely enabled. The recloser remains in the same state prior
to the loss of voltage. The SECTIONALIZING unit will
not close automatically. This also prevents any automatic closing when auto reset is enabled.
Note: LS must be enabled via the ProView interface software
Loop Scheme Settings Dialog screen located in the Idea Workbench.
FORM 6-LS RECLOSER
CONTROL DESCRIPTION
Description
The Form 6-LS pole-mount microprocessor-based recloser control includes extensive auto-reconfiguration system protection functionality, including phase, ground, and negative sequence overcurrent protection, over/ underfrequency, and voltage protection, directionality, sensitive ground fault, and sync check.
The control is for application in distribution feeder loop sectionalizing schemes. The Form 6-LS control senses the loss of voltage, and after a predetermined time delay, performs the programmed action to restore service to the affected feeder.
The control can be programmed for either the sectionalizing or tie mode of operation. The sectionalizing mode senses voltage on the source side of a normally closed recloser and is activated upon loss of source-side voltage. The tie mode of operation senses voltage on both sides of a normally open recloser and is activated upon loss of voltage on either side. The tie mode is used for both one­way and two-way tie applications.
Analysis tools include fault locating, event recording, TCC Editor II, Idea Workbench, Data Profiler, and oscillography functions, including oscillography replay.
Metering functions include demand and instantaneous current on a per-phase basis, instantaneous voltage and
power factor on a per-phase basis, and power (real, reactive, apparent) on a per phase or total basis.
Symmetrical components for both voltage and current are displayed along with kilowatt-hours for energy metering. Harmonics from the 2nd to the 15th harmonic are also included.
The front panel LCD display is used to configure the operating settings for the control. It is also used to display metering, counter information, control parameters, reset alarms, and provide diagnostic information.
Control parameters can also be programmed via a personal computer connected to the control through the front panel RS-232 port. Control programming, interrogation, and operations are performed with Form 6 ProView interface software on a personal computer.
ProView interface program software includes additional functions used to create and graphically display Time Current Curves and provides the Idea Workbench for configuring user-selected inputs and outputs, configurable event and alarm data, and selectable communication points for serial communication.
The control operates on 50 and 60 Hz systems.
The control can be configured, by the factory or by the user, for a wide variety of applications. If user requirements change, the control functions can be modified to meet the new requirements.
The control is accessible from both the front and back of
the cabinet (Figure 2).
4
TRIP SOLENOID
CLOSE SOLENOID
A Ø CT
B Ø CT
C Ø CT
OPEN / CLOSE
SWITCHES
CT COMMON
RECLOSER
POWER
24 VDC BATTERY
INTERCON­NECTION BOARD
CPU
I/O
FRONT PANEL
RS-232
(PROVIEW
PROTOCOL
ONLY)
TB7
TERMINAL
BLOCK
120/VAC OUTLET DUPLEX
ACCESSORY
TB8
TERMINAL
BLOCK
SENSING
VOLTAGE
INPUTS
3 inputs
USER
CONNECTIONS
5 outputs
8 inputs
USER
CONNECTIONS
8 outputs
MATCHING
TRANSFORMERS
AND SIGNAL
CONDITIONING
ANALOG INPUT
RIF
OPTICAL
ISOLATION
OPTICAL
ISOLATION
OPTICAL
ISOLATION
OPTICAL
ISOLATION
RS-232 IRIG-B
COMMUNICATIONS BOARD ACCY
RS-485
FIBER-OPTIC
ETHERNET
TRANSFER
RELAY
SOURCE I
SOURCE II
INPUT VOLTAGE 120 VAC
TEST SWITCHES
Figure 2. Form 6-LS pole mount recloser control is accessible from both the front and back of the cabinet.
Theory of Operation
A functional block diagram of the Form 6-LS recloser con­trol is shown in Figure 3. Current sensing is provided by three current transformers located in the recloser and inter­faced to the Form 6 recloser control via the control cable. This cable also supplies Trip, Close, and Recloser status,
and connects to the Recloser Interface (RIF) module to
provide isolation for reliable operation. Voltages for meter­ing are connected to the analog input module through terminal block TB8.
Line current flowing through the recloser is converted by the CPU module to a digital signal suitable for metering and fault current calculations. Data sampling occurs at a rate of
64 times per cycle. The CPU contains a data acquisition
section that uses the acquired samples to compute the fundamental currents and voltage for use in overcurrent, under/overvoltage, and under/overfrequency protection, as well as currents and voltages for metering functions.
S280-70-10
The current for overcurrent protection is calculated on a sub-cycle basis; it includes only the fundamental and DC component.
When the phase or ground current exceeds its pro­grammed minimum-trip value and associated time-cur­rent-curve (TCC) timing, the control initiates the pro­grammed sequence of recloser tripping and reclosing operations via the CPU and RIF modules. If the fault is temporary, the control ceases to command recloser oper­ations after a successful reclose, and the control resets to the start of its operating sequence after a preset time delay. If the fault is permanent, the control performs its complete programmed sequence of reclose commands and locks out with the recloser open. Once locked out, the control must be closed via the operator panel or SCADA communications. This resets the control to the start of the operating sequence.
The following chain of events occurs for an operating
sequence of two trips to lockout (one trip on TCC1, one trip on TCC2):
1. The overcurrent signal is integrated with time on the selected curve for the first trip operation (TCC1) to pro­duce the signal which energizes the trip circuit.
2. Energizing the trip circuit connects the supply to the trip solenoid to open the recloser.
3. Upon opening, the control starts timing on the first reclosing interval-delay time.
4. Upon expiration of this reclosing interval-delay, a clos­ing signal is issued from the control, closing the reclos­er, and selecting the time-current characteristics for the
second trip operation (TCC2).
5. If current remains above the minimum-trip level, the recloser will trip on TCC2 and lockout the recloser.
Figure 3. Form 6-LS pole mount recloser control operational flow diagram.
5
Form 6-LS Pole Mount Recloser Control Installation and Operation Instructions
CONTROL POWER
CONTROL OK
CONTROL LOCKOUT RECLOSER OPEN
RECLOSER CLOSED
A PHASE FAULT
B PHASE FAULT C PHASE FAULT GROUND FAULT
SENSITIVE GND
ALARM
ABOVE MIN TRIP TIE SECTIONALIZER
LS DISABLED
A PHASE VOLTAGE
B PHASE VOLTAGE
C PHASE VOLTAGE FREQUENCY TRIP
VOLTAGE TRIP
METERING
RESET
TARGETS
EVENTS
LAMP TEST
MENU
ENTER
+
SETTINGS
OPER
COUNTER
ALARMS
CHANGE
F1 F2 F3 F4
TRIP CLOSE
HOT LINE TAG
ON
GRD TRIP BLOCKED
NON
RECLOSING
SUPERVISORY
OFF
LS RESET
SOURCE I ENABLED
SOURCE II ENABLED
F6 Recloser Control
RS-232 DATA PORT
OPTION#1 OPTION #2 OPTION#3
(LOCKOUT)
X PHASE VOLTAGE
Y PHASE VOLTAGE Z PHASE VOLTAGE INDICATOR 7
INDICATOR 8
LCD Display
LCD Display
Dedicated
Function Keys
One-Touch
Analysis Keys
Hot Line Tag Toggle Switch and Three-Segment LED Indication
RS-232 Configuration Data Port
CLOSE Pushbutton
TRIP (LOCKOUT)
Pushbutton
LED Indicators
LCD Display Dedicated Function Keys
One-Touch Function Keys
Cursor Movement Arrows
LCD Menu Function Keys
One-Touch Analysis Keys
Close Circuit Disable Fuse and Fuseholder
CLOSE CIRCUIT
DISABLE
Control Front Panel
The Form 6-LS control front panel is illustrated in Figure 4.
The front panel is separated into two clearly identified, color-coded sections:
• The top portion of the front panel is used for programming
the control and providing LED status indication.
• The lower portion of the front operating panel is used
for operating the control and recloser.
The control includes a Power Save feature that will turn off
the backlit LCD display and all LEDs (except Hot Line Tag)
if no front panel keypad is pressed within ten minutes. Pressing the LAMP TEST key will re-activate the display and LEDs.
Note: The Power Save feature is a ProView interface software
default setting. This feature can be disabled via the ProView interface software.
The control includes a Reset Menu feature that will cause the LCD display to revert to the root menu after ten minutes of inactivity.
Note: The ten minute timer and MMI Reset Menu is a ProView
interface software default setting. The menu selection and timer can be changed via the ProView interface software.
Front Panel Text Messaging
The LCD messages are accessed from the front panel by following the Text Messages menu path. This menu displays any active user-configured text messages.
Up to fourteen user-configurable text messages can be programmed via the Idea Workbench. Refer to Service
Information S280-70-4 (ProView 4.X.X) or S280-70-21 (ProView 5.X.X) Form 6 Control Programming Guide for
information on programming the text messages.
These text messages appear on the front panel LCD and can be programmed to appear for alarm or other conditions.
Text messages displayed on the front panel are limited to
four lines of 20 characters each (including spaces). Text
messages can also be accessed by pressing the LAMP TEST one-touch analysis key on the front panel.
Figure 4. Form 6-LS control front panel.
6
S280-70-10
METERING
RESET
TARGETS
EVENTS
LAMP TEST
MENU
ENTER
+
SETTINGS
OPER
COUNTER
ALARMS
F1 F2 F3
F4
CHANGE
Programming Panel
The Programming panel has the following sections:
One-Touch Analysis Keys
There are eight analysis keys (Figure 5) that allow one-
button access to a variety of control and monitoring func­tions that appear in the LCD display. Pressing these but­tons causes the following information to display or function to occur:
Note: When pressing a membrane pushbutton, always press
and hold for 0.5 seconds to ensure the button press is recognized by the device.
METERING: Displays the systems instantaneous metering values for current and voltage on the LCD display.
RESET TARGETS: Resets the fault target indicators on the operator panel.
EVENTS: Displays the last 25 events from the Sequence of Events log.
LAMP TEST: All operator panel LEDs are illuminated for verification of proper connection and operating status of all indicator lights. All status indicators will then return to their previous state. While in the LAMP TEST mode, the control response to operator panel keys is disabled, except for the
TRIP (LOCKOUT), CLOSE, and HOT LINE TAG switches.
SETTINGS: Displays recloser settings on the LCD display.
OPER COUNTER: Displays the total number of trip opera­tions and target counters for each A, B, and C Phase; Ground, and Sensitive Ground on the LCD display.
ALARMS: Provides status information on the LCD display for all recloser alarms.
CHANGE: Allows the user to change the state of the con­trol functions on the operator panel function keys.
Note: The CHANGE mode is a ten second period in which one
function setting can be changed. If no change is made in that time, the control returns to the current setting.
LCD Display
The LCD Display is a backlit 4-line, 20-character display
that provides extensive distribution system, recloser, and control status information using a minimum of eight naviga-
tion keypads (Figure 5).
Note: The LCD display panel contrast is field-adjustable to
allow for various mounting heights and applications.
Press the MENU key and then press the (+) or (–) key to
increase or decrease the contrast.
The four LCD navigation buttons are as follows:
MENU: Identifies the LCD Display menu options.
ENTER: Selects a menu option.
+: Increases value selection.
–: Decreases value selection.
The four LCD menu function keys activate specific menu commands. When a command appears in the LCD display directly above one of the four LCD menu function keys, the user can press the key to accept/select the command.
The four LCD menu function keys are as follows:
F1 F2 F3 F4
The four cursor movement arrows allow movement in the following directions:
 Moves the cursor left.
 Moves the cursor right.
 Moves the cursor up one line.
 Moves the cursor down one line.
Figure 5. Analysis keys, LCD display, LCD menu function keys, and cursor movement arrows.
7
Form 6-LS Pole Mount Recloser Control Installation and Operation Instructions
CONTROL POWER
CONTROL OK
CONTROL LOCKOUT RECLOSER OPEN
RECLOSER CLOSED
A PHASE FAULT B PHASE FAULT C PHASE FAULT GROUND FAULT
SENSITIVE GND
ALARM ABOVE MIN TRIP TIE SECTIONALIZER
LS DISABLED
A PHASE VOLTAGE
B PHASE VOLTAGE
C PHASE VOLTAGE FREQUENCY TRIP VOLTAGE TRIP
X PHASE VOLTAGE Y PHASE VOLTAGE Z PHASE VOLTAGE INDICATOR 7
INDICATOR 8
Status Indicator LEDs
The status indicator LEDs (Figure 6) in the Programming
section of the Operator Panel give instant information on the control and recloser status:
All of the default status indicators LEDs (except for CONTROL OK, CONTROL POWER, and ALARM) can be
reconfigured via the Idea Workbench. Refer to Service Information S280-70-4 (ProView 4.X.X) or S280-70-21 (ProView 5.X.X) Form 6 Control Programming Guide for
additional information.
The label inserts can be user-customized. Refer to Using Removable Inserts section of this manual for additional information.
CONTROL OK: The green LED indicates the control is operating normally and not in an alarm state.
The CONTROL OK LED will not be illuminated during these
alarms (indicated by the red ALARM LED and displayed in the alarm status log):
• Battery Alarm: This alarm indicates battery voltage is
low or the battery failed an operator-initiated manual test.
• RAM Failure: This alarm indicates a failed RAM memo­ry test.
• ROM Failure: This alarm indicates a failed ROM mem­ory test.
• No AC Present: This alarm indicates AC power was
unavailable for 10 continuous seconds. This alarm resets when AC power is restored.
• Power Supply Malf[unction]: This alarm indicates
internal control operation power was outside of its operating tolerance for more than 20 seconds. This alarm resets when the internal control operation power returns to operation within its normal tolerances.
• RIF Comm Failure: This alarm indicates a loss of communication from the RIF (Recloser Interface) circuit
board to the main CPU circuit board. This alarm resets if communication is re-established.
CONTROL POWER: The green LED indicates there is adequate VTC voltage to trip the recloser. This LED does not indicate the presence of AC or battery power.
CONTROL LOCKOUT: The green LED indicates the control is in a locked out state, i.e. a reclosing sequence is not in progress. This LED does not indicate that the recloser is open.
RECLOSER OPEN: The green LED indicates the recloser is in the open position.
RECLOSER CLOSED: The red LED indicates the recloser is in the closed position.
Note: There are several conditions that will cause the alternate
blinking of the CONTROL LOCKOUT, RECLOSER OPEN, and RECLOSER CLOSED LEDs: Failure to Trip, Failure to Close, Interrupter Malfunction, and 52a/b Disagreement.
The LED blinking pattern for these conditions is the
CONTROL LOCKOUT green LED and RECLOSER CLOSED red LED alternating with the RECLOSER OPEN green LED.
In addition to the above LED blinking pattern, the red
ALARM LED will also be illuminated for these alarms: Failure to Trip, Failure to Close, and Interrupter Malfunction.
A PHASE FAULT, B PHASE FAULT, C PHASE FAULT: The red LEDs indicate A, B, and/or C phase current was either the maximum phase current or within 20% of the maximum when a trip signal was issued.
