Cooper DF6000 User Manual

DF6000 Control Panel
User Manual
Fire
Assessed to: ISO 9001:2000 Certification number: 714h/01
Approved to: EN54-2 1997 & A1;2006 EN54-4:1997 & A1;2002 A2:2006
Document Drg Ref: PR200-04-513-15 Marketing Ref: CC1809a
0832 – CPD – 1060
DF6000 - USER MANUAL
2
Introduction to the Manual
This manual provides information on the installation, operation and maintenance of the Menvier DF6000 System.
Notice
The operating system of the DF6000 may be revised as a result of enhancements to the system software
or hardware. Revisions to this manual will be issued and supplied on request and should be logged
in the table supplied on the contents page.
Caution
Risk of explosion if battery is replaced by an incorrect type dispose
of the used batteries according to the instructions
Contact
Technical: 01302 303350
Service: 01302 303352
Sales: 01302 303303
DF6000 - USER MANUAL
3
Contents
Section 1 - System Installation and Design
Introduction 5 Project Planning 6 System Design Guidelines 7 Compatible Equipment 8 Detectors 9 Callpoints 10 Beacons and Sounders 11 Base Sounder 11 Stand Alone Sounders 12 Loop Powered Beacon 12 Compatible Interfaces 13 3 Channel I/O 13 1 Channel I/O 14 Zone Monitor Unit 14 Shop Monitor Unit 15 Spur Isolator 16 4 Way Sounder Circuit Controller 16 Micro Interfaces 17 Fan Controller Interfaces (FC18 / FC6) 18 Equipment Compatiblity 19 System Overview 20 Technical Specification 22 Optional Functions as per EN54 Pt 2 & 4 24 Optional Functions Not Approved to EN54 Pt 2 & 4 28 Cable and Wiring 29 Installation 30 Fixing Details 31 External Connections 32 Networking 33 Inputs/Outputs 34 Maintainance 36
Section 2 - Panel Assembly Information
Attaching Panel Door 38 Installing Optional Screen Door 39 Replacing Printer Paper Roll 40
Section 3 - Commissioning
Commissioning Mode 42 Configuration 43 Panel Fault Finding 44 Protocol 45 PC Comissioning Software 46
Section 4 - Panel Controls And Indicators
System Indicators 50 Panel Layout 51 Touch Screen Display 52 Panel Operation 53 Public (Access Level 1) 54 Evacuate (Access Level 2) 55 Silence Alarms 56 Mute Buzzer 57 Reset 57 Pre Alarms 58 Disabled Devices 58
y
View Faults 59 Enable / Disable (Others Menu) 59 Print 61 Lamp Test 62 Weekly Test 63 View Events 64 Check Auto Config 65 Replace Device 66 Test Device 67 Test Zone 68 Sounder Level Test Mode 69 Global LED Flashing On/Off 70 One Man Walk Test 71 Load CDR From Laptop 72 Download CDR To Laptop 73 Auto Learn 74 Erase Log 75 System Details 76 Analogue Levels 77 Printer Settings 78 Change Panel Number 79 Number of Panels In Network 80 Screen Cover 81 Programming I/O and Sounders 82 Sound Settings 83 Change Date/Time 84 Change Address Text 85 Change Zone Text 86 Change Panel Text 87 Configure Zones 88 Change User Code 89 Add Zone 90 Delete Zone 91 Add Device 92 Delete Device 93 Configure Heat Detectors 94 Network 95 Password Protection 96
Section 5 - Appendix
Spur Isolator 98 4 Way Sounder Controller 99 Zone Monitor Unit 100 Shop Monitor Unit 101 1 Way Input Output Unit 102 Detector Base Wiring 103 System Wiring 104 IP66 Wall Sounder 105 Internal Wall Sounder 106 Base Sounder 107 3 Way Input Output Unit 108 Loop Powered Beacon 109 Callpoint 110 EN54 Product Spec Label 111 Battery Disposal Instructions 112 CE Marking 113
DF6000 - USER MANUAL
4
Section 1
System Installation and Design
Section 1 - System Installation and Design
DF6000 - USER MANUAL
5
Introduction
DF6000 provides all of the sophisticated features required of a leading edge analogue addressable fire system along with the simple operation and neat installation demanded by installers and building users.
The panel can be flush or surface mounted and the generously sized metal back box allows ample facilities for rear or top cable entries. It is available in single two and four loop versions, with or without an integral printer.
In addition both passive and fully functional repeater panels are available.
A comprehensive range of ancillary devices is available to operate with DF6000, including optical, ionisation, photo-thermal and heat detectors, base mounted and stand alone sounders (including an IP67 version) a loop powered beacon and a wide range of input and output interfaces.
Each of the DF6000 system components has been specifically designed to operate as part of a DF6000 system, this provides an assurance that the panel, the detectors, the interfaces and the ancillaries are all fully compatible with each other and that the full range of system functionality is supported by each device.
Each loop of a DF6000 panel can accommodate up to 200 addresses. To comply with EN54 requirements no more than 512 addresses should be connected to a single panel. Each panel can indicate upto 96 zones. Panels are available with upto 4 detection loops, up to 126 panels can be networked together to form a single system capable of operating with over 32,000 devices.
Note:
Network systems fall outside the scope of EN54.
Section 1 - System Installation and Design
DF6000 - USER MANUAL
6
Project Planning
The following is a typical program and timetable for a DF6000 installation project, once the initial order has been received:
1. Project Meeting
Installer and user to be present; system specifications, schematic diagram and proposed circuit drawing to be available. DF6000 Installation and Commissioning Guide to be provided.
2. Equipment Fix
Typically 2 week's notice is required for equipment to be delivered. Cable to be installed and bases/back boxes to be fitted. Then fire detectors, callpoints, alarm sounders, isolator units and interface units to be installed.
3. Address Schedule
Schedule of sensor locations to be completed by installer and returned to enable system programming.
4. Auto Learn
Fire panel/repeater panels to be installed and terminated. System to be powered up by installer and auto learn mode activated (see Auto Learn section). System to be tested and verified by installer, prior to final commissioning.
