Cooper CF2000 Installation Manual

Page 1
CF2000
INSTALLATION MANUAL
Wheatley Hall Road Doncaster South Yorkshire DN2 4NB
Tel 01302 321 541 www.cooperfire.com
Assessed to ISO 9001:2000 Certification number 714h/02
Document Drg Ref PR200-50-502-20
QUALITY
MANAGEMENT
0832 – CPD – 1089
EN54-2 1997 & A1;2006 EN54-4:1997 & A1;2002 A2:2006
Approved to
Page 2
Introduction to the Manual
CF2000
Analogue Addressable Fire Detection System
This manual provides information on the installation, operation and maintenance of the Cooper Fire Systems CF2000 System.
NOTICE
The operating system of the CF2000 may be revised as a result of enhancements to the system software or hardware. Revisions to this manual will be issued and supplied on request and should be logged in the table supplied on the contents page.
Introduction
CAUTION
RISK OF EXPLOSION IF BATTERY IS REPLACED
BY AN INCORRECT TYPE DISPOSE OF THE USED BATTERIES ACCORDING TO THE INSTRUCTIONS ( Appendix Page 92 )
Page 3
Contents
Contents Page
1.0 System Design & Installation 5
Introduction 6 Project Planning 7 System Design Guidelines 8
Compatible Equipment 9 Detectors 10 Call Points 14 Sounders 16
Interfaces 17
3 Channel I/O 17 1 Channel I/O 17 Zone Monitor Unit 18 Shop Unit Interface 18 Spur Isolater 19 4 Way Sounder Circuit 19
20 21 24 26 28
Equipment Compatiblity System Overview Technical Specification Optional Functions External Connections Installation
29
Fixing details
30
System Wiring
31
2.0 Commissioning CF2000
33
Commissioning Software
34
Panel Fault Finding
38
Protocol
39
3.0 Panel Controls and Indicators
40 41 42 43 44 44 46 47 48 50 51 52
Panel Controls and Indicators System Healthly View Event Fire Event View Fires View Pre-Alarm View Fault View Disabled Address View Disabled Zone View Disabled I/O View Log Operations
Soft Reset
53
Evacuate
54
Silence Alarms
55
Lamp Test
56
Weekly Test
57
Page 4
Contents
Contents Page
Access Level 2
Commissioning
59
Panel Settings
Erase Log
60
Change Password
61
Change Lanuage
62
Date Time
63
System Details
64
Testing
Testing Device
65
Test Zone
66
Test Sound Levels
67
One Man Walk Test
68
Global Flashing LED
69
Analogue Levels
70
Device Config
71 72
Add Device Delete Device
4.0 Appendix
73
74
75 76 77 78
79
80 81 82 83 84
85 86
Spur Isolator 4 Way Sounder Controller Zone Monitor Unit Shop Monitor Unit 1 Way Input Output Unit Sensor Base Wiring System Wiring IP66 Wall Sounder Internal Wall Sounder Base Sounder Wiring 3 Way Input Output Unit Loop Powered Beacon Call Point
CE Marking
Battery Disposal Instructions
87 88
Page 5
System Installation and Design
Section 1
5
Page 6
Introduction
CF2000 provides all of the sophisticated features required of a leading edge analogue addressable fire system along with the simple operation and neat installation demanded by installers and building users.
The panel can be flush or surface mounted and the generously sized metal back box allows ample facilities for rear or top cable entries. It is available as a two loop panel with or without an integral printer.
A comprehensive range of ancillary devices is available to operate with the CF2000 panel, including Optical, Ionisation, photo-thermal and heat sensors, callpoints and a comprehensive range of interfaces.
Each of the CF2000 system components has been specifically designed to operate as part of a CF2000 system, this provides an assurance that the panel, the sensor, the interfaces and the ancillaries are all fully compatible with each other and that the full range of system functionality is supported by each device.
Each loop of a CF2000 panel can accommodate up to 200 (99 Belgium) addresses.
6
Page 7
Project Planning
The following is a typical program and timetable for a CF2000 installation project, once the initial order has been received:
1. Project Meeting
Installer and user to be present; system specifications, schematic diagram and proposed circuit drawing to be available. CF2000 Installation & Commissioning Guide to be provided.