GROUND FAULT, SENSITIVE GROUND FAULT: The red LEDs indicate that a Ground and/or Sensitive Earth Fault tripping function was asserted at the time the trip signal was asserted.
ALARM: The red LED indicates an alarm has been issued. Review the alarm status and log on the LCD display for the specific alarm.
ABOVE MINIMUM TRIP: The red LED indicates the current exceeds the level set for minimum trip.
Figure 6. Form 6-LS control status indicator LEDs.
8
S280-70-10
TIE: The red LED indicates the control is in tie mode and will respond to voltage conditions on Source I and/or Source II.
SECTIONALIZER: The red LED indicates the control is in
sectionalizing mode and will respond to voltage conditions on Source I.
Note: When in Sectionalizing mode, the SOURCE II ENABLED
function key is not responding to voltage even though it is illuminated.
LS DISABLED: The red LED indicates the LS accessory is not active. When LS is disabled, the Form 6-LS control will not respond to the LS loss of voltage parameters as set in the ProView interface software Loop Scheme Settings Dialog screen located in the Idea Workbench.
Note: In the event of loss of AC control power to the control
(without battery back-up power), the LS control will be
disabled when power is restored to the control:
• In the TIE Mode, once voltage is restored, the LS is
disabled until locally or remotely enabled. This is to ensure that the TIE recloser will not close automati­cally upon restoration of voltage from one source.
• In the SECTIONALIZING mode, once voltage is
restored, the LS is disabled until locally or remotely enabled. The recloser remains in the same state prior
to the loss of voltage. The SECTIONALIZING unit will
not close automatically. This also prevents any auto­matic closing when auto reset is enabled.
Note: LS must be enabled via the ProView interface software
Loop Scheme Settings Dialog screen located in the Idea Workbench.
A PHASE VOLTAGE, B PHASE VOLTAGE, C PHASE VOLTAGE: These red memory LEDs indicate the appropri-
ate phase(s) that initiated the Loop Scheme functionality.
These LEDs are controlled by the Voltage Controls settings in the Loop Scheme Settings dialog box.
If LS is enabled, at the moment loss of voltage occurs, the LEDs for the phases that lost voltage turn off and the LS option begins timing.
Note: The TIE mode will not initiate any loss of voltage timing if
both sources are lost. If one source is available, while the TIE mode is timing on loss of voltage, and the available source also loses voltage, the TIE will reset the loss of voltage time to its original value.
If voltage is restored before the voltage transfer time delay elapses, the LEDs for the phases with restored voltage illuminate and the LS timer resets.
If voltage is not restored before the Voltage Transfer time delay relay elapses, the LEDs remain off even if voltage returns to a particular phase. This identifies the phase that caused the LS to operate.
Activating the LS RESET one-touch function key resets
the LS function and illuminates these LEDs (if voltage is present).
FREQUENCY TRIP: Indicates the recloser tripped due to
an under or over frequency condition.
VOLTAGE TRIP: Indicates the recloser tripped due to an under or over voltage condition.
X PHASE VOLTAGE, Y PHASE VOLTAGE, Z PHASE VOLTAGE: These red memory LEDs indicate Source II (load) voltage is present on X, Y, or Z phase(s). These LEDs are
controlled by the Voltage Controls settings in the Loop Scheme Settings dialog box.
If LS is enabled, at the moment loss of voltage occurs, the LEDs for the phases that have lost voltage turn off and the LS option begins timing.
Note: The TIE mode will not initiate any loss of voltage timing if
both sources are lost. If one source is available, while the TIE mode is timing on loss of voltage, and the available source also loses voltage, the TIE will reset the loss of voltage time to its original value.
If voltage is restored before the voltage transfer time delay elapses, the LEDs for the phases with restored voltage illuminate and the LS timer resets.
If voltage is not restored before the Voltage Transfer time delay relay elapses, the LEDs remain off even if voltage returns to a particular phase. This identifies the phase that caused the LS to operate.
Activating the LS RESET one-touch function key resets the
LS function and illuminates these LEDs (if voltage is present).
INDICATOR 7, INDICATOR 8: Customizable LEDs that are used with functions programmed through the Idea Workbench. The LED indicators do not have active default values. The LEDs are illuminated when the status config­ured via the Idea Workbench is present.
Operating Panel
RS-232 Configuration Data Port
The RS-232 connector (shown in Figure 4) on the front
operating panel allows direct connection to a personal computer without any special cables or connectors. This port is used only for configuring the control with ProView application software. All settings, metering, events, and oscillography data are available from this port. The port is
Data Communication Equipment (DCE) wired for direct
connection to a personal computer.
A 9-pin RS-232 cable (Catalog Number KME5-66) to
connect from the PC to the RS-232 data port is available as an accessory.
9
Form 6-LS Pole Mount Recloser Control Installation and Operation Instructions
TRIP CLOSE
HOT LINE TAG
ON
CLOSE CIRCUIT DISABLE
F6 RECLOSER CONTROL
(LOCKOUT)
HOT LINE TAG ON/OFF Toggle Switch and LED Indicator
WARNING: Hazardous voltage. Do not use Hot
Line Tag as a substitute for a visible disconnect. Always establish a visible disconnect prior to performing any work requiring a de-energized line. Failure to comply may cause death, severe personal injury, or equipment damage. T276.0
Hot Line Tag is provided for live-line work applications. All closing operations are disabled when the Hot Line Tag feature is activated.
IMPORTANT: Hot Line Tag activation does not cause the recloser to trip open. It only prevents the recloser
Figure 7. TRIP (Lockout) pushbutton; CLOSE pushbutton; Hot Line Tag switch and Hot Line Tag red indicator LEDs.
from closing.
CLOSE Pushbutton
IMPORTANT: Hot Line Tag is intended solely for live-line work applications, such as maintenance, repairs or improvements to the distribution system, that occur while the line remains energized.
Hot Line Tag prevents all closing attempts from the control and shifts protection to one trip-to-lockout on the composite curve of the Hot Line Tag definite time and the TCC1 curve (whichever is faster). Hot Line Tag takes precedence over Cold Load Pickup, Non-Reclosing, and Fast Trips Disabled.
Hot Line Tag is activated from either the operator panel toggle switch, serial communications, or a discrete SCADA function. All sources must be off to de-activate Hot Line Tag.
To activate the function from the operator panel, flip toggle switch up to the ON position. See Figure 7. The LED indicator illuminates when the function is active.
The Hot Line Tag function may only be reset by the source which initiates it. For example, if Hot Line Tag is activated at the operator panel, the reset function is only possible at the operator panel, and not via SCADA command.
When pressed, the CLOSE pushbutton (Figure 7) returns
the control to the initial or home sequence position, closing the recloser. The control is ready for the start of a new trip/ close sequence.
Note: The Close Malfunction alarm must be reset before
Closing will be allowed.
Note: Pressing the CLOSE pushbutton from the Lockout
position initiates Cold Load Pickup (CLPU) protection, if
the feature is enabled.
The user does have the ability to block COLD LOAD
PICKUP through the LCD menu or by configuring one of the Option one-touch function keys via the Idea Workbench feature in ProView.
If the recloser is closed, pushing and holding the CLOSE
pushbutton does not activate the Cold Load Pickup feature. See Cold Load Pickup in the Control Features section of this manual.
IMPORTANT: If the CLOSE button is pressed after the Close Circuit Disable fuse is removed, do not reinstall the
fuse until after the ALARM LED illuminates (within approximately five seconds) to indicate CLOSE
MALFUNCTION. Re-installing the Close Circuit Disable fuse prior to the CLOSE MALFUNCTION ALARM indication will cause the control to close the recloser.
IMPORTANT: If the power save feature is enabled
(default), and more than ten minutes elapses since the
last panel operation, all the LEDs, except HOT LINE TAG
(if active), will turn off.
TRIP (Lockout) Pushbutton
The TRIP pushbutton (Figure 7) provides front-panel access to trip (lockout) the recloser. When pressed, the
TRIP pushbutton opens the recloser and locks out the control.
Note: In the event of main microprocessor failure, the trip circuit
10
can operate independent of the main microprocessor.
CLOSE CIRCUIT DISABLE
Close Circuit Disable (Figure 7) is a removable fuse that,
when removed from the front operating panel, disables the close circuit from the control to the recloser. Removing the fuse from the control disables all electrical closing of the recloser and provides a physical disconnect to the recloser closing circuit. As a result, the control cannot perform a close operation. This disconnect overrides all close functions and makes a remote or manual close operation impossible.
Note: When the Close Circuit Disable fuse is removed, the trip
circuit remains active and will trip per the programmed time current curve for a faulted condition.
S280-70-10
One-Touch Function Keys
Quick access to frequently operated Form 6-LS control features is provided with nine function key pushbuttons on the control operator panel.
The Form 6-LS control operator panel one-touch function keys are illustrated in Figure 8.
GND TRIP BLOCKED
LS RESET
OPTION#1 OPTION#2 OPTION#3
NON
RECLOSING
SOURCE I ENABLED
SUPERVISORY
OFF
SOURCE II
ENABLED
Figure 8. Form 6-LS control operator panel one-touch function keys.
Red LEDs located on each function key indicate the status of the function, regardless of local or remote activation. For example, if Ground Trip Blocked is activated from a SCADA signal, the red indicator will illuminate even though it was not activated from the operator panel.
Operator panel function key activation or de-activation
requires the operator to first press the CHANGE key to enter the CHANGE mode. A function must then be selected or de-selected within ten seconds to activate or de-activate the function. Once selected, the control returns to normal operation until prompted for another change request. This prevents accidental changing of functions of features.
Note: Only one function can be changed per each CHANGE
mode activation.
GND TRIP BLOCKED
The Ground Trip Blocked function blocks all ground sens­ing in the control for the active profile. This red indicator is illuminated when Ground Trip Block is activated from the
serial port, I/O, the interface software, or locally (via the front panel) causing the control to block all ground sensing.
NON RECLOSING
The Non-reclosing mode disables any automatic reclosing operations. The red indicator is illuminated when the control is operating in a non-reclosing mode. Non-reclosing does not alter the active TCC. Activation is possible from
the SCADA port, I/O, the interface software, or locally (via the front panel).
SUPERVISORY OFF
When the SUPERVISORY OFF red indicator is illuminated,
supervisory commands are blocked. Supervisory functions through the back panel serial communication ports and the discrete I/O are blocked. Serial communications through the front panel RS-232 port remain active independent of
the status of the SUPERVISORY OFF switch. Activation of
this function key is restricted to the operator panel and is accomplished by pressing the CHANGE key and then
pressing the SUPERVISORY OFF key. Operational data
and metering information are available while the control is
in the SUPERVISORY OFF position. The TRIP and CLOSE
pushbuttons and Hot Line Tag are active independent of
the SUPERVISORY OFF function.
LS RESET: When the LS RESET red indicator is illuminated, the LS function has been reset and the control is ready to respond to the next loss of voltage occurrence. Activation
is possible from the SCADA port, I/O or locally (via the front panel). This LED cannot be de-selected. It will only turn off
when an LS action occurs.
SOURCE I ENABLED: When the SOURCE I ENABLED red indicator is illuminated, the control is in LS mode and
responding to voltage conditions on Source I (Source side Phases A, B, and C). Activation/de-activation is possible
from the SCADA port, I/O, the interface software, or locally
(via the front panel).
SOURCE II ENABLED: When the SOURCE II ENABLED red indicator is illuminated, the control is in Tie mode and
responding to voltage conditions on Source II (Load side Phases X, Y, and Z). Activation/de-activation is possible
from the SCADA port, I/O, the interface software, or locally
(via the front panel).
Note: When the control is in Sectionalizing mode, the SOURCE
II ENABLED function key may or may not be illuminated
(depending on the LS Enable SII setting in the Loop Scheme Settings Dialog box). It is not responding to
Source II voltage.
OPTION #1, OPTION #2, AND OPTION #3
The OPTION #1, OPTION #2, and OPTION #3 function keys must be programmed via the ProView Idea Workbench software.
The OPTION LEDs are illuminated when the options configured via the Idea Workbench are selected. Refer to
Service Information S280-70-4 (ProView 4.X.X) or S280­70-21(ProView5.X.X)Form6ControlProgrammingGuide
for additional information.
These OPTION keys provide a momentary signal. For instance, these keys can be programmed to toggle control status, protective functions, or a momentary input pulse.
The OPTION #1, OPTION #2, and OPTION #3 function keys are intentionally not defaulted to any function. The functions are assigned to each OPTION key via the Idea Workbench application.
11
Form 6-LS Pole Mount Recloser Control Installation and Operation Instructions
Control Features
The Form 6-LS recloser control offers numerous standard features and accessories that allow the user the utmost flexibility applying the recloser control.
Control Security
The Form 6-LS control has multiple customer-programmable security codes to limit control programming and viewing function access to authorized personnel. The front panel
Man-Machine Interface (MMI) includes a user-selected
security code to access the settings. Plus, the ProView interface software has it’s own security levels for multiple­user access.
Refer to ServiceInformationS280-70-4(ProView4.X.X)or
S280-70-21(ProView5.X.X)Form6ControlProgramming Guide for additional information.
Protection Profiles
Four protection profiles capable of fully specifying control operation are standard in the control. Each protection pro­file includes the following as a minimum:
• Overcurrent Protection
• Over/Undervoltage Protection
• Over/Underfrequency Protection
• Directional Protection
• Hot Line Tag Functionality
• Sync Check
• Sensitive Earth Fault Protection
• Sequence Coordination
• Operation Settings
Time Current Curves
Time-current curves are available for numerous functions, including fast and delayed operations for phase, ground, and negative sequence protection. Each time-current is selected from a defined fifty curves which can be further customized by the user. The time-current curves are also selected from a graphical TCC Editor II to visualize any modifications prior to configuring the control.
The time-current curves include the following modifications for phase, ground, and negative sequence protection:
• Time Multiplier with a range of 0.1 to 25 in .1 increments.
• Time Adder with a range of 0 to 30 seconds in .01
second increments.
• Minimum Response Time with a range of 0.01 to 1
seconds in .001 second increments.
• High Current Trip multiplier with a range of 1 to 32
multipliers in increments of 0.1.
• High Current Trip Time Delay with a range of 0.01 to
.150 second in .001 second increments.
• Time Dial Reset co-efficient with a range of .1 to 30
seconds in 1 second increments.
Sequence Coordination
Sequence Coordination eliminates nuisance tripping through trip coordination. It allows the control to step through selected operations in the operating sequence without tripping. The number of Sequence Coordination advances is programmable from one to three operations to provide trip coordination with a downline recloser. This feature is independently selectable for each protection profile.
Cold Load Pickup
The control includes a Cold Load Pickup feature to prevent the control from tripping while energizing non-fault system loads. This feature has independently programmable minimum trip value time-current curve, reclose interval, and number of independent operations to lockout for each protection profile. Cold Load Pickup also includes TCC Multipliers, TCC Adders, Minimum Response Time, Time Dial Reset, and High Current Lockout. Also, direct values, not multiples of minimum trip, are provided for high current lockout.