5. Final Commissioning
Minimum 2 weeks notice is required from receipt of address schedule and commission request form. Cooper Fire service engineer to attend site implement/oversee the final commissioning procedures (see commissioning section), in conjunction with the installer.
Section 1 - System Installation and Design
DF6000 - USER MANUAL
7
System Design Guidelines
Guidelines
Systems should to the relevant local standards and codes of practice, for the UK this is BS5839 Pt 1. DF6000 meets all the relevant requirements of BS5839 Pt 1: 2002. Installation planning is simplified by the fact that every addressable DF6000 device contains an integral short circuit isolator. Care must be taken to ensure that local standards requirements regarding aspects such as loop coverage, area covered by a single spur and cable specification are observed.
There may be certain applications in which deviations from the code may be necessary and these must be listed on the commissioning certificate. (See commissioning section).
Loop Lengths
The maximum permitted loop length is 2 km measured from the near to the far terminals on the DF6000 motherboard PCB. There is no minimum limit to loop length. Any wiring spurs off the loop must be included within the 2 km limit. On long loop runs, the lengths of wiring rises and falls (between floors, down to manual callpoints) must be included. Remember to include these especially when taking loop lengths from plan drawings.
Loop Loading - Total Number of Addresses
The total number of addresses per loop is 200. this includes detectors, callpoints and all other addressable items (e.g. MPU, MIO, loop repeaters etc.) When designing systems its recommended that allowances are made for future expansion, Short circuit isolators are incorporated into every DF6000 loop device, including Smoke detectors, heat detectors, sounders, callpoints and interfaces. Therefore, no further fault protection is required, in the event of a single fault, none of the devices connected to the loop will fail to operate as the fault will be isolated by the two adjacent devices. Spur connected devices downstream of a cable fault will cease to function.
DF6000/PR Repeater Panels
Each repeater unit requires one address and consumes no more current from the loop than a smoke detector. The repeater also requires a local mains supply and incorporates battery backup.
Loop Loading System Verification
Unless a loop loading calculation has already been carried out, please contact our technical support department (01302 303350), before starting installation to verify that a proposed loop loading arrangement is acceptable.
Section 1 - System Installation and Design
DF6000 - USER MANUAL
8
Compatible Equipment
Section 1 - System Installation and Design
DF6000 system components
Order Code Description Dimensions (mm) DF6000/1 1 Loop DF6000 Panel 495 W x 400 H x 180 D DF6000/2 2 Loop DF6000 Panel 495 W x 400 H x 180 D DF6000/4 4 Loop DF6000 Panel 495 W x 400 H x 180 D DF6000/1/P 1 Loop DF6000 panel c/w integral printer 495 W x 400 H x 180 D DF6000/2/P 2 Loop DF6000 panel c/w integral printer 495 W x 400 H x 180 D DF6000/4/P 4 Loop DF6000 panel c/w integral printer 495 W x 400 H x 180 D DF6000/1/G 1 Loop DF6000 Panel Graphite finish 495 W x 400 H x 180 D DF6000/2/G 2 Loop DF6000 Panel Graphite finish 495 W x 400 H x 180 D DF6000/4/G 4 Loop DF6000 Panel Graphite finish 495 W x 400 H x 180 D DF6000/1/P/G 1 Loop DF6000 panel c/w integral printer Graphite finish 495 W x 400 H x 180 D DF6000/2/P/G 2 Loop DF6000 panel c/w integral printer Graphite finish 495 W x 400 H x 180 D DF6000/4/P/G 4 Loop DF6000 panel c/w integral printer Graphite finish 495 W x 400 H x 180 D DF6000/COV Hinged protective cover kit DF6000/PR Passive repeater for DF6000 MAS850 Sounder Base 102 Dia x 40 D MASC Cover for MAS850 102 Dia x 13 D MASB870 Base Sounder Beacon 114 Dia x 36 D MASB870-NT Base Beacon 114 Dia x 36 D MAS850LPS Wall Sounder 105 L x 105 H x 95 D MAS850LPS/WP IP66 Wall sounder 108 L x 108 H x 103 D MAB870 Addressable Beacon 95 Dia x 50 D MBG813 Surface / Flush Callpoint 85 L x 85 W x 53 D MBG817 Weatherproof Callpoint 108 L x 108 W x 65 D MIO324 3 Channel I/O Device 147 L x 88 W x 57 D MIO324T 3 Channel I/O Device 1 Address 147 L x 88 W x 57 D MIO324S 3 Channel I/O Device reset on silence 147 L x 88 W x 57 D MIO1240 1 Channel Output Unit (mains rated) 180 L x 130 H x 60 D MIU871 Zone Monitor Unit 150 L x 89 H x 58 D MIU871/ IS Zone Monitor Unit Intrinsically Safe 150 L x 89 H x 58 D MSU840 Shop Unit Interface 150 L x 89 H x 58 D MSI850 Spur Isolator 112 L x 41 H x 33 D MPU424 4 Way Sounder Circuit Controller. 300 L x 300 H x 74 D MAB800 Common Mounting Base For Analogue Detectors 104 Dia x 22 D MAP820 Optical Smoke Detector 101 Dia x 33 D MAH830 Multi Mode Heat Detector 101 Dia x 43 D MAOH850 Combined Photo Thermal Detector 101 Dia x 43 D MIU872 Micro Zone Monitor Unit 63 L x 35 H x 18.5 D MCIM-C Micro Callpoint Input Module 63 L x 35 H x 18.5 D MCOM-S Micro Sounder Output Module 63 L x 35 H x 18.5 D MCOM-R Micro Output Module Resetable 63 L x 35 H x 18.5 D MICM-NF Micro Analogue Non Fire Input Module 63 L x 35 H x 18.5 D
DF6000 - USER MANUAL
9
Detectors
Analogue Photoelectric Detector - MAP820
This is the most commonly used detector and is most suitable for detecting slow burning fires. The status LED can be programmed to either be permanently off under normal conditions or to pulse in order to confirm that it is in communication with the DF6000 control panel.