2. Equipment Fix
Typically 2 week's notice is required for equipment to be delivered. Cable to be installed and bases/back boxes to be fitted. Then fire sensors, call points, alarm sounders and interface units can installed.
3. Address Schedule
Schedule of sensor locations to be completed by installer and returned to enable System programming.
4. Auto Learn
Fire panel/repeater panels to be installed and terminated. System to be powered up by installer and auto learn mode activated (see Auto Learn section). System to be tested and verified by installer, prior to final commissioning.
5. Final Commissioning
Minimum 2 weeks notice is required from receipt of Address Schedule and Commission request form for a Cooper Fire Systems Service Engineer to attend site to implement/oversee the final commissioning procedures (see Commissioning section), in conjunction with the installer.
7
Page 8
Guidelines
Systems should to the relevant local standards and codes of practice, for the UK this is BS5839 part 1. CF2000 meets all the relevant requirements of BS5839 part 1: 2002. Installation planning is simplified by the fact that every addressable CF2000 device contains an integral short circuit isolator. Care must be taken to ensure that local standards requirements regarding aspects such as loop coverage, area covered by a single spur and cable specification are observed.
There may be certain applications in which deviations from the code may be necessary and these must be listed on the commissioning certificate. (See commissioning section)
Loop lengths
The maximum permitted loop length is 2 km measured from the near to the far terminals on the CF2000 Motherboard PCB. There is no minimum limit to loop length. Any wiring spurs off the loop must be included within the 2 km limit. On long loop runs, the lengths of wiring rises and falls (between floors, down to manual call points) must be included. Remember to include these especially when taking loop lengths from plan drawings.
Loop loading - total number of addresses
The total number of addresses per loop is 200 (99 Belgium). this includes detectors, call points and all other addressable items and call points. When designing systems its recommended that allowances are made for future expansion, Short circuit isolators are incorporated into every CF2000 loop device, including Smoke detectors, heat detectors, sounders, callpoints and interfaces. Therefore, no further fault protection is required , in the event of a single fault, none of the devices connected to the loop will fail to operate as the fault will be isolated by the two adjacent devices. Spur connected devices downstream of a cable fault will cease to function.
System Design Guidelines
8
Page 9
Compatible Equipment
Add re ssa ble Ca ll P oi nts
CBG370 Addressable c all point - Flush 85(H) x 85(W ) x 30(D) CBG370/S Addressable c all point - Surface 85(H) x 85(W ) x 53(D) CBG370/W P W eatherproof addres sable call point 108(H) x 108(W) x 65(D)
Ana logu e Sensors
CAH330 A nalogue heat detector 101 Dia x 43(D) CAP320 Analogue optical s moke detector 101 Dia x 33(D) CAI310 Analogue ionization smok e detector 101 Dia x 33(D) CAPT340 Analogue photo/therm al dual detector 101 Dia x 43(D) CAB300 Common mounting base 104 Dia x 22(D)
Add re ssa ble Inte rfa ce s
CSI350 Spur Isolator 85(H) x 145(W) x 58(D) CIO351 3 Channel I/O Unit 130(H) x 180(W) x 60(D) CZMU352 Zone Monitor Unit 85(H) x 145(W ) x 58(D) CMIO353 230v Relay I/O Unit 130(H) x 180(W) x 60(D) CSC354 4 W ay Sounder Controller 300(H) x 300(W) x 74(D) CSUM355 Shop Unit Monitor 130(H) x 180(W) x 60(D)
Add re ssa ble S ounde rs a nd Bea cons
CAS380 Loop Mounted Base Sounder 102 Dia x 40(D) CAS381 Wall Sounder 105(H) x 105(W) x 95(D) CAS381/W P W all Sounder - weatherproof 110(H) x 110(W) x 105(D) CAB382 Loop Mounted Beacon 93 Dia x 53(D) CASB B384 Loop Mounted B ase S ounder/Beacon 115 Dia x 35(D) CASB 383 W all Sounder/Beacon 106(H) x 106(W) x 91(D) CASB 383/W P W all Sounder/Beacon IP66 110(H) x 110(W) x 100(D)