Fast Trips Disabled
The control includes a Fast Trips Disabled feature to modify protection, so that all trip operations use the programmed TCC2. This feature is independently selectable for each protection profile. All trip operations will time on TCC2. Typically, TCC1 is fast and TCC2 is delayed. So, as an example, the control will change it’s sequence from 2 fast and 2 delayed operations to 2 operations on TCC2 when Fast Trips Disabled is active.
High Current Lockout
The High Current Lockout feature will automatically lockout the control on the selected operation when current exceeds a programmable level. The active trip numbers for the lockout is selectable for phase, ground, and negative sequence. This feature is independently selectable for each protection profile.
Sensitive Ground/Earth Fault Operation
The control has a Sensitive Ground/Earth Fault Trip feature that provides tripping of the recloser after a programmable, definite time for ground currents below normal ground minimum trip levels. The feature has programmable operations to lockout and reclose intervals independent of the ground settings. This feature is independently selectable for each protection profile.
Thermostatically Controlled Heater
The control has a standard 15 Watt thermostatically
controlled heater (ON at 70°F on falling temperature, OFF at 85°F on rising temperature) for humidity control and
voltage input independent. The heater is powered from the power supply board.
12
S280-70-10
Metering
The control provides instantaneous and/or demand metering with programmable integration intervals for the following functions:
• Real and reactive power for each phase and total,
including directional, on an individual phase basis.
• Demand currents on a per phase basis.
• Instantaneous currents, including ground current.
• Instantaneous voltage on a per phase basis.
• Instantaneous frequency.
• Positive, negative, and zero sequence voltages.
• Instantaneous power factor on a per phase basis.
• Metering settings to include demand interval, and
alarm thresholds for current, single-phase kW, three­phase kW, single-phase kvar, and three-phase kvar.
Event Recorder
The Form 6-LS control contains capabilities to perform Sequence of Events time-stamping for up to 33 standard event types. Factory-defined event types include:
• Overcurrent Protection Trip
• External Trip
• Non-Reclose Trip
• External Close
• Lockout
• Reset
Sixteen additional inputs can be user-defined through the Idea Workbench.
Note: Seven of these additional inputs are already factory-
The Event Recorder maintains a minimum of 90 event records. The last 25 events are viewable on the front panel LCD display. Refer to Service Information S280-70-4
(ProView 4.X.X) or S280-70-21 (ProView 5.X.X) Form 6 ControlProgrammingGuide for additional information.
defined (default) for the Form 6-LS control.
Recloser Duty Monitor
The Form 6 recloser control software is equipped with a Recloser Interrupting Duty Monitor. The Duty Monitor accumulates the summation of I currents on each interrupter. This feature permits programmable entries to preset the duty of an existing recloser. The recloser duty monitor displays interrupting duty in percent of duty used. If the duty cycle monitor exceeds 100%, the recloser should be examined for maintenance.
1.5
for all interrupted
Discrete SCADA Communications
The control provides five configurable output status contacts and three configurable input control contacts as standard. Each status contact is configurable using graphical interface software to combine status functionality along with Boolean algebra. Default output status contacts are: Lockout, Recloser Open, Recloser Closed, Ground Trip Block, and Hot Line Tag. One output status contact is
a solid state output (SS1) with a pickup time no longer than
two milliseconds.
The control also provides a minimum of three configurable input control contacts. Each control contact is configurable using a graphical interface software. Contacts accept a
whetting voltage range of 12–250 VDC, 120/240 VAC.
Each digital input is configured for either a momentary, maintained, or maintained with precedence contact. Default input control contacts are: Supervisory Trip and Lockout, Supervisory Close, and Remote Trip and Lockout.
A Discrete Interface Board is also available as an acces­sory to provide an additional eight output status contacts and eight input control contacts. The expansion I/O board is completely user-configurable.
TCC Editor II
Coordination and actual time current modifications are available with a graphic interactive TCC Editor or similar graphical software.
The TCC Editor II includes a complete database of stan-
dard recloser industry time current curves (TCC), both
ANSI and IEC types, along with the ability to customize the TCCs with multipliers, constant time adders, or minimum response time adders. Also, the user is able to derive their own specific TCC through data point entry. Each modified time current curve can be identified with a user-customized name and is selectable for configuring the control. The grid and format for presenting the TCCs has a user-adjustable scale, including the option of presenting multiple TCCs in various user-configured colors.
Oscillography
Oscillography is provided to present current and voltage waveforms, along with protection element and recloser response status changes. Filtered and unfiltered data are provided for viewing.
The recorded values are super-imposed on the protection scheme, and the state or value at any point in the scheme is displayed. The user has the capability to move through the event and watch the response of every function. All analog signals, digital inputs, and contact outputs are monitored. Analog oscillography is displayed at 16 sam­ples per cycle.
Oscillographic data is recorded to analyze multiple events during a permanent fault or other event type. The oscillo­graphic data shows two cycles before the trigger point and
eight cycles after the trigger point (default).
Note: The configuration settings are programmable.
Oscillography automatically initiates trigger points for the following functions:
• Above Minimum Trip for Phase, Ground, and Sensitive
Ground Fault
• Single- and Three-Phase Overvoltage
• Single- and Three-Phase Undervoltage
• Over- and Underfrequency
• Trip Signal Issued
• Close Signal Issued
13
Form 6-LS Pole Mount Recloser Control Installation and Operation Instructions
Removable Inserts
Removable inserts are included with the control design for customization of specific protection requirements. Inserts are available for the status indicator LEDs, the operator panel function keys, and the analysis keys. The removable inserts are designed for use without adhesives, labelmakers, or temporary labels. Refer to Using Removable Inserts in this manual for more information.
An electronic label template is included on the ProView application software CD and can be accessed through the following default address:
C:\Program Files\Cooper\ProviewXX\Form6\Form 6 Inserts.doc
Idea Workbench
The Idea Workbench provides access to various inputs, intermediate variables, and internal Form 6 alarms, status, and targets to allow user-customization of the Form 6 recloser control to meet specific and unique applications. The Idea Workbench also gives the user the ability to perform logical functions with these variables by using a simple graphical user interface. Refer to ServiceInformation
S280-70-4(ProView4.X.X)orS280-70-21(ProView5.X.X) Form 6 Control Programming Guide for additional
information.
Over/Underfrequency Protection
The control includes two-stage operation for both underfrequency and overfrequency protection. A fixed time delay ranging from 0 to 100 seconds in .001 second increments is available for both over and underfrequency. A frequency restoration function, enabled or disabled by the user, is provided to allow the recloser to automatically close should frequency return to within configured settings for a user-settable time. Over/Underfrequency Protection is included as part of each protection profile.
Over/Undervoltage Protection
The control includes single-phase and three-phase under voltage tripping. The control also includes three-phase overvoltage tripping. Both over and undervoltage functions include a single-phase and three-phase pick-up setting; a single-phase and three-phase time delay setting ranging from 0 to 100 seconds.
Directional
Directional functionality is included to maintain system coordination from multiple sources, as well as circuit reconfiguration for each profile. Directional applies to phase, ground, and negative sequence protection, selected independently. A maximum torque angle has a range of
0–90 degrees.
Data Profiler
A fully-configurable data profiler is available which allows the user to collect information by sampling data at selectable intervals. These time-stamped values can then be viewed to determine weekly load profiles, daily harmonic disturbances or hourly voltage fluctuations. The number of days of information the data profiler can provide depends upon configuration parameters. Refer to ServiceInformation
14
S280-70-4(ProView4.X.X)orS280-70-21(ProView5.X.X) Form 6 Control Programming Guide for additional
information.
Fault Location
The control includes an impedance-based fault locator based upon the Takagi algorithm1. Load-compensated impedance calculation is used for calculating the distance. Positive and zero sequence is configured in ohms, and the fault locator line length is configured in kilometers/miles.
1
T. Takagi, Y. Yamakoshi, J. Baba, K. Uemura, T. Sakaguchi, "A New
Algorithm of an Accurate Fault Location for EHV/UHV Transmission Lines: Part I - Fourier Transformation Method", IEEE Trans. on PAS, Vol. PAS- 100, No. 3, March 1981, pp 1316-1323.
Sync Check
Sync Check is a permissive system used to qualify any close signal to the mechanism when enabled via the sync check settings. Sync check allows for closing for any combination of dead/live bus/line, and to perform anticipatory closing for a live bus/live line condition by calculating slip and anticipating the mechanism closing delay. In addition to the anticipatory close calculation, the sync check system performs verification of line and bus voltage magnitudes and frequencies to determine that they are within pre-determined ranges, and that the angular difference between the two systems is also within the pre­determined range. For a live/live close, where there is no slip between the systems, the sync check system allows permissive closing after the two systems are within frequency and voltage limits, and the angular difference between the systems has been within the allowable limits for a pre-determined time.
Sync Check functionality includes the following applications: Hot Line/Hot Bus Closing; Dead Line/Hot Bus Closing; Hot Line/Dead Bus Closing; and Dead Line/Dead Bus Closing.
Sync Check Parameters include the following configurable settings: Voltage Angle; Mechanism Operating Delay; Static Angle Delay; Dead Threshold; Live Threshold; Positive Sequence Dead Threshold; Upper Voltage Limit; Lower Voltage Limit; Lower Frequency Limit; Upper Frequency Limit; and Fail to Close Timer.
Manual Close Delay
Manual Close Delay provides a delay from the time that the manual CLOSE button is pushed to the time the manual close operation is performed.
The delay is programmable from 0 to 60 seconds in 1 second increments. A programmed delay value can be overridden for immediate closing by pressing the CLOSE button a second time.
An active Manual Close Delay can be canceled by pressing the TRIP/LOCKOUT button.
The default setting has the feature disabled (0 seconds). A
countdown on the front panel LCD screen indicates Manual Close Delay is active.
S280-70-10
TB1
12357911 13 15 17 19
4681012141618
CI1
CI2CI3 SS1CO1
CO2CO3
CO4
CI4
CI1CI2 CI3SS1 CO1CO2 CO3CO4
TB3
13579111315171921
CI5CI6 CI7CI8 CI9CI10CI11CO5 CO6
TB4
2
4681012141618
20
CI4CI5 CI6CI7 CI8CI9 CI10 CI11 CO5
CO6
1357911 13
CO7CO8
CO9CO10CO11
CO12
2
4681012
CO7CO8 CO9CO10CO11CO12
J1-RS-232
IRIG-B
RS-485
RS-232 DTE
Discrete Interface
Board (Accessory)
AC Power Fuse
RS-232 Serial Communication Port
Fiber Optic port, "ST" Type Connector (optional), Ethernet Port, "MT-RJ" Fiber RJ45 Connector (optional)
Power Supply Board
AC Customer Connection Terminal Block TB7
Grounding Terminal, One
External & One Internal
(#14 to #4 Stranded)
1
65432
Power Supply LED
Power Connections
1
43
2
7
1211
109
8
Voltage Sensing
Customer Connection
Terminal Block TB8
120/240 Vac
Selector Switch
Battery Connector (2-position)
RS-485 Serial Communication Port (optional)
TB9
+
28 VDC
WHETTING VOLTAGE
P1
P2
P3
P4
VOLTAGE SENSING
53VDC CONTROL CABLE 28 VAC
123
45
123
45
23
22
21
20
19
11
10987
18
17
16
15
14
654
32
13
1
24
12
123
4
5
3
1
3
1
3
4
2
4
24
1
2
C + –
IRIG-B Time Sync Connector
Communications
Communication Ports
The Form 6 control has two back panel communication ports and a front panel configuration data port.
The front panel configuration data port is described in the Operating Panel section of this manual.
There is one standard 9-pin RS-232 and one optional
communication port (RS-485, serial fiber, Ethernet wire or fiber or both) on the back operator panel, as well as a stan-
dard IRIG-B port for user time-syncing. See Figure 9.
Communication Protocols
Four communication protocols are available for the Form 6 control:
• Modbus
• DNP3
• 2179
• IEC870-5-101
One communication protocol can be selected for either the back panel RS-232 or the optional communication port.
All four protocols are selected and configured by the user with the ProView Communications Workbench application software.
Ethernet Communications
• ProView over TCP/IP
• DNP3 over TCP/IP
Ethernet connection allows for network application of the Form 6 control for both DNP3 and ProView protocols. In addition, the front panel data port can simultaneously communicate ProView to the PC.
Ethernet configuration is accomplished via ProView inter­face software. Refer to Service Information S280-70-4
(ProView 4.X.X) or S280-70-21 (ProView 5.X.X) Form 6 Programming Guide , Section 4: Schemes,
Communicating with the Form 6 Control, for Ethernet Configuration information.
When a communication protocol is selected for the option-
al communication boards (serial fiber or the RS-485 serial port), the RS-232 serial port is defaulted to ProView inter-
face software protocol.
DNP3 is factory-defaulted to the RS-232 port.
When a communication protocol is selected for the RS-232
serial port, the optional RS-485 or serial fiber optic board
is not active.
The RS-485 or fiber optic serial ports do not support
ProView interface software protocol.
The user can simultaneously communicate to the Form 6 control using both the front panel data port and the appro-
priate back panel serial communication port (provided the
back panel RS-232 port or the Ethernet optional commu-
nications board is not configured to be ProView protocol).
Control Information
Control information includes firmware identification by cat­alog number and name, date code, and ProView release number. Control information is available through the
Settings menu on the front panel (Figure 4).
Control Back Panel
The control back panel is easily accessible through the
back door of the control cabinet (Figure 2) with readily identifiable serial ports and connections (Figure 9).
Figure 9. Form 6-LS pole mount recloser control back panel terminal block and communication port identification.
15
Form 6-LS Pole Mount Recloser Control Installation and Operation Instructions
INSTALLATION PROCEDURE
Initial Programming Prior to Installation
CAUTION: Equipment misoperation. Do not
connect this control to an energized recloser until
all control settings have been properly programmed and verified. Refer to the programming information for this control. Failure to comply can result in control and recloser misoperation, equipment damage, and per­sonal injury. G110.3
CAUTION: Equipment Misoperation. Check minimum trip values prior to changing an alternate profile. Failure to do so may cause misoperation of the recloser under load conditions. T280.1
IMPORTANT: Program all protection profiles. Unused alternate profiles should be programmed with the same settings as one of the applicable profiles. Default settings on unused alternate profiles can cause unnecessary outages if they are below normal system requirements.
The control must be programmed with all necessary operating settings, all alternate profiles, and parameters prior to operation with an energized recloser.
Note: Initial programming of the control is the responsibility of a
qualified technician or engineer familiar with control functions and programming parameters required for the specific recloser installation.
The control must be programmed with the Form 6 ProView interface software. Refer to ServiceInformationS280-70-4
(ProView 4.X.X) or S280-70-21 (ProView 5.X.X) Form 6 Microprocessor-Based Recloser Control Programming Guidefor additional information.
Note: The Pole Mounted Control checkbox in the ProView
System Configuration screen must be selected for all Form 6 pole mount controls. This includes both pole and substation applications.