Analogue Photo/thermal Detector - MAOH850
This is a new addition to the Menvier range of detectors. It is the ideal detector for a multi-use environment as it has an excellent response to smouldering and fast burning fires. Photo/thermal detectors can be programmed for thermal only operation at certain times of day. The status LED can be programmed to either be permanently off under normal conditions or to pulse in order to confirm that it is in communication with the DF6000 control panel.
Analogue Heat Detector - MAH830
Heat detectors are suitable for dusty environments or environments where smoke is likely to be present under normal operating conditions. The MAH830 can be programmed to operate in A1R, BS or CS mode of operation depending on the required application and sensitivity requirements. The status LED can be programmed to either be permanently off under normal conditions or to pulse in order to confirm that it is in communication with the DF6000 control panel.
Section 1 - System Installation and Design
DF6000 - USER MANUAL
10
Callpoints - MBG813 / MBG817
The range of purpose designed callpoints for DF6000 consists of a surface callpoint, a flush callpoint and a surface weatherproof callpoint. A range of accessories is available including a hinged protective cover, resettable element kit and a flush bezel. The status LED can be programmed to either be permanently off under normal conditions or to pulse in order to confirm that it is in communication with the DF6000 control panel.
Section 1 - System Installation and Design
Flush mounted callpoint
MBG813
Weatherpoof callpoint
MBG817
Surface mounted callpoint
MBG813
DF6000 - USER MANUAL
11
Sounders and Beacons
A wide range of loop powered sounders and beacons are available to operate with DF6000 consisting of a combined sounder base with a maximum output of 95 dB(A), a standalone sounder with a maximum output of 100 dB(A) that is available in standard or weatherproof versions and a stand alone loop powered beacon.
For applications where a discreet dedicated sounder is required, a cover plate is available for the white base mounted sounder enabling it to be used as a stand alone wall or ceiling mounted sounder.
All of these devices are fully programmable via the sophisticated DF6000 multi stage cause and effect programming facilities.
All sounders have multiple selectable volume settings, the volume setting is controlled globally by the DF6000 panel and so can be altered without needing to access the sounder. Alternatively individual sounders can be set through the Menvier programming utility.
Base Sounder - MAS850
The MAS850 has been designed specifically to complement the latest generation of Menvier soft addressed detectors. it consists of a first fix bracket, and a main body which clips onto the bracket incorporating the sounder and a detector mounting base in a single composite assembly.
After the body has been clicked into place and connected, a detector or front cover is then added to complete a very simple quick and neat installation. The cover enables the MAS850 to be used as a discreet stand alone wall or ceiling mounted device. The sounder base design incorporates a mechanism that can be activated if required to lock either the detector or the cover into place to prevent unauthorised removal.
Section 1 - System Installation and Design
Base sounder
MAS850
Base sounder with MASC fitted
MAS850
Base sounder with detector fitted
MAS850
DF6000 - USER MANUAL
12
Stand Alone Sounders ­MAS850LPS / MAS850LPSWP
Stand alone sounders are ideal for applications wher
e greater sound outputs are required than can be achieved with a base sounder or for applications requiring a higher level of resilience or ingress protection. Two different versions are available standard version and an IP66 rated version.
Loop Powered Beacon - MAB870
A loop powered flashing beacon is available for applications where visual alarm indication is required such as areas of high ambient noise or buildings which are used by people who are hard of hearing.
Base Sounder Beacon - MASB870
Loop powered base sounder with a built in beacon where both sound and visual alarms are required. Taking 1 address
Base Beacon - MASB870-NT
Loop powered base beacon where visual alarm without sound are required. Taking 1 address.
Section 1 - System Installation and Design
Stand alone sounder
MAS850LPS
Stand alone sounder - weatherproof
MAS850LPSWP
Loop powered beacon
MAB870
Loop powered beacon
MASB870-NT
DF6000 - USER MANUAL
13
Compatible Interfaces
DF6000 has been designed to be suitable for a wide range of applications, various interfaces have been developed to enable the simple integration of other fire systems or building control and safety systems. The following devices are available:
3 Channel I/O device - MIO324
MIO324 has 3 input channels and 3 output channels, it is used to monitor up to 3 separate inputs from equipment such as sprinkler flow switches and also to provide 3 separately controlled volt free output contacts which are intended to be used to control external equipment such as air handling plant or access control systems. All inputs and outputs operate completely independently of each other and can be programmed using the sophisticated cause and effect capabilities of DF6000 to operate either globally or in response to activation of specific devices or specific inputs. Inputs are monitored for open and short circuits, a specific resistance is required to activate an alarm condition, fully open or short circuit conditions are monitored and generate a system fault signal. Inputs are suitable for use as fire signal inputs such as from a sprinkler flow switch, however they can also be used to monitor non fire inputs such as external keyswitches. Outputs are rated to switch a maximum of 1A resistive at 30 V dc. MIO324 fixes to a standard, deep, double gang back box and can be either surface or semi recess mounted.
MIO324T
This unit is identical in build to the MIO324 but this has been designed to take 3 addresses (this can be expensive in terms of outputs because it replies as 3 x 3 Channel I/O's), this means that text information can be allocated to each channel. It also allows each individual input and output to be disabled (by address). The maximum number of addressable MIO324T per loop is 6.
MIO324S
Once again this unit is identical with the MIO324 only taking 1 address. The programming is the same as the MIO324. This unit was designed so that the relay outputs reset on silence rather than full reset, thus enabling the user to interface this device with other fire panels and hence prevents locking up. The maximum number of addressable MIO324S per loop is 20.
Section 1 - System Installation and Design
3 channel I/O device
MIO324 / MIO324T / MIO324S
DF6000 - USER MANUAL
14
1 Channel I/O device with mains rated switching capability (MIO1240)
MIO1240 is a single channel input / output unit, the output is capable of switching up to 8 A at 230 V ac. Commonly used for applications such as door release contr
ols and plant shut down signalling the input is monitored for open and short circuits, a specific resistance is required to activate an alarm condition, fully open or short circuit conditions are monitored and generate a system fault signal. The input is suitable for use as a fire signal input such as from a sprinkler flow switch, however it can also be used to monitor non fire inputs such as an external keyswitch.