Con ve ntiona l Ca ll P oints
CBG375 Flush mounting c all point 87(H) x 87(W ) x 20(D) CBG375/S Surface mounting c all point 87(H) x 87(W ) x 53(D) CBG376 W eatherproof surfac e c all point 110(H) x 110(W) x 65(D)
Con ve ntiona l De te ctors
CPD320 P hotoelec tric sm oke detector 101 Dia x 33(D) CID310 Ionization smok e detec tor 101 Dia x 33(D) CPT340 Com bined photo/therm al detector 101 Dia x 43(D) CFR330 Fast response heat detec tor 101 Dia x 43(D) CMT360 Medium res ponse heat det ector 101 Dia x 43(D) CHT390 High temperature heat detector 101 Dia x 43(D) CDB B300 Common mounting base 104 Dia x 22(D)
Con ve ntiona l Soun de rs
AC/R 24V flus h mounting electronic s ounder 86(H) x 86(W ) x 42(D) * CXBB/R Surface m ount ing back box for AC/R SY/R 24V low current sounder 105(H) x 105(W) x 95(D) SQ/R Bas e s ounder 112 Dia x 30(D) ROLP/R/S Elec tronic sounder - s hallow base for indoor applications 93 Dia x 75(D) ROLP/R/D E lec tronic sounder - deep base (W eatherproof) 93 Dia x 105(D)
Con ve ntiona l Soun de r/Beacons
FL/ RL/R/D Combined sounder/beacon deep base 93 Dia x 92(D) FL/ RL/R/S Combined sounder/beacon Shallow base 93 Dia x 121(D)
9
Page 10
CPD320 Conventional Photoelectric Detector, this is the most commonly used detector and is most suitable for detecting slow burning fires.
The range of compatible detectors for the CF2000 system consists of the following:
CPT340 Conventional Photo/thermal Detector, this is a new addition to the Cooper Fire Systems range of detectors. It is the ideal detector for a multi-use environment as it has an excellent response to smouldering and fast burning fires.
CMT360 77°C Fixed Conventional Heat Detector,
Heat detectors are suitable for dusty environments or environments where smoke is likely to be present under normal operating conditions.
Compatible Equipment
Conventional Devices
Model CID310 CPD320 CFR330 CMT360 CHT390 CPT340
Operating voltage
Standby current (max) 70µA
Start-up Current (max 20 seconds) 340µA
Alarm current (max) 20mA
Ambient Temperature (m ax) 45ºC 60ºC 75ºC 75ºC
Ambient Temperature (m in)
Alarm temperature (static )
60ºC
77ºC
Heat detector class as defined by EN54-5:2000
Radioactive material/strength Am 18.5KBq
Relative humidity (non cond)
Height (w/o base)
Height (with base)
Diameter
Weight (w/o base) 86g 78g 78g
Material
Colour
76g
15 to 30V dc
25mA
30µA
210µA N/A
47mm 56mm
100mm
N/A
N/A
60ºC
-20ºC
34mm
White
90ºC
N/A
0 to 95%
43mm
A2R BS CS A2S
PC/ABS
10
Page 11
CHT390 92°C Fixed Conventional Heat Detector,
Heat detectors are suitable for dusty environments or environments where smoke is likely to be present under normal operating conditions.
CFR330 Rate of Rise A2R Heat Detector,
Heat detectors are suitable for dusty environments or environments where smoke is likely to be present under normal operating conditions.
CDBB300 Conventional Detector Base,
Compatible Equipment
Conventional Devices
11
Page 12
CAP320 Analogue Photoelectric Sensor, this is the most commonly used sensors and is most suitable for detecting slow burning fires.
The status LED can be programmed to either be permanently off under normal conditions or to pulse in order to confirm that it is in communication with the CF2000 control panel.
The range of compatible sensors for the CF2000 system consists of the following:
CAPT340 Analogue Photo/thermal Sensor, this is a new addition to the Cooper Fire Systems range of sensors. It is the ideal sensor for a multi-use environment as it has an excellent response to smouldering and fast burning fires. Photo/thermal sensors can be programmed for thermal only operation at certain times of day
The status LED can be programmed to either be permanently off under normal conditions or to pulse in order to confirm that it is in communication with the CF2000 control panel.