IMPORTANT: Form 6-LS control users must activate the loop scheme default settings in the ProView application software Idea Workbench:
1. Click on LOAD IDEA WB STRUCTURE.
2. Select WBI-Form6-F6Default-LS.sch and click on
Open.
3. Click on READ IDEA WB SETTINGS FROM DISK.
4. Select WBI_Form6_Settings_F6 Default-LS.txt and
click on Open.
5. Enable the LS functionality by selecting the LS
Enable checkbox in the Loop Scheme Settings Dialog box located in the Idea Workbench Optional Loop Scheme Workbench.
Control / Recloser Compatibility
The Form 6-LS recloser control is adaptable to the following Kyle reclosers:
WE*, WVE27, WVE38X, VWE, VWVE27, VWVE38X, VSA12, VSA16, VSA20, VSA12B, VSA20A, VS012, VS016, NOVA15**, and NOVA27**.
* This control is not compatible with Form 1 Type WE reclosers
below s/n 300 and RE reclosers below s/n 400.
** Control-powered NOVA reclosers that are manufactured after
September 2004 require a Voltage Trip/Close (VTC) interface
for tripping and closing. This VTC requirement applies to three­phase control-powered NOVA reclosers with a Type A or a Type D mechanism and Form 5, Form 5 LS/UDP, Form 6, and Form 6 LS controls with the control-powered interface. These reclosers and controls are equipped with 19-pin control cable receptacles. Refer to RECLOSER VTC INTERFACE and CONTROL VTC INTERFACE sections of this manual for additional information.
Reclosers manufactured prior to June 1989 are equipped
with Type A bushing current transformers. These reclosers were designed for use with Form 2, Form 3, and Form 3A controls. Because the Form 6 recloser control is designed for use with reclosers equipped with Type B current­sensing Transformers, reclosers retrofitted with Form 6 recloser controls should be retrofitted with Type B current transformers. All reclosers manufactured since 1989 are
equipped with Type B (1000:1, 1000/500:1, or 2000:1)
sensing CTs.
Reclosers equipped with Type B sensing CTs are compatible with all Cooper Power Systems recloser
controls (Form 2, Form 3, Form 3A, Form 4A, Form 4C, FXA, FXB Form 5, and Form 6 recloser controls), and are
identified with the following label prominently displayed on the recloser sleet hood or the front of the operator cabinet:
NOTICE
RECLOSER IS EQUIPPED WITH TYPE B
SENSING CTs.
RECLOSER DOES NOT HAVE A BATTERY
CHARGER.
The Form 6 recloser control can be used with the old-style Type A CTs; however, the event recorder and duty cycle monitor will have limited accuracy for currents above 5000 Amps.
Retrofit kits with the new Type B sensing CTs are available to upgrade existing families of reclosers for operation with Form 6 recloser controls. For additional information, contact your Cooper Power Systems representative.
For identification, Table 1 lists the serial number breaks between old-style Type A and the new-style Type B sensing CTs. Below this serial number, the recloser is equipped with the Type A CTs.
Note: For reclosers shipped prior to June 1989 and not listed
below, please contact your Cooper Power Systems representative with the recloser type and serial number for verification of type A or B bushing current transformers.
16
S280-70-10
TABLE 1 Serial Number Break for Reclosers with Type A Sensing CTs
Recloser Below Serial Number
RXE 5831
RVE 5894
WE 11199 WVE 3695 VWE 7199 VWVE27 7208
VWVE38 1204
All VSA reclosers are equipped with Type A Sensing CTs. All VSML reclosers are equipped with Type A Sensing CTs. All VSA12, VSA12B, VSA16, VSA20, VSA20A, and VSA20B
reclosers are equipped with Type B Sensing CTs. All VWVE38X and VWE38X reclosers are equipped with Type B
Sensing CTs.
TABLE 2 Duty Cycle Factor
Interrupting 100% Duty Recloser Rating Cycle Type (rms sym Amps) Factor*
RXE, RVE 6,000 97
WE 12,000 @ 4.8 kV 257 WE 10,000 @ 14.4 kV 196
VWE
VWVE27 12,000 1045
VWVE38X
WVE27 8,000 140
WVE38X 8,000 140
VSA12 12,000 1045
VSA16 16,000 1608 VSA20
VSA20A 20,000 2248
VSA20B
VSO12 12,000 1045
VSO16 16,000 1608 Auxiliary-Powered
NOVA 12,500 1111 Control-Powered
NOVA 12,500 1111
*Duty Cycle Factor is Value x 105.
TABLE 3 Available Form 6 Control Cable Lengths for Kyle Reclosers
Duty Cycle Monitor
The Duty Cycle Monitor provides the following duty cycle information:
• Measures and records duty for each individual phase in
non-volatile memory.
• The recloser duty is measured and stored on the basis
of Current
1.5
xNumberofOperationsforEachPhase
(ANSI C37.61).
• Readout is based on a percentage of total duty cycle
for each phase.
• Duty record can be adjusted or reset if recloser is
changed-out, serviced, etc.
Using Table 2, select the appropriate recloser interrupting duty cycle factor and enter that value via the ProView inter­face software.
Control Cable
WARNING: Hazardous voltage. Recloser and
control must be solidly grounded. Follow all approved procedures and safety practices when grounding this equipment. Improper grounding can result in contact with high voltage, which will cause death or severe personal injury. G115.1
The control cable is fabricated with connectors which mate with the female receptacle of the recloser on one end, and the male receptacle of the control or junction box on the other end.
Note: The control cable must be supported along its length to
Limits on control cable lengths are determined by the recloser type and the distance between the control and recloser: See Table 3 for available Form 6 recloser control Cable Lengths for Kyle reclosers.
prevent repeated movement due to wind or other outside forces which can damage the cable.
IMPORTANT: All external inputs to the Form 6 recloser control must be routed within 8 inches of their corresponding ground. During a surge, a potential of approximately 1.5 kV per foot can develop in the conductors. Differences between conductor and ground path lengths can add additional stress to the control components in the event of a power surge.
Recloser Type Gauge Length (Meters) Length (Feet)
WE, WVE27, WVE38X, VWE, VWVE27, VWVE38X,
Auxiliary-Powered NOVA15, Auxiliary-Powered NOVA27 18 24.1 (maximum) 79 (maximum) 16 24.4 to 38 80 to 125 14 38.4 to 61 126 to 200
VSA12, VSA12B, VSA16, VSA20,
VSA20A, VSO12, VSO16 18 3.4 to 6 11 to 20 16 6.4 to 10.7 21 to 35 14 11 to 15.25 36 to 50
Control-Powered NOVA15, Control-Powered NOVA27 16 3.4 to 38 11 to 125
17
Form 6-LS Pole Mount Recloser Control Installation and Operation Instructions
Mounting the Control
WARNING: This equipment is not intended to
protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply may result in death, severe personal injury and equipment damage. G102.1
CAUTION: Follow all locally approved safety practices when lifting and mounting the equipment. Use the lifting lugs provided. Lift the unit smoothly and do not allow the unit to shift. Improper lifting can result in equipment damage. G106.2
Mount the Form 6-LS recloser control in a convenient, accessible location. Mounting dimensions are provided in Figure 10.
Note: Unless otherwise specified, dimensions shown in mm
(inches).
A hole and keyway in the control mounting bracket
accommodates a 15.9 mm (5/8”) bolt.
Locking the Control
The handles on the Form 6 control cabinet are able to accept a padlock to prevent unauthorized access. For cabinets with the quarter-turn latch, the top handle has two locking holes provided depending on the diameter of the lock shackle being used. Refer to Figure 10.
• Use the smaller hole for shackle diameters of .177-
295”.
• Use the larger hole for shackle diameters of .295-.394”.
Note: DO NOT use a smaller shackle (.177-.295) in the
larger diameter hole as it will NOT LOCK the cabinet.
Grounding the Control
WARNING: Hazardous voltage. Recloser and
control must be solidly grounded. Follow all locally approved procedures and safety practices when grounding this equipment. Improper grounding can result in contact with high voltage, which will cause death or severe personal injury. G115.1
The control cabinet must be grounded. A grounding connector on the underside of the cabinet will accommodate
No. 14 solid through No. 4 stranded conductors.
Suggested methods for grounding the control and recloser are shown in Figures 11 and 12.
Figure 11 illustrates grounding methods for 4-wire multi-
grounded systems with local supply voltage transformer.
Figure 12 illustrates grounding methods for 4-wire multi-
grounded systems with remote supply voltage transformer.
For effective surge protection, all control and power conductors for the Form 6 control must be routed parallel to a corresponding ground path. For example, the AC power supply for the control should be parallel to and equal in length to the transformer ground path. The control cable should be parallel to and routed close to the recloser ground path.
18
Front View
710
(28.0)
310
(12.25)
Vent
Bottom View
Vent
1.44 Dia. Hole for Voltage Input Connection (Caplug Installed)
Mounting Angle
Control Cable Receptacle (14-pin or 19-pin)
1.44 Dia. Hole (Caplug Installed)
1.44 Dia. Hole
(Caplug Installed)
67 (2.75)
38 (1.5)
67 (2.75)
79 (3.25)
RS-232 Connection Port
29
(1.25)
CONTROL POWER
CONTROL OK
CONTROL LOCKOUT RECLOSER OPEN
RECLOSER CLOSED
A PHASE FAULT
B PHASE FAULT
C PHASE FAULT GROUND FAULT
SENSITIVE GND
ALARM
ABOVE MIN TRIP TIE SECTIONALIZER
LS DISABLED
A PHASE VOLTAGE
B PHASE VOLTAGE C PHASE VOLTAGE FREQUENCY TRIP
VOLTAGE TRIP
METERING
RESET TARGETS
EVENTS
LAMP TEST
MENU
ENTER
+
SETTINGS
OPER COUNTER
ALARMS
CHANGE
F1 F2 F3 F4
TRIP CLOSE
HOT LINE TAG
ON
GND TRIP BLOCKED
NON
RECLOSING
SUPERVISORY
OFF
LS RESET
SOURCE I ENABLED
SOURCE II ENABLED
F6 Recloser Control
RS-232 DATA PORT
OPTION #1
OPTION #2
OPTION #3
(LOCKOUT)
X PHASE VOLTAGE
Y PHASE VOLTAGE Z PHASE VOLTAGE INDICATOR 7
INDICATOR 8
CLOSE CIRCUIT
DISABLE
170 (6.75)
355 (14.0)
400 (15.75)
16 (.63) Dia. Mounting Holes (2)
Grounding Terminal #14 To #4 Stranded
665
(26.25)
Right Side View
Lifting Lugs
SHACKLE DIAMETER .177-295"
SHACKLE DIAMETER .295-.394"
S280-70-10
Note: DO NOT use a smaller shackle (.177-
.295) in the larger diameter hole as it
will NOT LOCK the cabinet.
Figure 10. Form 6-LS recloser control weight, dimensions, and pad-lock shackle diameters.
CONTROL WEIGHT 34 kg (75 lbs)
19
Form 6-LS Pole Mount Recloser Control Installation and Operation Instructions
Surge Arrester
Recloser Head Ground
Surge
Arrester
Transformer
Surge
A
rrester
Arrester Ground
Recloser
Pole
Supply
Voltage
Pole
Ground
Form 6 Control
Customer Ground Connection At External Lug
NEU
AC
GND
NEU
AC
Input Terminal Block
Control
Cable
AC
NEUTRAL
Form 6 Control
Supply Voltage
Transformer
ELECTRICAL CONNECTIONS
Line to Neutral connected transformer
Input Terminal Block
External Ground Lug
Grounding with a Local Supply Voltage Transformer; 4-Wire Multi-Grounded
Installation of a Form 6-LS pole mount recloser control with a local supply voltage transformer must include the following:
• Protection of the recloser bushings and the supplying
transformer with lightning arresters.
• Grounding of the recloser head and tank.
• Grounding of the transformer tank.
• Grounding of the control cabinet.
• Grounding of the SCADA equipment.
IMPORTANT: All external inputs to the Form 6 recloser control must be routed within 8 inches of their corresponding ground. During a surge, a potential of approximately 1.5 kV per foot can develop in the conductors. Differences between conductor and ground path lengths can add additional stress to the control components in the event of a power surge.
4-Wire Multi-Grounded Systems
IMPORTANT: In pole-mounted applications, a ground connection must be made between the recloser, transformer, recloser control, and SCADA equipment for proper protection of the equipment. The pole ground must be sized per local utility practices to minimize the impedance between the recloser and the control.
Figure 11. Recommended grounding method for the Form 6-LS pole mount recloser control installed on 4-wire multi­grounded, with local supply voltage transformer.
20
S280-70-10
Surge Arrester
Recloser Head Ground
Supply
Voltage
Pole
Ground
Pole
Recloser
Pole
Surge Arrester
Transformer
Arrester
Ground
Form 6 Control
HOT NEU GND
NEU
AC
Input Terminal Block
Control Cable
Surge Arrester
Arrester Ground
Customer Ground Connection at ExternalLug
AC
NEUTRAL
Form 6 Control
Supply Voltage
Transformer
ELECTRICAL CONNECTIONS - Remote dedicated supply
transformer
Input Terminal Block
External Ground Lug
Note: Distance between
transformer and recloser should be one pole span or less
System Neutral
Grounding with a Remote Supply Voltage Transformer; 4-Wire Multi-Grounded
Installation of a Form 6-LS pole mount recloser control with a remote supply voltage transformer must include the following:
• Protection of the recloser bushings and the supplying
transformer with lightning arresters.
• Grounding of the recloser head and tank.
• Grounding of the transformer tank.
• Grounding of the control cabinet.
• Grounding of the SCADA equipment.
IMPORTANT: In pole-mounted applications, a ground connection must be made between the recloser, transformer, recloser control, and SCADA equipment for proper protection of the equipment. The pole ground must be sized per local utility practices to minimize the impedance between the recloser and the control.
IMPORTANT: All external inputs to the Form 6 recloser control must be routed within 8 inches of their corresponding ground. During a surge, a potential of approximately 1.5 kV per foot can develop in the conductors. Differences between conductor and ground path lengths can add additional stress to the control components in the event of a power surge.
Figure 12. Recommended grounding method for the Form 6-LS recloser control installed on 4-wire multi-grounded with remote supply voltage transformer.
21
Form 6-LS Pole Mount Recloser Control Installation and Operation Instructions
Customer Connections for AC Power to Form 6-LS Control
DANGER: Hazardous voltage. Do not connect
potential transformer low-voltage secondaries to the control through cables or other wiring until the unit is installed in the field. Transformer high-voltage primary windings will become live when 120V AC is applied to the control from an alternate source if the transformer secondary is connected. Failure to comply may result in severe personal injury or death. T371.1
WARNING: Hazardous voltage. Before applying
power to the control, confirm that male pins of the input power receptacle are electrically insulated to prevent unintentional contact with 120V AC voltage. Failure to do so may result in severe personal injury or death. T372.0
CAUTION: Equipment damage. Do not drill
connection holes into the top of the cabinet.