Zone monitor unit (MIU871)
MIU871 is designed to enable a zone of compatible conventional detectors and callpoints to be connected into the DF6000 loop, it is compatible with up to 20 Menvier conventional detectors connected via FXN520 bases. Please refer to local standards e.g. BS5839 Pt1:2002 for details of the maximum allowable area to be covered by a single spur / zone. MIU871 fixes to a standard, deep, double gang back box and can be either surface or semi recess mounted. When semi recessed only the front section protrudes giving a maximum 29mm depth.
MIU871/IS
Similar to the above but the detection zone has been programmed to accept a Zener barrier and zone of intrinsically safe detectors. End of line for this zone now becomes 6K8 and the diode in the detector base must be removed.
Section 1 - System Installation and Design
1 channel I/O device
MIO1240
Zone monitor unit
MIU871 / MIU871/IS
DF6000 - USER MANUAL
15
Shop Unit Interface - MSU840
MSU840 accepts a zone of conventional detectors plus an unlimited number of callpoints which can be connected to the same input as the detectors or a separate callpoint input if requir
ed. There is also a
facility to connect a power supply, which can then be monitored for fault.
In addition it has the facility to connect two circuits of conventional polarised sounders, which are monitored by means of an end of line resistor and powered in alarm conditions from the external power supply. The sounder circuits can be programmed to operate in pulsed, continuous or time delayed mode.
Please refer to local standards e.g. BS5839 Pt 1:2002 for details of the maximum allowable area to be covered by a single spur / zone.
Note: This unit must always be used with a 24 V power suply
Section 1 - System Installation and Design
Shop unit Interface
MSU840
DF6000 - USER MANUAL
16
Spur Isolator - MSI850
Enables soft addressing to work when the loop contains spurs, it contr
ols the addressing operation so that when the system reaches a spur, all devices on the spur are allocated an address before it continues addressing the loop. The device also incorporates a short circuit isolator. Because each device contains a short circuit isolator only 1 is required at the start of each spur. MSI850 is mounted on a standard deep double gang back box (supplied) please refer to BS5839 Pt 1:2002 f
4 Way Sounder Circuit Controller - MPU424
MPU424 provides power for 4 separately controllable conventional sounder circuits, each circuit can be separately programmed. MPU424 is designed to greatly simplify installation in applications where specialist sounders or beacons are required since it powers the sounders and allows full control of the sounder operation without having to wire the sounder back to the DF6000 control panel.
A 4 way unit takes up a single address but each circuit can be independently controlled. An MPU424 unit requires a local un-switched 230 V supply and incorporates a back up battery to 24 hours of standby operation followed by a minimum of 30 minutes of full alarm ringing. A standby of 72 hours can be achieved at the expense of reduced load capability.
Section 1 - System Installation and Design
Spur Isolator
MSI850
4 Way sounder circuit controller
MPU424
DF6000 - USER MANUAL
17
Micro Interfaces
A range of micro interfaces modules are also available:
MCIM
Is a competitively priced input module, designed to enable a Menvier panel to accept input signals from external devices such as key switches and sprinkler flow switches. It is extremely compact and therefore ideal for incorporation into other equipment. The maximum number of addressable MCIM per loop is 20.
MCOM
Is a competitively priced output module, designed to enable a Menvier panel control external devices such as door holders or access control systems. It is extremely compact and therefore ideal for incorporation into other equipment. The maximum number of addressable MCOM per loop is 20.
MIU872
Is a compact single zone input, soft addressed, microinterface, incorporating integral short circuit isolators. It is fully compatible with the current range of Menvier analogue fire detection panels. It is suitable for interfacing a zone of up to 20 conventional Menvier detectors onto a Menvier analogue fire panel. It will operate with any Menvier conventional detector in configuration with a schottky diode type base.
MCIM-C (Identified as a Callpoint)
Is a compact input module used to accept input signals from external equipment such as beam detectors, flow switches, valve monitor switches etc. The maximum number of sounder devices per loop is 200.
MCOM-S (Identified as a Sounder)
Is a compact single channel output unit. This device is identified as a sounder output by a Menvier addressable panel. The maximum number of sounder devices per loop is 60.
MCOM-R
Is a compact output module used to control or signal external equipment which require removal of power for reset purposes. The maximum number of addressable MCOM-R per loop is 20.
MICM-NF
Is a compact single channel input unit. This device is identified as a non-fire input module by the Menvier addressable panel. The maximum number of addressable MICM-NF per loop is 200. Complex cause and effect can still be achieved using the latest site installer software without any indication on the panel. However the action will still be seen in the event log. Ideally suited for non fire applications.
Section 1 - System Installation and Design
Micro interfaces
MCIM / MCOM / MIU872 / MCIM-C / MCOM-S / MCOM-R / MICM-NF
DF6000 - USER MANUAL
18
Fan Controller Interfaces (FC18 / FC6)
FC18 and FC6 Interface is designed to work with the Menvier range of analogue fire alarm control panels, providing the capability to control and display the status of AHU fans.
FC18 and FC6 Interface is connected to a Menvier analogue addressable fire alarm control panel by means of the comms loop, utilizing only one address whilst providing the ability to monitor and control up to six AHU Fans.
Each FC6 and FC18 Interface incorporates its own CPU specifically configured to control the relevant input and output logic making programming quick and easy via the ‘CAPPER’ software or site installer.
Using the CAPPER software or site installer, each individual Fan Control channel on the FC6 is programmed to an output and feedback input field device to control and monitor the status of an AHU fan.
Features
> Convenient loop mounting > Comprehensive LED display > Surface/rack mounting options > Key operated auto/manual operation > Comprehensive software cause and effect
Section 1 - System Installation and Design
Fan controller interface
FC6
Fan controller interface
FC18
DF6000 - USER MANUAL
19
Equipment Compatibility
Detectors
Loop wired detectors must be of the Menvier 800 series soft addressed analogue type. FXN500 series conventional detectors can be connected via an MIU871 interface. The connection of other detector types via an MIU871 interface is not recommended.