Connection holes in the top of the cabinet will allow moisture to seep into the control and damage the components or cause control misoperation. Failure to comply will void the control’s factory warranty. T249.0
power supply accessory is available for communication equipment rated for 13.8 VDC. Refer to Radio Mounting Accessory in the Accessories section of this manual for additional information regarding the radio power supply. Some additional features are as follows:
• Positive LED indicator for power supply presence
• Self-protective fuse (5 amp, 250 VAC)
• 28 VDC whetting voltage for I/O contact inputs
IMPORTANT: Prior to energizing the control, the selector switch must be set as follows:
• For 120 VAC incoming power, the selector switch
must be set to the 115V position.
CAUTION: Equipment misoperation. Verify that
the 120/240 VAC selector switch is correctly set
for incoming voltage. Failure to comply may cause
misoperation (unintentional operation) of the control
and/or equipment damage resulting in personal injury. T278.0
AC
Power
Fuse
Input power (120 VAC) to the Form 6-LS control is con­nected to Terminal TB8. B phase (H) is connected to TB8-
3. B phase (N) is connected to TB8-4. Y phase (H) is con­nected to TB8-9. Y phase (N) is connected to TB8-10. Refer to Figure 14.
Input power is required:
• To power the control
• To provide voltage and power metering
• To power the thermostatically controlled heater
• For the convenience outlet accessory
IMPORTANT: Delta connections are not used on the Form 6-LS control.
Power Supply / Battery Charger Board
CAUTION: Equipment damage Form 6-LS (Loop
Scheme). Do not connect 240 VAC to B or Y phases on terminal blocks TB7 or TB8. 240 Volts will damage
internal components and cause control misoperation. T314.0
Incoming AC power is routed to the Power Supply / Battery Charger Board. While this board is designed to
accept either 120 VAC or 240 VAC through a selector switch located directly on the board (Figure 13), the Form
6-LS control must be set for 120 VAC incoming power.
The battery charger includes a temperature-compensated design to optimally charge the control battery. The power supply / battery charger board also includes an auxiliary power supply for connection to communication equipment
(radios, modems, etc.). The auxiliary power supply is rated
28 VDC, 65 Watts peak. A separate 28 VDC to 13.8 VDC
Selector Switch
Figure 13. Power Supply / Battery Charger Board.
Power Supply Board
Terminal Blocks
Two terminal blocks are used for connection to the Form 6-LS control. Both terminal blocks are fit for a #6 screw which can allow a maximum ring size for a #10 AWG for metering.
Terminal Block TB7 provides power to the Form 6-LS control and is directly connected to the power supply circuit board. Terminal Block TB8 is used to connect sensing transformer voltage. The wiring of the transformers should follow the application illustrations per Figure 15 or 16.
Loop Scheme
The Form 6-LS control is equipped with a transfer relay to provide power to the control and power to the recloser if either voltage is present on the source or load side of the recloser. The relay transfers the control power source from
Source I of the control to Source II (load side) upon loss of
source side voltage. This circuitry is rated for 120 VAC
operation only, and is connected to B and Y phases on
TB8 as Source I and Source II respectively. Transfer relay
output contacts connect to TB7. Refer to Figure 14.
Power Connections
The transformer required for power is 1kVA minimum.
Transfer relay connections are shown in Figure 14.
22
Heater &
Power to Control
Convenience Outlet
S280-70-10
65
NEU
15
fuse
Amp
15 Amp
fuse
NEU
43
120/240
2
120
1
TB7
120 (L1)
Power Connections
(L2)
COIL
RELAY
TRANSFER
Transfer Relay
(shown de-energized)
Wye Connection
Factory Wiring for
1211
V3
109
V2
Load
8
V1
7
5 6
4
3
2
V(5-6)
Voltage Sensing Connections
Source
Figure 14. Default factory wiring (transfer relay connections) connected to B-Phase voltage metering with B-Phase incoming supply.
TB8
TB7-4 are factory-jumpered together.
1
V (1-2) V(3-4)
Note: Terminal Block positions TB7-3 and
TB7-6 are factory-jumpered together.
Terminal Block positions TB7-5 and
23
Form 6-LS Pole Mount Recloser Control Installation and Operation Instructions
N
N
A
B
C
D
E
F
G
H
Recloser
A
B
C
N
X
Y
Z
120
(BØ or YØ)
Form 6-LS
Control
TB8
1
3
5
2
7
9
11
TB7
Transfer
Relay
120 Vac Input
Receptacle
(8-pin)
Sensing/Low Voltage
Cable for the Control
Junction Box
3
Control Cable
Recloser low
voltage cable
WARNING: Hazardous voltage. Before applying
power to the control, confirm that male pins of
the input power receptacle are electrically insulated to
prevent unintentional contact with 120V AC voltage.
Failure to do so may result in severe personal injury or
death. T372.0
DANGER: Hazardous voltage. Do not connect
potential transformer low-voltage secondaries to
Figure 15. Typical tie application with junction box accessory. Six single-phase Transformer Connection, Wye configuration only (TB8 Terminal Block Connection).
24
the control through cables or other wiring until the unit is
installed in the field. Transformer high-voltage primary
windings will become live when 120V AC is applied to
the control from an alternate source if the transformer
secondary is connected. Failure to comply may result in
severe personal injury or death. T371.1
S280-70-10
NEU
1
43
2
7
1211
109
8
TB8
Voltage Sensing Connections
Source
Load
V (1-2) V(3-4)
V(5-6)
V1
V2
V3
56
User-Supplied
Disconnect
Switches
WARNING: Hazardous voltage. Before applying
power to the control, confirm that male pins of
DANGER: Hazardous voltage. Do not connect
the input power receptacle are electrically insulated to
prevent unintentional contact with 120V AC voltage.
Failure to do so may result in severe personal injury or
death. T372.0
T371.1
potential transformer low-voltage secondaries to
the control through cables or other wiring until the unit is
installed in the field. Transformer high-voltage primary
windings will become live when 120V AC is applied to
the control from an alternate source if the transformer
secondary is connected. Failure to comply may result in
severe personal injury or death.
Figure 16. Typical sectionalizer application, no junction box. Three-Phase Transformer Connection, Wye configuration only (TB8 Terminal Block Connection).
25
Form 6-LS Pole Mount Recloser Control Installation and Operation Instructions
Standard Default Supervisory Input Control and Output Status Contacts
Standard customer connections TB1 and accessory
customer connections are TB3 and TB4. Refer to Figures 17 and 18 and Tables 4, 5, and 6. The Idea Workbench
allows customization of all the control and status points. Refer to ServiceInformationS280-70-4(ProView4.X.X)or
S280-70-21 (ProView 5.X.X) Form 6 Microprocessor­BasedRecloserControlProgrammingGuidefor additional
information.
IMPORTANT
Shielding and Surge Protection of Supervisory Cables
All supervisory operation and control monitor leads must be protected within shielded cables. Refer to Figure 19.
NOTICE: External leads must be shielded and the shield must be grounded at both ends. Terminate each lead
with a 320VAC, 150 Joules metal oxide varistor (MOV),
or equivalent, at the remote end. Attach MOV’s between the leads and ground. Failure to properly shield and protect leads can result in equipment damage and/or unintentional operation.
TABLE 4 Operating Current Requirements for Standard and Optional Supervisory Inputs
Nominal Minimum Input Voltage Current Operating Time
12 VDC – 250 VDC, 120/240 VAC 2.5 mA 5 milliseconds
TABLE 5 Ratings Table for Output Status Contacts CO1 through CO12 (Resistive Load – Pickup Time 8 ms, Dropout 15 ms)
Contact Input Voltage Rating
120 VAC 8 A
12 VDC 8 A
24 VDC 8 A
48 VDC 1 A
125 VDC 0.4 A
TABLE 6 Ratings Table for Output Status Contact SS1 (Resistive Load – Pickup Time 2 ms, Dropout 15 ms)
Contact Input Voltage Rating
120 VAC 8 A
12 VDC 8 A
24 VDC 8 A
48 VDC 8 A
125 VDC 8 A
26
TB1
SS1
1
2
35
7
91113151719
4
68
10
12
14
16 18
CI1
CI2 CI3
SS1 CO1
CO2 CO3
CO4
CI1 CI2 CI3
CO1
CO2
CO3
CO4
Remote Trip and Lockout
Supervisory Trip and Lockout
Supervisory Close
Control
Lockout
Status (Not in
Lockout)*
Recloser
Status
(Recloser
Open)*
A
B
Hotline
Tag
Status
(Hotline
Tag Off)*
Control
OK
Status
(Control
Not OK)*
Ground Trip
Blocked
Status
(GRD TRIP
Normal)*
Customer Wiring
Remote/Supervisory Common
Customer-Supplied
Voltage Inputs**
**Whetting voltage is also available from the Form 6-LS Control on Terminal Block TB9. Refer to Figure 19.
Note: Contact output relays revert to de-energized positions as shown upon downloading new schemes or Workbench files.
*Relay Contacts shown for Indicated Status
IMPORTANT
Shielding and Surge Protection of Supervisory Cables
All supervisory operation and control monitor leads must be protected within shielded cables. Refer to Figure 19.
NOTICE: External leads must be shielded and the shield must be grounded at both ends. Terminate each
lead with a 320VAC, 150 Joules metal oxide varistor (MOV), or equivalent, at the remote end. Attach MOV’s
between the leads and ground. Failure to properly shield and protect leads can result in equipment damage and/ or unintentional operation.
S280-70-10
Figure 17. Form 6-LS control standard default supervisory input control and output status contacts.
27
Form 6-LS Pole Mount Recloser Control Installation and Operation Instructions
CI4
TB3
1
3579 11 13 15 17 19 21
CI5
CI6
CI7 CI8
CI9
CI10
CI11
CO5
CO6
TB4
2
46 810121416
18
20
CI4 CI5 CI6 CI7 CI8 CI9
CI10
CI11
CO5
CO6
13
5
7911 13
CO7 CO8
CO9 CO10 CO11
CO12
2
46
8
10
12
CO7 CO8 CO9
CO10
CO11
CO12
Supervisory Ground Trip Block
Supervisory Reset Targets
Supervisory Non-Reclose
Unassigned
Remote Alternate Profile 2
Remote Alternate Profile 1
Remote Alternate Profile 3
Non-Reclosing
Status
(Normal
Reclose)*
Remote Normal Profile
Alarms
Status
(No Alarms)*
Alternate
Profile 1
Status
(Not in
Alt 1
Profile)*
Normal
Profile
Status
(Not in
Normal
Profile)*
Alternate
Profile 2
Status
(Not in
Alt 2
Profile)*
Frequency
Alarm
(Frequency
Normal)*
Alternate
Profile 3
Status
(Not in
Alt 3
Profile)*
Voltage
Alarm
(Voltage
Normal)*
*Relay Contacts shown
for Indicated Status
Customer Wiring
Remote/Supervisory Common
Customer-Supplied
Voltage Inputs**
**Whetting voltage is available from the
Form 6-LS Control on Terminal Block
TB9. Refer to Figure 19.
IMPORTANT
Shielding and Surge Protection of
Supervisory Cables
All supervisory operation and control monitor leads must
be protected within shielded cables. Refer to Figure 19.
NOTICE: External leads must be shielded and the shield
must be grounded at both ends. Terminate each lead with
a 320VAC, 150 Joules metal oxide varistor (MOV), or
equivalent, at the remote end. Attach MOV’s between the
leads and ground. Failure to properly shield and protect
leads can result in equipment damage and/or uninten-
tional operation.
Figure 18. Form 6-LS control Discrete Interface Board accessory default supervisory input control and output status con­tacts.
28
FORM 6-LS CONTROL
REMOTE
BOX
Not All Remote
Connections
Shown
SHIELD
12 CO1
3
5
7
4
6
8
CI1
CI2
CI3
CI1
CI2
CI3
Remote Trip and
Lockout
Supervisory
Trip and
Lockout
Supervisory
Close
TB1
1
2
+
Whetting Voltage TerminalsCustomer Wiring
Customer Wiring
28 VDC
11
13
CO1
Recloser
Status
A*
B*
*Contacts shown
with recloser in
OPEN position.
Factory-Supplied
28 VDC Whetting
Voltage
A Single common wire can be used for multiple inputs if it is jumpered at the I/O board terminals.
NOTES: Arresters to be metal oxide varistors (MOVs) 320 VAC, 150 Joules or equivalent.
Shielding for Supervisory Cables should follow the representative input control contacts and output status contacts as shown.
External lead resistance must not exceed 200 ohms.
Supervisory and Remote Functions are default functions.
TB9
S280-70-10
Figure 19. Shielding and Surge Protection for Supervisory and Remote Cables.
29
Form 6-LS Pole Mount Recloser Control Installation and Operation Instructions
RS-232 DTE
J1-RS-232
12
3
45
6
7
89
TB1
123 57911 13 15 17 19
4681012141618
CI1
CI2 CI3 SS1 CO1
CO2 CO3
CO4
CI4
CI1 CI2 CI3 SS1 CO1 CO2 CO3 CO4
TB3
13579111315171921
CI5 CI6 CI7 CI8 CI9 CI10 CI11 CO5CO6
TB4
2
4681012141618
20
CI4 CI5 CI6 CI7 CI8 CI9 CI10 CI11 CO5
CO6
1357911 13
CO7CO8
CO9CO10CO11
CO12
2
4681012
CO7CO8 CO9CO10CO11CO12
J1-RS-232
IRIG-B
RS-232 DTE
RS-232 Serial
Communication Port
TB9
+
28 VDC
WHETTING VOLTAGE
P1
P2
P3
P4
VOLTAGE SENSING
53VDC CONTROL CABLE28 VA C
123
45
123
45
23
22
21
20
19
11
10987
18
17
16
15
14
654
32
13
1
24
12
123
4
5
3
1
3
1
3
4
2
4
24
1
2
IRIG-B Time
Sync Connector
Rear Panel RS-232 Communication Port Pin Assignments
Tables 7 indicates the pin assignments for the rear panel
RS-232 communication port (Figure 20). Refer to Figure 21
for pin identification. Refer to Protocols for additional information.
Refer to the Accessories section of this manual for additional communication options.
TABLE 7 Rear Panel RS-232 Communication Port Pin Assignments
Pin Number Signal Name
1 DCD .................... Carrier Detect
2 RXD .................... Receive Data
3 TXD ..................... Transmit Data
4 DTR .................... Data Terminal Ready
(Not Connected)
5 GND .................... Signal Ground
6 DSR .................... Data Set Ready
(Not Connected)
7 RTS .................... Request to Send
8 CTS .................... Clear to Send
9 NC ..................... Not Used
10 (Shroud) ................. Chassis Ground
Figure 21. Rear panel RS-232 communication port pin identification.
Figure 20. Form 6-LS control rear panel RS-232 communication ports (standard configuration).
30
S280-70-10
Before Placing the Control and the Recloser into Service
CAUTION: Equipment misoperation. Do not
connect this control to an energized recloser until all control settings have been properly programmed and verified. Refer to the programming information for this control. Failure to comply can result in control and recloser misoperation, equipment damage, and personal injury. G110.3
Prior to placing the control and recloser into service, the following installation procedures must be properly com­pleted and verified:
1. Front panel label inserts changed (if applicable).
Note: Refer to Using Removable Inserts in this manual.
2. Control properly mounted for the installation.
3. Recloser installed according to all locally approved standards and practices.
4. AC disconnect switches installed.
5. Control and recloser properly grounded in accordance with guidelines in this manual and the applicable recloser manual.
CAUTION: Equipment misoperation. Verify that
the 120/240 VAC selector switch is correctly set
for incoming voltage. Failure to comply may cause
misoperation (unintentional operation) of the control
and/or equipment damage resulting in personal injury. T278.0
CAUTION: Equipment damage Form 6-LS (Loop Scheme). Do not connect 240 VAC to B or Y phases on terminal blocks TB7 or TB8. 240 Volts will damage
internal components and cause control misoperation. T314.0
6. Control cable properly connected and supported.
7. Verify the selector switch on the Power Supply/Battery Charger Board is set to the 115V position for 120 VAC incoming power.
8. Control battery connected and tested for proper operation.
Note: The battery test is blocked for 30 seconds upon
power-up of the control.
Test the battery as follows:
A. Press the MENU button on the front panel.
B. Using the down arrow key, navigate to the BATTERY
menu and press ENTER.
C. Using the down arrow key, navigate to the TEST
BATTERY menu and press ENTER.
D. Press the F4 button to test the battery.
Note: This message will appear on the programming
panel LCD display: ----TESTING----
The battery test results will display in the battery
metering menu.
Note: With AC disconnected and the battery supplying
the load, current will read -400 to -600 mA
depending on accessories connected.
9. AC power connected to the control. (Control OK LED
indicator is illuminated.)
Note: The control Power Save feature will turn off the back-
lit LCD display and all LEDs if no front panel keypad is pressed within ten minutes.
10. All control programming entered and verified by appro- priate personnel.
Note: Refer to Service Information S280-70-4 (ProView
4.X.X) or S280-70-21 (ProView 5.X.X) Form 6 Microprocessor-Based Recloser Control ProgrammingGuide for additional information.
IMPORTANT: Form 6-LS control users must activate the loop scheme default settings in the ProView application software Idea Workbench:
1. Click on LOAD IDEA WB STRUCTURE.
2. Select WBI-Form6-F6Default-LS.sch and click on Open.
3. Click on READ IDEA WB SETTINGS FROM DISK.
4. Select WBI_Form6_Settings_F6 Default-LS.txt and click on Open.
5. Enable the LS functionality by selecting the LS Enable checkbox in the Loop Scheme Settings Dialog box located in the Idea Workbench Optional Loop Scheme Workbench.
11. Control clock set to the correct time.
Note: Refer to Service Information S280-70-4 (ProView
4.X.X) or S280-70-21 (ProView 5.X.X) Form 6 Microprocessor-Based Recloser Control ProgrammingGuide for additional information.
12. Customer connections for remote and supervisory operation checked and completed in accordance with
proper shielding and surge protection (Figure 19).
NOTICE: External leads must be shielded and the shield must be grounded at both ends. Terminate each lead with
a 320VAC, 150 Joules metal oxide varistor (MOV), or
equivalent, at the remote end. Attach MOV’s between the leads and ground. Failure to properly shield and protect leads can result in equipment damage and/or unintentional operation.
31
Form 6-LS Pole Mount Recloser Control Installation and Operation Instructions
Using Removable Inserts
CAUTION: Control damage. De-energize both AC and
DC power prior to removing or installing any internal connections or circuit boards in the control. Failure to comply can result in damage to the control. T241.1
CAUTION: Equipment damage. Always wear a grounding wrist strap to control static electricity before handling circuit boards. Failure to use this strap may result in circuit board damage. T253.1
The front panel inserts can be changed, if desired.
1. De-energize both AC and DC power.
2. Use a flathead or 3/33" hex key screwdriver to unscrew the six front panel screws.
3. Pull the right side of the front panel out towards the left
(Figure 22).
Note: Various connecting wires will keep the panel attached
to the control.
Note: It is not necessary to disconnect any wires.
4. Use tweezers to gently pull out the removable insert.
Note: The insert will slide out of the right side of the
operating panel (Figure 23).
Note: The insert will slide out of the top of the programming
panel indicator section (Figure 22).
5. Change the existing label or slide in a new label with the name of the programmed option.
An electronic label template is included on the ProView
application software CD and can be accessed through the following default address:
C: \ Program Files \ Cooper \ ProviewXX \ Form 6 \
Form 6 Inserts.doc
IMPORTANT: Laminate the removable inserts prior to installing. This will seal the ink/toner and avoid damage to the front panel.
6. Gently push the removable insert from right to left into
the right side of the operating panel (Figure 23) or down
into the programming panel LED indicator section
(Figure 22).
Removable LED Status Indicator Panel
Figure 22. Open front panel. Labels are easily removed from and inserted into the top of the programming panel LED status indicator section.
Figure 23. Labels are easily removed from and inserted into the operating panel.
7. Place the front cover panel back onto the control. Using a flathead screwdriver screw the screws into the control and tighten all hardware completely.
32
ACCESSORIES
TB1
123 57911 13 15 17 19
4681012141618
CI1
CI2 CI3 SS1 CO1
CO2CO3
CO4
CI4
CI1 CI2 CI3 SS1 CO1 CO2CO3 CO4
TB3
13579111315171921
CI5 CI6 CI7 CI8 CI9 CI10 CI11 CO5CO6
TB4
2
4681012141618
20
CI4 CI5 CI6 CI7 CI8 CI9 CI10 CI11 CO5
CO6
1357911 13
CO7CO8
CO9CO10CO11
CO12
2
4681012
CO7CO8 CO9CO10CO11CO12
J1-RS-232
IRIG-B
RS-485
RS-232 DTE
TB9
+
28 VDC
WHETTING VOLTAGE
P1
P2
P3
P4
VOLTAGE SENSING
53VDC CONTROL CABLE 28 VAC
123
45
123
45
23
22
21
20
19
11
10987
18
17
16
15
14
654
32
13
1
24
12
123
4
5
3
1
3
1
3
4
2
4
24
1
2
C + –
DIF Board Accessory
S280-70-10
These accessories are available. Contact your Cooper Power Systems representative for additional information.
Loop Sectionalizing Accessories
Various wiring options for 120 VAC low voltage closing reclosers or control-powered NOVA reclosers, 120 VAC single or three-phase sensing are available. Refer to Table 8 for ordering options.
Cable Locking Sleeves
To prevent detachment of the control cable from the con­trol cabinet by unauthorized personnel, a cable-locking sleeve is available to enclose the cable plug. The plug is passed through the sleeve and the sleeve is then fastened from inside the control cabinet. There is no access to the cable receptacle without opening the locked cabinet door and detaching the sleeve.
Catalog Number KME6-1772-1: Quantity 1
Catalog Number KME6-1772-2: Quantity 2
TABLE 8 Loop Sectionalizing Accessories
Description Catalog Number
Wiring Options for 120 VAC Low-Voltage Closing Reclosers, 120 VAC Single- or Three-Phase Sensing
Junction box equipped with Source 1 and Source 2 sensing cables. (4-conductor, 5 ft. length) includes hardwiring the low-voltage closing cable for the recloser (KA11ME1-X) and hardwiring the sensing/low
voltage cable for the control (KA145LS-X) ...................................................... KA235LS1*
Input-sensing/low voltage cable, 8 conductor, 120 VAC (basic cable, no length) .........................KA145LS
Replace “X” with desired length. Select from 5 to 80 feet. ........................................KA145LS-X
120 VAC/240 VAC Input receptacle, 8-pin ......................................................KME6-805-1
Wiring Options for Control-Powered NOVA recloser, 120 VAC Single- or Three-Phase Sensing
Junction box equipped with Source 1 and Source 2 sensing cables. (4-conductor, 5 ft. length) includes
hardwiring the sensing/low voltage cable for the control (KA145LS-X) .................................KA235LS1**
Input-sensing/low voltage cable, 8 conductor, 120 VAC (basic cable, no length) .........................KA145LS
Replace “X” with desired length. Select from 5 to 80 feet. ........................................KA145LS-X
120 VAC/240 VAC Input receptacle, 8-pin ......................................................KME6-805-1
*Requires KA11ME1-X cable, ordered with recloser. KA145LS-X cable and the KME6-805-1 receptacle are to be ordered separately.
**KA145LS-5X cable and the KME6-805-1 receptacle are to be ordered separately.
120 VAC GFI Duplex Outlet
The GFI Duplex Outlet (Catalog Number KME6-1776-2) is
available for controls powered by 120 VAC three-wire sup­ply power. This convenience outlet is rated for 15 Amperes and is accessible through the front door in the control cabinet. The 120 VAC GFI Duplex Outlet is used for many applications such as power for the MET Tester, auxiliary measurement equipment, and supplemental lighting.
Discrete Interface Board (DIF) Option Accessory
A Discrete Interface Board Option accessory provides eight configurable input control contacts and eight configu-
rable output status contacts (Figure 24). The ordering options include: Standard (3 inputs / 5 outputs) or Additional (8inputs/8outputs).
Cabinet Ordering Accessories
• AISI 304 stainless steel cabinet construction
• Three-point door latch
Figure 24. Form 6-LS control discrete interface board accessory.
33
Form 6-LS Pole Mount Recloser Control Installation and Operation Instructions
Radio-Mounting
Bracket
24 Vdc to 13.8 Vdc Converter
Customer-Supplied
Power Leads
Radio Antenna Cable (only available with full automation accessory)
Power Cable
Antenna Surge Suppresser and Connector (only available with full automation accessory)
Customer-Supplied
Radio
J1-RS-232
IRIG-B
RS-485
RS-232 DTE
TB9
+
28 VDC
WHETTING VOLTAGE
P1
P2
P3
P4
VOLTAGE SENSING
53VDC CONTROL CABLE28 VAC
123
45
123
45
23
22
21
20
19
11
10987
18
17
16
15
14
654
32
13
1
24
12
123
4
5
3
1
3
1
3
4
2
4
24
1
2
C + –
In-Line 1 Amp Fuse
+ 1
– 2
P2
Radio Mounting Accessory
The radio mounting accessory (Figure 25) is powered from
a voltage regulated power supply factory-calibrated with an output of 13.8 VDC.
The radio power supply input is fused by a 1 Amp in-line fuse for a nominal voltage of 28 VDC. The output is 13.8
VDC between P2-1 (+) and P2-2 (-) on the radio power
supply circuit board with a maximum continuous watt rating of 17.25W @ 13.8 VDC.
Note: This output cannot be field-calibrated.
The radio will continue to operate during the loss of AC power as long as power is supplied from the battery. The
power supply is designed to provide up to 40 Watts (peak)
and is fused to isolate any potential radio problems without disturbing the protection system in the recloser control. Refer to Table 9.
Contact your Cooper Power Systems representative for any additional voltage requirements.
TABLE 9 Radio Mounting Accessories
Description Catalog Number
Full Automation accessory
12 VDC radio provision ................ KME6-1774-5
(Radio and fiber-optic/RS232 interface not included)
Automation accessory (bracket only)
12 VDC provision ...................... KME6-1774-4
Figure 25. Form 6-LS control radio mounting accessory.
34
S280-70-10
Communication Board Accessories
The Form 6-LS control is equipped with a Communication
Board Accessory (expansion bay) offering versatile support
for modern communication media. Six distinct communi-
cation options (Figure 26) are available, providing two-way,
real time digital communications with a remote terminal unit
(RTU), wireless, telephone modem, Ethernet network, or
other communication devices. The following options are available:
• No auxiliary communication card installed (standard)
• RS485 (isolated) Serial communication card
• Fiber-optic-based Serial Communication Card (ST)
• 10/100 Base-T dual Ethernet communication card (2*RJ-45)
• 100 Base-FX dual Ethernet communication card (2*MT­RJ)
• 10/100 Base-T, 100 Base-FX Ethernet communication card (RJ-45 + MT-RJ)
The expansion bay based Communication Board Accessory concept offers high versatility with respect to communica­tion medium and protocol support. Additional accessories are being continuously developed. Contact your Cooper Power Systems representative for the latest information regarding particular media and communication protocol support.
RS485 Serial Communication Card
The RS485 serial communication card accessory provides
means for establishing asynchronous link-based digital communications with the Form 6-LS control. The Galvanic
isolated (1000V DC) RS485 port uses a single shielded
twisted pair connection and can support 32 devices in multi-drop configuration. Communication speed is con-
trolled through software and can be set at: 1200, 2400, 4800, 9600, 19.2k, 38.4k, 57.6k, and 115kBPS.
Digital communications must be programmed through the Communications Workbench to ensure proper operation of
the RS485 communication card accessory. Refer to
Service Information S280-70-4 (ProView 4.X.X) or S280­70-21 (ProView 5.X.X) Form 6 Microprocessor-Based RecloserControlProgrammingGuidefor additional proto-
col support information.
Fiber-Optic Based Serial Communication Card
The Fiber-Optic based Serial Communication Card offers
means of establishing asynchronous (RS-232 like) digital
communications through multi-mode fiber media. The use of the fiber-optic based serial communication card acces­sory can enhance communication reliability, and provides excellent electrical isolation thus protecting transmitted data from extraneous electrical interference.
An optional fiber-optic-to-RS-232 converter with DB-9
connector (Catalog Number KME6-1875-1) is available for
interfacing between an optical signal and a hard-wired RS-232 signal, when required. This converter is compatible
with loop (ring) and point-to-point (star) configurations.
A pair of industry standard ST type fiber-optic connectors are mounted on the back of the board enabling customer connection to a digital communication system using fiber-
optic cables (customer-supplied).
The fiber-optic link has separate receive (RX) and transmit (TX) ports operating at 820nm. Typical transmission dis-
tance is 2000m with 62.5/125µm multi-mode fiber. Consult your Cooper Power Systems representative for availability of long haul solutions. Link communication speed is con-
trolled through software and can be set at: 1200, 2400, 4800, 9600, 19.2k, and 38.4k. Modbus can also be set at
57.6k.
The fiber-optic accessory must be programmed through the Communications Workbench for the appropriate proto­col. Refer to Service Information S280-70-4 (ProView
4.X.X) or S280-70-21 (ProView 5.X.X) Form 6 Microprocessor-Based Recloser Control Programming Guidefor additional information.
The fiber-optic based serial accessory includes TX and RX indicating LEDs for verifying communications along with an echo / non echo switch for supporting ring / star fiber topologies.
When operated in a ring configuration, the toggle switch must be set in the ECHO position. In this mode, the fiber-
optic card will repeat (pass through) all messages received
on the RX fiber, and will respond to the Master station by first echoing the incoming command and then sending the response. This arrangement is best suited for creation of low cost multi device fiber loops. For reliable communica­tions, the fiber loop system requires that all devices in the loop remain powered at all times, thus enabling unob­structed flow of information throughout the loop.