Callpoints
Loop wired callpoints must be the Menvier 800 series soft addressed analogue type, FX200 series conventional callpoints can be connected via an MIU871 interface. The connection of other callpoint types via an MIU871 interface is not recommended.
Sounders
Loop powered addressable sounders must be of the Menvier 800 series soft addressed analogue type. Conventional sounders can also be connected either to the conventional sounder circuits at the panel or to the loop via a MPU424 addressable sounder controller interface providing they meet the following:
1. They are suitable for operation between 18 V and 28 V.
2. They are polarised and suppressed.
3. The total alarm load is less than the rating of the panel / alarm power interface. Note:
It is possible to use devices outside these requirements if they are supplied with power from a separate source and switched via a suitable relay.
Relay circuits
Additional relays can be added to the DF6000 system by using either MIO1240 or MIO324 relay units. Relays / Auto-dialers and auxiliary equipment A wide variety of relays and other equipment can be connected to the DF6000 system, but you should note the following constraints:
1. DF6000 provides monitored outputs to drive fire and fault relays mounted in external equipment.
External relays should be suppressed. If a non-suppressed relay is used then a diode can be connected. to suppress any reverse EMF on the release of the relay which might cause the panel to malfunction.
2. A 24 V dc output is provided at the panel to make it easy to connect ancillary equipment. Although the
panel can supply a continuous quiescent load of up to 30 mA, BS5839 precludes this practice and any ancillary equipment you connect should only consume power in the alarm or fault mode to meet the requirements of BS5839.
Additional instructions for electromagnetic compatibility
When used as intended this product complies with EMC Directive (89/336/EEC) and the UK EMC regulations 1992 (SI 2372/1992) by meeting the limits set by the standards BS5406 (Pt 2 & 3) 1988, EN50130-4 immunity and EN 61000-6-3 emission requirements. The following installation guidelines must be followed.
1. External cables must be connected using the cable entries or knockouts provided.
2. When routing external cables inside the product they must be
a) Kept as short as possible b) Routed close to the housing c) Kept as far as possible from the electronics
Any modifications other than those stated in this manual, or any other use of this product may cause interference and it is the responsibility of the user to comply with the EMC and low voltage directives.
Section 1 - System Installation and Design
DF6000 - USER MANUAL
20
System Overview
Simple User Interface
The main element of the user interface with DF6000 is a large (120mm x 90mm visible area) touch screen display, which provides comprehensive user information and also acts as a multifunctional keypad.
Comprehensive context sensitive help information is provided throughout the menus to assist unfamiliar users with system operation.
The DF6000 touch screen display automatically reconfigures to suit the selected function, for example, if the change device text menu option is selected, the touch screen is automatically formatted as a full QWERTY keyboard to enable fast and simple text entry.
The use of the touch screen display enables a wide range of user and engineering facilities to be incorporated into the panel whilst still offering simple operation.
As well as a large format LCD display providing full system status information, the panel incorporates 96 traditional zone indication LED's to provide clear information about the status and spread of a fire even to a user who is completely unfamiliar with the operation of the system.
In addition there are a number of system status LED's designed to give clear status information to non technical users.
User Configuration And Maintenance Facilities
DF6000 has comprehensive facilities for on site system configuration, whereby the user can add or remove simple devices or change device text directly via the panel, without the need for a service engineer to visit site. For initial configuration or major system changes special PC configuration software is available enabling Cooper Lighting and Safety personnel to do this more efficiently than can be achieved using the system screen. Exiting configurations can be uploaded to the PC so that changes can be made to the existing system rather than having to revert to initial files.
Sophisticated Sounder Control Facilities
DF6000 has the ability to support highly complex ringing pattern requirements. Multistage cause and effect programming is possible whereby each addressable sounder or output interface can be programmed independently if required and can be set to respond to specific addresses, specific detection zones, specific panels on a networked system or standard global ringing.
The panel supports 3 separate sets of programming per sounder and each stage can be triggered differently For example, if a single detector is triggered the panel can be programmed such that the sounder nearest to the detector operates immediately and continuously, the remaining sounders in the affected zone operate in pulsed mode and the other sounders delay for a selectable period to allow the cause of the alarm to be investigated before global ringing commences.
Section 1 - System Installation and Design
DF6000 - USER MANUAL
21
Spur Tolerant Soft Addressing
DF6000 utilises intelligent soft addressing technology to gr
eatly simplify the installation and commissioning processes. Once the system has been installed and the autolearn menu selected, the DF6000 control panel will automatically scan the detection loops and allocate each device with an address number corresponding with its position on the loop, this avoids the traditional need for manual addressing of the system devices which is time consuming and provides a potential for error.
A major innovation with DF6000 is the ability to incorporate spurs of analogue devices which are fed from the main loop by utilising a spur isolator. Whenever the panel detects a spur, it breaks from allocating address numbers to the loop wired devices, allocates address numbers to each of the devices on the spur in sequence and then continues to address the devices on the main loop. Every DF6000 analogue device incorporates an integral short circuit isolator ensuring maximum system integrity. A single short circuit will not disable any loop-mounted devices, the isolators in the devices each side of the short circuit will operate and the DF6000 control panel will drive communication from both ends of the loop. The spur isolator also incorporates a short circuit isolator such that in the event of a short circuit on the spur, the integrity of the main loop will not be compromised. Please refer to local standards e.g. BS5839 Pt1:2002 for details of the maximum allowable are to be covered by a single spur.
Simple Future Expansion
DF6000 is designed to ensure simplicity of future expansion. If an additional device is added after the system has been programmed, the DF6000 will allocate the next available address, it will not alter any of the existing address numbers allocation thus enabling simple updating of as fitted drawings etc. Similarly if a device is removed, the relevant address is saved as a spare address for future use, the addresses of the remaining devices are not altered.