A more resilient system can be designed by using the fiber-optic ports in a point-to-point or multiple point-to-
point (star) configuration. For this mode, the toggle switch
must be set in the NON-ECHO mode. The Form 6-LS control will respond to the Master station by sending a
response only (total separation of Receive and Transmit fibers). Additional hardware (fiber-optic star coupler) is
required to support the multiple point-to-point device con­figurations.
Ethernet Communication Cards
The Ethernet communication card accessory brings the Ethernet network connectivity to the Form 6-LS recloser control platform. It is highly flexible, offering simultaneous
support for multiple sessions, device management (ProView over TCP/IP) and SCADA communications (DNP3 over TCP/IP).
By natively supporting a set of widely accepted industry standards (TCP/IP, UDP/IP, OSI) the Ethernet communica­tion accessory ensures seamless interoperability with other network devices.
35
Form 6-LS Pole Mount Recloser Control Installation and Operation Instructions
TX
RX
NON-ECHO
Serial Fiber
Ethernet 100 Base-FX Type 2
Ethernet 10/100 Base-T, 100 Base-FX Type 3
Ethernet 10/100 Base-T Type 1
#2 #1
Standard (No Communication Option)
IRIG-B
J5
RS-485 Communication
RS-485 C
-
+
RX
TX
#2
#1
#2 #1
IRIG-B
J5
J4 – ETHERNET – J3
2 1
IRIG-B
J5
J4 – ETHERNET – J3
2 1
IRIG-B
J5
J4 – ETHERNET – J3
2 1
IRIG-B
J5
IRIG-B
J5
Ethernet 100 Base-FX Type 4
Default Primary Ethernet Interface
#2
#1
IRIG-B
J5
J4 – ETHERNET – J3
2 1
Figure 26. Back panel Ethernet and Communication options.
The Ethernet communication card accessory is offered in 3
physical layer configurations (twisted pair and optical-fiber options) as shown in Table 10.
TABLE 10 Ethernet Communication Card Configurations
Card Output Communication Type Configurations Connectors Speed
1 10/100 Base-T 2 * RJ-45 10 / 100MBps (auto switching)
2 100 Base-FX 2 * MT-RJ 100MBps (multi-mode fiber) (full duplex)
3 10/100 Base-T, RJ-45 + MT-RJ 10/100MBps
100 Base-FX and 100MBps
4 100 Base-FX, 2 * LC 100MBps (single-mode fiber) (full duplex)
Maximum link length is determined by the use of the particular physical layer implementation, and can be further constrained by the actual network configuration. In case of
the 100Base-FX MT-RJ connector based implementation,
maximum link length in excess of 2000m can be achieved with 62.5/125µm multi mode fiber. The fiber-optic link uses 1300nm wavelength, and can easily be interfaced to other
100Base-FX solutions (ST connector patch cord solution).
The Ethernet communication accessory card (Figure 26) is
equipped with two physical ports configured to act as primary and standby LAN connections. Availability of the backup communication port enables creation of highly redundant Ethernet networks thus increasing the overall system reliability.
Note: Under normal network conditions, all communications
will be channeled through the primary port (#1, Figure
26), with the standby port either logically disabled, or
configured for fast automatic throw-over in case of the primary Ethernet link failure. Refer to ServiceInformation
S280-70-4 (ProView 4.X.X) or S280-70-21 (ProView
5.X.X) Form 6 Microprocessor-BasedRecloser Control Programming Guide for additional Ethernet accessory
configuration information.
36
TESTING
CAUTION: Equipment misoperation. Do not
connect this control to an energized recloser until all control settings have been properly programmed and verified. Refer to the programming information for this control. Failure to comply can result in control and recloser misoperation, equipment damage, and personal injury. G110.3
IMPORTANT: The Form 6 control can be taken out of service for testing and placed back into service without de-energizing its recloser and interrupting the system. However, during the time the control is out of service, the recloser is inoperative.
Testing an Installed Control
The following tests to determine initial operation of the Form 6-LS control can be performed while connected to an operating recloser.
Note: These are the only tests performed on an installed, oper-
1. Verify operating status of all indicator lights by pressing
2. Check the operational values for currents, voltages,
3. Test battery operation as follows:
(continued on next page)
ating control.
and holding the LAMP TEST key for two seconds on
the programming panel (Figure 27).
and other metering information.
Note: Scroll through the LCD display messages by press-
ing the and cursor movement arrows under­neath the LCD display on the programming panel
(Figure 27).
Note: The battery test is blocked for 30 seconds upon
power up of the control.
Note: AC power can be either connected or disconnected
for battery test.
S280-70-10
CONTROL POWER
CONTROL OK
CONTROL LOCKOUT RECLOSER OPEN
RECLOSER CLOSED
A PHASE FAULT
B PHASE FAULT
C PHASE FAULT GROUND FAULT
SENSITIVE GND
Control OK LED
METERING
RESET
TARGETS
EVENTS
LAMP TEST
MENU
ENTER
+
SETTINGS
OPER
COUNTER
ALARMS
CHANGE
F1 F2 F3 F4
RS-232 DATA PORT
LCD Display
LAMP TEST Key
Cursor Movement
Arrows
Remove the Control from Service
IIMPORTANT: Disconnect switches for AC sensing
and power connections are necessary to isolate the Form 6 control for testing and servicing.
IMPORTANT: The control must be removed from ser­vice in the exact order specified in this section.
Figure 27. Lamp Test button, LCD display, and cursor movement arrows.
(continued from previous page)
A. Press the MENU button on the front panel.
B. Using the down arrow key, navigate to the BATTERY
menu, and press ENTER.
C. Using the down arrow key, navigate to the TEST
BATTERY menu and press ENTER.
D. Press the F4 button to test the battery.
Note: This message will appear on the programming
panel LCD display: ----TESTING----
The battery test results will display in the battery
metering menu.
Note: Voltage should be between 25–31 VDC – with the
Under normal conditions, with AC connected and
With AC connected and a discharged battery, the
With AC disconnected and the battery supplying
higher voltage at colder temperatures.
a fully charged battery, the charging current should be less than 20 mA.
current range should be 20–450 mA.
the load, current will read -400 to -600 mA
depending on accessories connected.
4. Verify the Control OK LED is illuminated on the control
operator panel (Figure 28). This indicates the presence
of AC power.
Note: The control includes a Power Save feature that will
turn off the backlit LCD display and all LEDs if no front panel keypad is pressed within ten minutes. Pressing the LAMP TEST key will reactivate the dis­play and active LEDs.
All other tests described in this TESTING section require the Form 6-LS control to be removed from service, con­nected to a bypassed recloser, or tested at a location where the proper testing equipment is available.
Figure 28. Control OK LED.
1. Enable GND TRIP BLOCKED to allow for ground trip to be disabled when re-energized.
A. Press the CHANGE button on the Operator Panel to
enter the CHANGE mode.
B. Depress the GND TRIP BLOCKED button within ten
seconds after entering the CHANGE mode.
Note: If the GND TRIP BLOCK button is not pressed
within ten seconds, the function is not activated.
2. Disconnect the battery.
3. Remove control AC sensing and power connections from the control using a separate disconnect switch.
CAUTION: Hazardous voltage. Open CT sec-
ondaries can generate high voltages. Contact with CT pins of the disconnected cable can cause elec­tric shock and may result in personal injury. Open recloser contacts and open disconnect switches before disconnecting control cable. T204.3
CAUTION: Equipment misoperation. Disconnect all control power sources prior to disconnecting or recon­necting the control cable from the control. Failure to comply can result in recloser misoperation at the time of disconnection or reconnection of the control cable to the control. T311.1
4. Disconnect control cable from control.
CAUTION: Hazardous voltage. Cable conductors
attached to controls will remain at 53 VDC and 120 VAC potential while connected to the control. Contact with any pins at the end of the cable directly or indirectly connected to a control can result in personal injury or equipment damage. Disconnect battery and external power sources in the control then remove control cable at control end before disconnecting from recloser end. T312.2
5. Remove any control input and status output wiring
from TB1, TB3, and TB4 (Figure 29).
6.
Disconnect any serial
C + –
communications ports and IRIG-B timing con-
nections (Figure 29).
7. Disconnect the ground from the control.
CI1
CI2 CI3 SS1 CO1
123 57911 13 15 17 19
TB1
4681012141618
CI1 CI2 CI3 SS1 CO1 CO2 CO3 CO4
CI4
CI5 CI6 CI7 CI8 CI9 CI10 CI11 CO5 CO6
13579111315171921
TB3
2
4681012141618
CI4 CI5 CI6 CI7 CI8 CI9 CI10 CI11 CO5
CO2 CO3
CO4
20
CO6
J1-RS-232
RS-232 DTE
CO7CO8
CO9CO10CO11
1357911 13
2
4681012
CO7CO8 CO9CO10CO11CO12
RS-485
IRIG-B
CO12
TB4
8. Carefully transport the control to a suitable service facility.
Figure 29. Back view of top half of Form 6-LS recloser control.
37
Form 6-LS Pole Mount Recloser Control Installation and Operation Instructions
Preliminary Testing with No AC Available
If the Form 6 control is not in service and requires energization for preliminary testing, it can be powered up with battery power only.
Note: Controls with expanded memory require battery voltage
to be 23VDC minimum.
1. Open the rear door of the Form 6 pole-mount control cabinet and locate terminals TM1 and TM2 on the
power supply circuit board (Figure 30).
Testing with Type MET Tester
The Type MET electronic recloser control tester (Figure 31)
is used for testing the following functions of the Form 6 recloser control:
• Overcurrent Timing
• Reclose Time
• Operating Sequence
• Reset Time
• Minimum Trip Current
• High Current Trip and Lockout
The MET Tester is completely self-contained, capable of performing all required checks and tests from a simple verification of operation to a complete verification of all operating parameters.
Refer to Service Information S280-76-1 Type MET Electronic Recloser Control Tester Operating Instructions for proper setup and use of the MET Tester.
Figure 30. Location of terminals TM1 and TM2 on the power supply circuit board
2. Momentarily jumper terminals TM1 and TM2 together.
(The control will power up.)
3. To power down the Form 6 control, unplug the battery
(disconnect the black/red battery connector).
4. Perform a battery charging cycle. Refer to Battery Charging in the Battery Test and Charging Procedures section of these instructions.
IMPORTANT: While the Form 6 control is powered in this manner, the control battery is being continuously discharged. When the battery voltage drops to 22V DC, the control will automatically power down.
If the battery is left in a discharged condition, the
battery(s) will sustain permanent irreversible damage.
Therefore, a battery charging cycle should always be
performed after this procedure to bring the battery(s)
back up to full charge.
Figure 31. Type MET electronic recloser control tester.
38
S280-70-10
5 6
3
4
1 2
C
B
A
BYPASS SWITCHES
(CLOSED)
SOURCE SIDE DISCONNECT SWITCHES (CLOSED)
LOAD SIDE DISCONNECT SWITCHES (OPEN)
CLOSING
COIL
LOAD
SOURCE
SOURCE
LOAD
Closing the Recloser During Testing
Electrical Closing – Solenoid-Operated Reclosers
Line voltage is required for automatic recloser operation during testing of reclosers equipped with a closing solenoid
(except for reclosers equipped with the low voltage closing accessory).
WARNING: Hazardous voltage. Interconnect
source leads X and Y and ground solidly to the
recloser tank (Figure 34). Do not connect lead Z to any
other phase or mechanical ground. Dangerous voltages to
ground exist on the phase connected to lead Z. Solidly
ground all equipment. Failure to comply can result in severe personal injury and/or equipment damage. T224.1
For on-line testing, bypass the recloser, open the load­side disconnects and keep the source-side disconnects closed. This will remove the recloser from service, but will
keep line voltage supplied to the closing solenoid (Figure
32).
WARNING: Hazardous voltage. The switchgear
(apparatus and control) and high-voltage trans­former must be in a test cage or similar protected area to prevent accidental contact with the high-voltage parts.
Solidly ground all equipment. Failure to comply can result in death, severe personal injury, and equipment damage. T221.5
For shop testing, the closing solenoid voltage is supplied by back-feeding a transformer with a low-side rating equal
to the voltage rating of an available power source, and a high-side rating equal to the voltage rating of the recloser (Figure 34). A 75 kVA transformer of the proper voltage rat­ing with an impedance drop of approximately 3% is satis­factory. The AC source must have a comparable imped­ance drop.
A test circuit for these solenoid-closed reclosers is shown in Figure 33. The following equipment is required for the recommended shop testing setup:
Note: Solenoid-closed reclosers equipped with a 120- or 240-
VAC low-voltage closing coil accessory can be tested as shown in Figure 35.
• Variable Autotransformer T1, 230 Volts, 20 Amps.
• Low-Voltage transformer T2 to simulate fault conditions.
Ratio and size will depend upon the maximum current
to be used. The recloser presents a low impedance to the transformer, so secondary voltage must be only high enough to force the required current through the secondary of the transformer and the recloser.
Note: An alternative method of providing the necessary
current through the transformer is shown in Figure
33.
• High-Voltage T3 to operate the closing solenoid.
The closing coil requirement is approximately 200 kVA
during the two-to-three cycle closing operation. The solenoid coil operating voltage must be maintained at the recloser bushings during the interval the closing coil is energized. This procedure is not used on reclosers equipped with the low-voltage closing accessory.
• Ammeter with a rating based on the level of test cur­rent.
• Current-actuated timer.
Figure 32. Closing source-side switches of a bypassed “on-line” recloser provides closing solenoid power for automatic operation during testing.
39
Form 6-LS Pole Mount Recloser Control Installation and Operation Instructions
3
6
4
T3
Y
H*
X
Z
VOLTAGE RATING OF RECLOSER CLOSING SOLENOID COIL
SENSING CTs (3)
CLOSING SOLENOID CONTACTOR
ROTARY SOLENOID
MAIN CONTACTS (S)
G* K*
A* B*
E* F*
TO 240 OR 480 VAC SOURCE
TO 240 VAC SOURCE
CLOSING SOLENOID COIL
TRIP SOLENOID
CONTROL CABLE RECEPTACLE
W
FORM 6 CONTROL
TO AMMETER AND RELAY TO OPERATE CYCLE COUNTER OR OTHER TIMING DEVICE
AC POWER
VARIABLE AUTOTRANSFORMER 240 VAC 20 AMPS
T2
1
2
5
J*
T1
*Indicates control cable receptacle pin/socket designation.
Electrical Closing – Motor-Operated
115Vac
1
Note: This test circuit can apply over 800 Amps to the recloser.
Variable Autotransformer (10 Amp)
600:5 Recloser BCT ON 600:5 Tap
2
Clamp-On Ammeter
Note: Use at least 2/0 cable between bushings.
Figure 33. Alternate method of producing variable line current (substitute for T2 and W-X circuit in Figures 34 and
35).
Low Voltage Closing Solenoid / NOVA Reclosers
WARNING: Hazardous voltage. Solidly ground
all equipment. Failure to comply can result in
death, severe personal injury, and equipment damage. T223.2
High-voltage is not required for reclosers utilizing a motor­operated closing mechanism, low voltage closing, or NOVA recloser. For information on energizing the recloser, refer to the appropriate recloser installation manual. Low
voltage supply can use either 120 or 240 VAC for input
power. Check the name plate on the recloser to verify the correct closing power requirements.
Figure 35 shows a test circuit for motor-operated, low­voltage solenoid-closing, and NOVA reclosers. Since these reclosers require only a low voltage source for closing, high-voltage transformer T3 and its protective cage is eliminated. All other equipment is the same as the test
equipment shown in Figure 34.
Figure 34. Suggested test circuit for high voltage “shop-testing” solenoid-closing reclosers.
40
S280-70-10
65
43
21
FORM 6 RECLOSER CONTROL
J
GK
H
X
W
120/240 VAC POWER SUPPLY
T1 T2
240 VAC
VARIABLE AUTOTRANSFORMER 240 VAC-20 A
AC POWER
TO AMMETER AND RELAY TO OPERATE CYCLE COUNTER OR OTHER TIMING DEVICE
SENSING CTs (3)
NOT APPLICABLE FOR CONTROL-POWERED NOVA RECLOSERS
Manual Closing – Solenoid-Operated Reclosers
WARNING: Explosion Hazard. Excessive
Contact Arcing. Do not use the manual closing tool to close an oil-insulated energized recloser. Closing an energized oil-insulated recloser with a manual clos­ing tool can cause excessive contact arcing, rapid build-up of gas within the equipment, and possible explosion which can cause death, severe personal injury, and equipment damage. T203.2
If high-voltage for operating the closing solenoid is not available, manual closing can be substituted for electrical closing. However, not all control settings can be checked since manual closing is not synchronized with the closing coil control circuit in the control.
Follow these steps to manually close the recloser:
1. Remove the closing tool port cover and gasket from the side of the recloser head casting.
Figure 35. Suggested test circuit for motor-operated, solenoid­closing reclosers with low-voltage closing.
CAUTION: Equipment damage. Do not turn the manu­al closing tool more than one-quarter turn clockwise. Forcing the tool beyond the mechanism stop may shear the pin on the closing shaft of the recloser. T222.0
2. Insert the tee-handled tool (available as an accessory) into the port, engaging the pin on the closing shaft
(Figure 36).
3. Close the recloser by placing the yellow operating
handle (located under the sleethood) into the up or
CLOSED position and turning the closing tool one­quarter turn clockwise.
4. After each trip operation, about 1/2 second elapses while the closing solenoid plunger is moving upward to reset the main toggle latch.
5. After the main toggle latch resets, the recloser can be closed again by operating the manual closing tool.
6. Replace the gasket and port cover on the recloser head after testing has been completed.
Figure 36. Using a manual closing tool to operate the recloser.
41
Form 6-LS Pole Mount Recloser Control Installation and Operation Instructions
Battery Test and Charging Procedures
Test Procedure for Uninstalled Battery
The entire process should be conducted in a clean environment, such as a repair shop.
Test Procedure for Installed Battery
Follow the procedure below to perform a battery test in the Form 6-LS control. The values in the test procedures are
based on testing at 25°C (77°F).
The condition of the Form 6-LS control battery can be determined by using the Battery Test function in the
BATTERY MENU. No external current/voltage meter is
necessary for testing.
Alarm Conditions:
• During a manual battery test a 5Ω, 55 watt resistor is
placed across the battery terminals for approximately 5 seconds. The Form 6-LS control measures the battery voltage, if the voltage drops below 22.8 VDC for one
full second, the ALARM LED (battery alarm) is
illuminated.
• When the Form 6-LS control is disconnected from AC
Refer to Table 11 and follow this procedure to perform a bench test on a control battery in a service shop:
1. Remove the control from service. Refer to Remove the Control from Service procedure within the Testing section of this manual.
2. Remove the battery from the control and carefully transport it to a suitable service facility.
3. Measure battery voltage.
4. Apply test load and measure battery voltage after 5 seconds of load to determine voltage drop. Refer to Table 11 for Bench Test Load Condition.
5. Remove test load.
If the battery fails the test or is at least four years old, it should be replaced. Refer to Table 11 for battery catalog part number.
power and the control battery drops below 23.5 VDC for 60 seconds, the ALARM LED will illuminate. If the battery voltage continues to decay and drops below 22 VDC, the Form 6-LS control will shut down.
Note: The battery test is blocked for 30 seconds upon power
Note: AC power can be either connected or disconnected for
Note: If the battery voltage drops below 19V, the battery must
up of the control.
battery test.
be charged by the external battery charger KA43ME7001.
1. Press the MENU button on the front panel.
2. Using the down arrow key, navigate to the BATTERY menu and press ENTER.
3. Using the down arrow key, navigate to the TEST
BATTERY menu and press ENTER.
4. Press the F4 button to test the battery. The battery test results will display in the battery metering menu.
Note: Voltage should be between 25–31 VDC with the
Under normal conditions, with AC connected and a
With AC connected and a discharged battery the
With AC disconnected and the battery supplying the
TABLE 11 Control Battery Bench Testing and Replacement Information
Bench Acceptable Battery Test Load Voltage Drop Catalog Amp/ Condition at End of Control Type Part # Voltage Type Hour for 5 sec. Test Load
Form 6-LS (high capacity) KME5-134-1 24v Lead 13 5 (two Acid 55 watt or less
12v
batteries)
higher voltage at colder temperatures.
fully charged battery, the charging current should be less than 20 mA.
current range should be between 20 and less than
450 mA. Current of 450 mA or greater indicates a
problem with the charging circuit on the pole mount power supply.
load, current will read -400 to -600 mA depending on
connected accessories.
ž
2v
42
S280-70-10
Battery Charging
If it is not possible to charge the battery with the control’s
built-in charger, a KME5-60-1 (120 VAC) portable bench
type battery charger kit is available, which includes the
KA43ME7001 Battery Charger (Figure 37) and the KME5-
325-1 Adapter Cable. Refer to S280-79-14KA43ME7001 PortableLeadAcid BatteryChargerInstructions for addi-
tional information.
IMPORTANT: Do not attempt to charge a lead acid
battery below 2 VDC with the KA43ME7001 charger.
The charger requires a minimal voltage to sense a battery is connected.
If the lead acid battery is below 19 VDC for over 2 days, replace the battery. The expired battery should be disposed of in an environmentally responsible manner. Consult local regulations for proper battery disposal.
Charge the battery with a KA43ME7001 (120 VAC) porta­ble charger as applicable:
• Form 6 Pole-mount Recloser Control (High Capacity)
– Use adapter KME5-325-1 to connect the two 12 volt batteries to the KA43ME7001 charger.
Note: A yellow LED indicator on the body of the charger
illuminates when charging. A green LED indicator illuminates when the charge is complete.
The charger senses when the battery voltage reaches 2.27 volts per cell, then the charge rate reduces to maintain a trickle charge.
The yellow LED flickers to indicate the battery has reached
a full charge. This process can take up to 24 hours.
Refer to Table 12 for additional battery charging accessories.
TABLE 12 Battery Charging Accessories
Description Catalog Number
120 VAC Battery Charger Accessory ......... KME5-60-1
IMPORTANT: Never connect a single 12 volt battery to
the KA43ME7001 charger. Use adapter KME5-325-1
with the battery assembly when connecting the charger to the two 12 volt batteries.
Figure 37. KA43ME7001 Battery Charger.
43
Form 6-LS Pole Mount Recloser Control Installation and Operation Instructions
Return the Control to Service
CAUTION: Equipment misoperation. Do not
connect this control to an energized recloser until all control settings have been properly programmed and verified. Refer to the programming information for this control. Failure to comply can result in control and recloser misoperation, equipment damage, and per­sonal injury. G110.3
After the required work is completed, disconnect the con­trol from the test set and follow this procedure to return the control to service:
1. While still in service shop, appropriate personnel must verify that all control settings are correct.
CAUTION: Equipment misoperation. Disconnect all control power sources prior to disconnecting or recon­necting the control cable from the control. Failure to comply can result in recloser misoperation at the time of disconnection or reconnection of the control cable to the control. T311.1
IMPORTANT: Prior to reconnecting the control cable, verify the control was removed from service in the exact order specified in the Remove the Control from Service section of this manual.
• In the SECTIONALIZING mode, once voltage is
restored, the LS is disabled until locally or remotely enabled. The control remains in the present state
prior to the loss of voltage. The SECTIONALIZING
unit will not close automatically.
Note: LS must be enabled via the ProView interface soft-
ware Loop Scheme Settings Dialog screen located in the Idea Workbench.
7. Disable GND TRIP BLOCKED.
A. Press the CHANGE button on the Operator Panel to
enter the CHANGE mode.
B. Depress the GND TRIP BLOCKED button within ten
seconds after entering the CHANGE mode.
Note: Once selected (or after ten seconds), the control
returns to normal operation.
8. Verify the control clock is set to the current time after AC power has been reapplied.
Note: The control clock may require resetting if the
operating power has been disconnected for more than thirty days. Refer to ServiceInformationS280-
70-4(ProView4.X.X)orS280-70-21(ProView5.X.X) Form 6 Microprocessor-Based Recloser Control Programming Guide for information on setting the
control clock.
.
2. Reconnect the ground cable to the control.
3. Control cable properly connected and supported.
4. Plug in the control battery.
Note: The Form 6-LS control will not power up until AC
power is applied.
CAUTION: Equipment misoperation. Verify that
the 120/240 VAC selector switch is correctly set
for incoming voltage. Failure to comply may cause
misoperation (unintentional operation) of the control
and/or equipment damage resulting in personal injury. T278.0
CAUTION: Equipment damage Form 6-LS (Loop Scheme). Do not connect 240 VAC to B or Y phases on terminal blocks TB7 or TB8. 240 Volts will damage inter-
nal components and cause control misoperation. T314.0
5. Verify the selector switch on the Power Supply/Battery Charger Board is set to the 115V position for 120 VAC incoming power.
6. Apply AC power to the control.
Note: In the event of loss of AC control power to the control
44
(without battery back-up power), the LS control will
reset to the following conditions when power is restored to the control:
• In the TIE Mode, once voltage is restored, the LS is
disabled until locally or remotely enabled. This is to ensure that the TIE recloser will not close automati­cally upon restoration of voltage from one source.
RECLOSER VTC INTERFACE
Control-Powered Type NOVA reclosers with serial numbers 100,000 and above, as listed in Table 13, require a VTC­ready control. They are equipped with a 19-pin control cable receptacle and can be identified by labels prominently displayed on the bottom of the recloser tank and on the side near the 19-pin receptacle, as shown in Figure 38.
For more information on the Control-Powered NOVA Interface, refer to ServiceInformationS280-42-1
CAUTION: Equipment Misoperation. The
control-powered NOVA reclosers that require a VTC interface must be used with VTC-ready controls. Failure to use a VTC-ready control will result in failure to trip or close. G144.0
S280-70-10
TABLE 13 Serial Number Break for Control-Powered NOVA Reclosers with VTC
Control-Powered NOVA Serial No.
NOVA15 100,000
NOVA27 100,000
NOVA38 100,000
Note: Control-powered NOVA reclosers with serial numbers
below those listed in Table 13 do not require a VTC­ready control. Refer to the recloser nameplate for the serial number.
Figure 38. Receptacle side view and bottom view of NOVA recloser tank, showing placement of VTC label.
45
Form 6-LS Pole Mount Recloser Control Installation and Operation Instructions
CONTROL VTC INTERFACE
All Form 5 and Form 6 recloser controls that have the control-powered interface with serial numbers over those
shown in Table 14 are VTC-ready. Catalog numbers for
these controls begin with KME5B, KME5D, KME6P2B, or KME6PBLS. These controls have a 19-pin control cable receptacle and can be identified by the following label dis­played on the bottom of the control cabinet, as shown in Figure 39.
Note: VTC-ready controls can also be used with control-powered
NOVA reclosers with serial numbers below 10,000.
VTC control retrofit kits are available for Form 5 or Form 6 recloser controls with serial numbers below those shown in
Table 14 to make these controls compatible with control-
powered NOVA reclosers that require a VTC interface. Catalog numbers for these kits are listed in Table 15. To order these kits or to obtain information on how to make a
Form 4C recloser VTC-ready, contact your Cooper Power
Systems representative.
TABLE 14 Serial Number Break for VTC-Ready Recloser Controls
Control Model Catalog No. Serial No.
Form 5 pole-mount control KME5B 12669
Form 5 LS control KME5D 2922
Form 6 pole-mount control KME6P2B 10015
Form 6 LS control KME6PBLS 10012
Note: Refer to the control nameplate for the serial number.
Figure 39. Bottom view of Form 6 recloser control showing location of VTC label.
TABLE 15 Catalog Numbers for Control VTC Retrofit Kits
Control Model Catalog No.
Form 5 KME5-728-1
Form 6 with serial number above 10,000 KME6-728-1
Form 6 with serial number below 10,000 KME6-728-2
Form 6 LS KME6-728-1
46
ADDITIONAL INFORMATION
CAUTION: This equipment requires routine
inspection and maintenance to ensure proper
operation. If it is not maintained, it can fail to operate properly. Improper operation can cause equipment damage and possible personal injury. G105.1
Replacement Kits
Replacement kits for the Form 6-LS control are available through the factory Service Department. To order these kits, refer to the Replacement Parts price list for catalog numbers and pricing. Contact your Cooper Power Systems representative for additional information and order procedures.
Factory-Authorized Service Centers
Factory-authorized service centers are located throughout the continental United States to provide maintenance, repair and testing services for controls and reclosers. For further information, contact your Cooper Power Systems representative.
S280-70-10
Factory Maintenance Classes
The factory service department offers a basic testing and troubleshooting course for the Form 6 microprocessor­based electronic recloser control. This course, taught by experienced service technicians, is held at the factory’s in-house training facility. For additional information, contact your Cooper Power Systems representative.
Type MET Recloser Control Tester
A 30-minute video cassette program KSPV7Kyle®Type MET Electronic Recloser Control Tester Operation and TestingProcedures is available as a supplemental training
aid for service personnel.
47
Form 6-LS Pole Mount Recloser Control Installation and Operation Instructions
©2012 Cooper Industries. All Rights Reserved. All Cooper logos, Cooper Power Systems, Kyle, ProView, Idea Workbench, Communications Workbench, and TCC Editor are trade-
marks of Cooper Industries in the U.S. and other countries. You are not
permitted to use Cooper trademarks without the prior written consent of Cooper Industries. IEEE® is a registered trademark of the Institute of Electrical and
Electronics Engineers, Inc., (IEEE). This publication is not endorsed or
approved by the IEEE.
One Cooper | www.cooperpower.com | Online
KA2048-629 Rev: 02
2300 Badger Drive Waukesha, WI 53188
Loading...