Integral Power Supply and Battery
The DF6000 panel is designed for ease of installation, the power supply and battery are integral to the main control panel so only a single panel is required even on large 4 loop systems.
Optional Printer
DF6000 panels are available with optional built in printers. Where a printer is fitted, it is housed behind a printer cover door, which can be opened by means of a special tool (supplied) to provide simple and safe access to the printer paper roll without exposure to any live equipment. Paper replacement is extremely simple due to the drop in loading method and auto feed printer design, the paper roll is simply dropped into the purpose designed cradle and the end of the roll is then offered up to the printer, which will then automatically load the paper ready for use. The printer can be set to either print automatically or to print on demand When a printer is not fitted, a removable, flush fitting blanking plate is used to cover the printer paper aperture to enhance the appearance of DF6000 and to preserve its ingress protection rating.
Optional Hinged Lockable Cover
With a standard panel, access to all panel functions is controlled by a series of pass codes, which are entered via the touch screen display, for maximum security, a facility is built into the DF6000 to enable the user to alter the user pass code as required. For applications where a high level of resilience is required, a clear hinged lockable front cover is available which allows the screen and all of the system status indicators to be clearly seen but prevents access without first unlocking the cover. A single concealed locking mechanism provides access to both the printer door and the optional display cover where a hinged cover is fitted, additional buttons are provided to scroll the display and to silence the fault buzzer without opening the lockable cover
Section 1 - System Installation and Design
DF6000 - USER MANUAL
22
Technical Specification
Section 1 - System Installation and Design
Power Supply (Approved EN54 pt 4)
Mains
Nominal voltage 230 Vac + 10%, -15% Nominal current 75mA Maximum current 750mA Input fuse R1 NTC SG39 Imax 4 Amp Output voltage including tolerances 26 V = 18.5 to 29.5 V
26 V RAW = 18.5 V to 29.5 V 5 V Output = 4.6 V to 5.5 V
Ripple voltages 26 V = 800m V
26 V RAW = 800m V 5 V Output = 430m V
Maximum loadings 26 V O/P = 0.98A
26 V RAW O/P = 1.7A 5 V = 0.5A
Standby current (4 loops loaded) 26 V = 280 mA
26 V RAW = 150 mA 26 V = 280 mA 26 V RAW = 150 mA
5 V = 43 mA DF6000 is protected by an internal thermal device, this requires no maintenance * I max a, I max b and I min = Current as specified in BSEN54-4 Published 2006 (amendments 1 and 2)
Batteries
Number of batteries 2 Manufacturer YUASA NP12-12 Capacity 12 Ah Battery fuse 6.3A Anti-Surge (F4) Maximum battery current 3.5 Amps Standby current (mA) 175 (4 loops), 125 (2 loops) Maximum charging current to the batteries 1.0amp Float voltage 27.4 V Final voltage 21.0 V Charging characteristics Constant voltage with 0.970A
limit with temperature
compensation Maximum current drawn from the batteries (when the mains is not available) 3.5Amps Deep discharge protection 20.6 V Battery Internal Impedance Fault >0.5 ohms
Inputs
Addressable loops Max number 1 - 4 Max loop load per loop 220 ma Max number of addressable devices per Loop 200 Class change Operated by external volt free contact
DF6000 - USER MANUAL
23
Terminal Blocks: Do not use excessive force when tightening the screws on the terminal block
Risk of explosion if battery is replaced by an incorrect type dispose of the used batteries
according to the instructions
Section 1 - System Installation and Design
Outputs
Conventional sounder circuits Number of sounder circuits 4 Total sounder Load 1.5 Amps Sounder circuit fuses (F1/2/3/4) 1.6 Amp (Quick Blow) End of line resistor 6k8
Fire Protecting Equipment
Max load 60 ma Fused (PTC3) 100mA polyswitch End of line resistor 6k8
Fault Routing Equipment
Max load 30 ma Fused (PTC1) 100mA polyswitch End of line resistor 6k8 Auxiliary Relays - The auxiliary relays provide fused volt free change over contacts. These contacts are not monitored. Max load 24 V 1 Amp Fuse (PTC4) 1.35 Amps polyswitch Auxiliary 24 V Supply Nominal voltage 24 V ±10% Fuse (PTC5) 100 mA polyswitch Maximum current 30 mA This output is not to be used for fire protecting equipment or fire alarm routing equipment any power taken from the alarm system will effect the standby duration RS485 Port - Serial output port for driving DF6000 repeater panels, mimics etc.. This output is short circuit protected Max cable length 2 Km Min recommended cable size 1mm² (Screened) RS232 Port - Serial output port for driving DF6000 repeater panels, mimic etc. This output is short circuit protected Printer (Optional) Type High speed thermal Number of characters per line 40 Type of paper 58mm x 46mm Thermal Roll Replacement paper roll order code ADF6PRINTERPAPER
Mechanical Specification
Weight incl batteries 18kg, excl batteries 9kg Dimensions (standard batteries) 495mm(L) x 395mm(H) x 180mm(D) Type of material (backbox) Mild Steel (power coated) Type of material (Facia) PC/ABS Flammability rating UL 94 V0 Total number of knockouts 51 Diameter of knock out 20mm Anti-Tamper cover (optional) Weight : 250g
Material used : Poly Carbonate
Flammability rating : UL 94 5VA
DF6000 - USER MANUAL
24
Optional Functions as per EN54 Pt 2 & 4
DF6000 is approved to EN54 Parts 2 & 4 including all the following options which can be selected as required
Panel Outputs
Panel Sounders: (option 7.8 EN54 Pt 2)
Two pairs of outputs are provided. ONLY polarised equipment should be used. Ensure the polarity of the connections are observed at all times and end of line resistors (6K8 5%) are fitted for correct operation. The total alarm load across all sounder outputs = 1.5 Amp All outputs are fused with 1.6 Amp Glass fuse Alarm devices should be spread equally across the 4 sounder circuits.
WARNING: Do not exceed the rated output current
Output Fire Alarm Routing Equipment (option 7.9 EN54 Pt 2)
This output, which is fused, and monitored using a 6.8k end of line resistor, is used for the automatic transmission of the fire signals to fire alarm routing equipment (e.g. fire brigade). It operates by providing 24 V output to an auxiliary device (e.g. relay). It is current limited to 30 mA using a resettable polyswitch. Class change and test conditions do not operate this output. If operated under a fire alarm condition, the indication will be displayed on the Touch screen display and will remain until the fire alarm is reset. Ensure the polarity of the connections are observed at all times and end of line resistors (6k8 5%) are fitted for correct operation.
Output to Fire Alarm Protecting Equipment (option 7.10 EN54 Pt 2)
This output, which is fused, and monitored using a 6.8k end of line resisters used for the transmission of the fire signals to controls for automatic fire protecting equipment (e.g. Door released units etc). It operates by providing 24 V output to an auxiliary device (e.g. relay). It is current limited to 30 mA using a resettable. polyswitch. Class change and test conditions do not operate this output. If operated under a fire alarm condition, this output remains energised until the fire alarm is reset. Ensure the polarity of the connections is observed at all times and end of line resistors (6k8 5%) are fitted for correct operation.
Output to Fault Warning Routing Equipment (option 9.4.1c EN54 Pt 2)
This output, which is fused and monitored using 6.8k end of line resistor, is used for the transmission of fault signals to fault warning routing equipment This output is monitored using 6k8 end of line resistor and it current limited to 30 mA.Under normal condition it operates by providing 12 V dc which can be connected directly to a 12 V auxiliary device (relay). It is current limited to 30 mA. Under fault conditions or even if the DF6000 is powered down, this output will be switch to OV. Ensure the polarity of the connections is observed at all times and end of line resistors (6k8 5%) are fitted for correct operation.
Delays to Outputs (option 7.11 of EN54 Pt 2)
The DF6000 has the option to delay the operation of panel sounders, the fire routing equipment output and the fire protecting equipment. This delay is selectable using the DF6000 site installer download software .The delay is configurable in increments of 1 minute up to a maximum of 10 minutes. This delay can be enabled and disabled at access level 2. The DF6000 has the facility for a specific callpoint to override this delay by programming this callpoint via an input interface to provide an evacuate signal using DF6000 site Installer.
Section 1 - System Installation and Design
DF6000 - USER MANUAL
25
Dependencies on More Than One Alarm Signal - Type C (option 7.12.3 of EN54 Pt 2)
The DF6000 has the facility to inhibit the operation of the output sounders, output to fire r
outing equipment and the output of the fire protecting equipment until one more confirmatory signals are received from different zones. This feature is programmable using DF6000 site installer software.
Alarm Counter (option 7.13 EN54 Pt 2)
The panel records the number of instances that it enters the fire alarm condition. This is abbreviated in the touch screen by "AC" and it is displayed in the fire window at access level 2. This counter can only be reset by the manufacturer.
Optional Auxiliary Board VDS Requirement (option not required by EN54)
This board can be connected to an extinguishing system as well as a fire brigade control panel. This board has been tested and approved in according with DIN14661 and DIN 14675.
Input / Outputs to Fire Brigade Panel
Outputs
Output 1: Fire Protecting Equipment Operated "Extinguishing On"
This output is ON in alarm condition to indicate that the DF6000 control and indicating equipment has operated the fire protecting equipment (option 7.10 of EN54 Pt 2).
Output 2: Fire Routing Equipment Operated "Fire Brigade Link"
This output is ON in alarm condition to indicate that the DF6000 control and indicating equipment has operated the fire routing equipment (option 7.9 of EN54 Pt 2).
Output 3: Disablement of Fire Protecting Equipment
This output is ON to indicate that the fire protecting equipment has been disabled either by the DF6000 control and indicating equipment or the fire brigade panel.
Section 1 - System Installation and Design
DF6000 - USER MANUAL
26
Output 4: Disablement of the Fire Routing Equipment
This output is ON to indicator that the fire r
outing equipment has been disabled either by the
DF6000 Control and indicating equipment or the fire brigade panel.
Output 5: Reset from Fire Alarm Condition
This output is ON to indicate that the DF6000 control and indicating equipment is in alarm condition. This output will remain on for at least 15mins after reset or when the reset has been activated from the fire alarm brigade panel
Output 6: Disablement of Sounders
This output is ON to indicate that the sounders have been disabled either by the DF6000 control and indicating equipment or the rire brigade panel
Inputs
Input 1: Reset
This input is used to reset the control and indicating equipment
Input 2: Testing of Fire Routing Equipment
This input is used to test the output to the fire routing equipment
Input 3: Disablement of the Fire Routing Equipment
This input is used to disable the fire routing equipment if the DF6000. Once the FRE is disabled from this interface, it can never be enabled from the DF6000 control panel
Input 4: Disablement of the Fire Protecting Equipment
This input is used to disable the fire protecting equipment of the DF6000. Once the FRE is disabled from this interface, it can never be enabled from the DF6000 control panel
Input 5: Disablement of Sounders
This input is used to disable the sounders of the DF6000. The disablement of sounders from the fire brigade panel can be re-abled from the DF6000 control panel only when the system is not Alarm State.
Section 1 - System Installation and Design
DF6000 - USER MANUAL
27
German Interface Electrical Characteristics
Inputs
The inputs are designed to be actioned in one of two ways, see list below:
First: A change in logic state ie. switch toggled on / of
f.
Second: Logic pulse ie. nominal state logic high, then logic low > 200mS then return to logic high.
all inputs are held high via a weak pull up (logic high), the action of short circuiting any of the five inputs to there respective 0v will result in a logic low.
1: reset -> logic pulse 2: FRE relay test -> logic pulse 3: FPE disable -> logic state change 4: FRE disable -> logic state change 5: Acoustic disable -> pulse logic
Monitored Inputs
In Fault / Extinguisher Active
-> End Of Line resistor 3K3.
-> 680 Ohm across input to actiavte input
Relay Outputs
Normal status -> Input sees a 3K3 resistor. Active status -> Input sees a 680 ohm resistor.
Outputs 1: Extinguisher released -> output high 26 V 2: FRE operated 3: FPE disabled 4: FRE disabled 5: Panel in fire, will remain on after panel soft reset for > 15 minutes, or extinguish immediately with
interface reset
6: Disable all sounders.
Section 1 - System Installation and Design
DF6000 - USER MANUAL
28
Optional Functions Not Approved to EN54 Pt 2 & 4
Italian Mode: (option not required by EN54 Pt 2)
This mode can be programmed at access level 3. This relates to points 12.2(a) and 12.2(b) of the Internal Italian Ministerial Decree 9th April 1994 which states that in the event of a fire detection from 2 or more detectors or from an MCP there should be a 2 minute delay before output activation otherwise in the event of a fire detection from any one detector there should be a 5 minute delay before output activation, provided that the fire event is not acknowledged. These delays apply to siren activation as well as the shutting down/activation of other external equipment and additionally the legislation states that these delays should be adjustable depending on the type of activity being carried out within the building.
For example, if there was a fire detected from a single detector then we should start a 5-minute (adjustable) delay (T2). If however a fire is detected from a second detector or a call-point the delay should automatically revert to 2 minutes (adjustable) (T1). In this scenario the value of (T1) is critical. To keep things simple, let's assume that we set T1 = 2 minutes and T2 = 5 minutes.
Swedish Mode (option not required by EN54 Pt 2)
This mode is programmed at access level 3. One of the Swedish requirements is that access level 2 and 3 is only avalailabe by the access of the keyswitch. The key switch is wired to the class change input.
Commission per Loop (option not required by EN54 Pt 2)
This mode is programmed at access level 3. This allows the commissioning engineer to auto learn one loop at the time
Alarm Verification (option not required by EN54 Pt 2)
This mode is programmed at access level 3.This has the flexibility to delay the activation of detectors by 30 seconds. In the event of an alarm from a detector, the led of the detector will be illuminated and no alarm will be displayed on the panel. The detectors are checked continuously for 30 seconds. If after this time, the detector is still in alarm, the output will be activated otherwise the detector will be reset.
Timer T1/T2 (option not required by EN54 Pt 2)
This mode is set on at access level 3 and is a commonly used by eastern european countries.
In the event of a fire the timer T1 can be set from 0 to 3 min where the alarm will be displayed on the panel and no output activation, if during this time the alarm is acknowledged then timer T2 can be set from 0-10 min where the alarm can be investigated and alarm reset. However if timer T1 and T2 time out during alarm activation, the outputs will be activated.
Timer T1/T2 with callpoint Override (option not required by EN54 Pt 2)
This is similar to the above except a callpoint alarm will activate the output instantly
Section 1 - System Installation and Design
DF6000 - USER MANUAL
29
Cable and Wiring
Only the cable types listed below are allowable for loop connections.
1. Enhanced Fire TUF
2. Fire TUF™
3. FP200
4. MICC
When choosing your preferred cable type, you must take note of the following cable and wiring requirements.
1. The cable must be 2 core screened with an over sheath.
2. Maximum loop length with any of the above cables is 2 km
3. Maximum volt drop must be limited to 7 V.
4. The conductors should be 1.5mm minimum an no larger than 2.5mm
5. Multicore cable should not be used for detector wiring.
6. Different loops should NEVER be run within the same cable.
7. Loop feeds and returns should never be used within the same cable.
Cable Resistance
Cable Anchorage
The mains cable must be fixed securely with a 20mm cable gland. Remove a suitably located knockout feed the cable through the gland and bolt the gland to the DF6000 backbox as shown. Secure the cable to the side of the box using the cable clip provided.
NOTE: The mains cable tail ends must be insulated to prevent dangerous conditions arising in the event of accidental switching on of the mains supply.
Section 1 - System Installation and Design
Core Diameter Typica l FP200 Resistance
1.0mm² 18.1 Ohms/km/Core
1.5mm² 12.1 Ohms/km/Core
2.5mm² 7.41 Ohms/km/Core
4.0mm² 4.61 Ohms/km/Core
DF6000 - USER MANUAL
30
Installation
the panel should be installed in a clean, dry, reasonably well ventilated place, and not in direct sunlight. Temperatures in excess of 40°C and below 5°C may cause problems, if in doubt consult Cooper Lighting and Safety. The panel should be located away from any potential hazard, in a position where it is readily accessible to authorised staff, and the fire services, ideally on the perimeter of a building near a permanent entrance. Mount the panel to the wall using the drill template provided. Do not drill through the panel to the wall as dust will contaminate the circuitry.
Installation Guide ! Never carry out insulation tests on cables connected to electronic equipment. ! DO NOT OVER TIGHTEN TERMINAL CONNECTOR SCREWS ! Always use the correct type of cables specifically designed for the operation of fire detection and
alarm circuits.
! Always adhere to volt drop limitation when sizing cables ! Always observe polarity throughout. Non colour coded conductors should be permanently identified. ! Screen continuity must be maintained throughout the entire loop circuit including at each junction
point and at each device, terminals are provided on each device to facilitate this.
! The screen should be earthed at the connection point provided at the DF6000 panel and not at any
other point. Both the loop start and the loop end must be connected to the appropriate earthing points. Care must be taken to avoid connecting the screen to the earthed body of any metal devices, enclosures or cable containment. The screen or drain wire of the loop cables should not be considered as safety earth and therefore should not be connected to terminals marked with the earth symbol, except at the panel, and should not be insulated with green and yellow sleeving.
! DF6000 utilises intelligent soft addressing technology to greatly simplify the installation and
commissioning processes. Once the system has been installed and the autolearn menu selected, the DF6000 control panel will automatically scan the detection loops and allocate each device with an address number corresponding with its position on the loop, this avoids the traditional need for manual addressing of the system devices which is time consuming and provides a potential for error.
! It is of vital importance that accurate details are kept of the exact wiring route in order to determine
which address has been allocated to each device.
Section 1 - System Installation and Design
Loading...
+ 84 hidden pages