Compatible Equipment
Analogue Devices
Model CAI310 CAP320 CAH330 CAPT340
Operating voltage
Standby current (max)
Alarm current (max)
A1R 50ºC
BS 65ºC
CS 80ºC
Ambient Temperature (min)
A1R 60ºC
BS 77ºC
CS 90ºC
Heat sensor class as defined by EN54-5:2000
Radioactive material/strength Am 18.5KBq
Relative humidity (non cond)
Height (w/o base)
Height (with base)
Diameter
Weight (w/o base) 86g 78g 76g 78g
Material
Colour
18 TO 30V dc
220µA
5mA
-20ºC
N/A
A1R, BS, CS control panel
selectable
A2S
PC/ABS
0 to 95%
34mm 43mm
N/A
White
50ºC60ºCAmbient Temperature (max)
N/A 60ºCAlarm temperature (static)
47mm 56mm
100mm
12
Page 13
CAH330 Analogue Heat Sensor,
Heat sensors are suitable for dusty environments or environments where smoke is likely to be present under normal operating conditions. The CAH330 can be programmed to operate in A1R,BS or CS mode of operation depending on the required application and sensitivity requirements.
The status LED can be programmed to either be permanently off under normal conditions or to pulse in order to confirm that it is in communication with the CF2000 control panel.
CAB300 Analogue Sensor Base,
Compatible Equipment
Analogue Devices
Short Circuit Isolators
Each of the sensors in his range contain an integral short circuit isolator, which operates between the
-VE COM IN terminal and the -VE COM OUT terminal. The isolator operates in conjuction with the CF2000 Control Panel when a low parallel resistance fault of typically 200W is presented between the +VE and -VE of the loop wiring.
Short Circuit Isolation Data (Integral with ea ch sensor)
Total Loop Resistance for correct operation of short c ircuit isolator
50Ω (max)
Continuous Current allowable through isolator
700mA (max)
Isolator Resistance in closed state 0.13Ω (max)
Leakage Current into direct short circuit with isolator open
13mA (max)
Parallel Fault Resistance to be seen at the Control Panel for isolators to open
200Ω (typ)
13
Page 14
Compatible Equipment
Compatible callpoints
The range of purpose designed callpoints for CF2000 consists of a surface callpoint, a flush callpoint and a surface weatherproof callpoint. A range of accessories is available including a hinged protective cover, Resettable element kit and a flush bezel.
Compatible Sounders
A wide range of sounders are available to operate with CF2000. All sounders have multiple selectable volume settings, the volume setting is controlled by the CF2000 panel and so can be altered without needing to access the sounder.
Conventional
CBG375
CBG375/S
CBG376/WP
14
Page 15
Compatible Equipment
Compatible callpoints
The range of purpose designed callpoints for the CF2000 consists of a surface callpoint, a flush callpoint and a surface weatherproof callpoint. A range of accessories is available including a hinged protective cover, Resettable element kit and a flush bezel. The status LED can be programmed to either be permanently off under normal conditions or to pulse in order to confirm that it is in communication with the CF2000 control panel.
Compatible Sounders and Beacons
A wide range of loop powered sounders and beacons are available to operate with the CF2000 consisting of a combined sounder base with a maximum output of 95 dB(A), a standalone sounder with a maximum output of 100 dB(A) that is available in standard or weatherproof versions and a stand alone loop powered beacon. For applications where a discreet dedicated sounder is required, a cover plate is available for the white base mounted sounder enabling it to be used as a stand alone wall or ceiling mounted sounder. All of these devices are fully programmable via the sophisticated CF2000 multi stage cause and effect programming facilities.
All sounders have multiple selectable volume settings, the volume setting is controlled by the CF2000 panel and so can be altered without needing to access the sounder.
CBG370
CBG370/S
CBG370/WP
Analogue
15
Page 16
Base sounder
The CAS380 has been designed specifically to complement the latest generation of Cooper Fire Systems soft addressed detectors. it consists of a first fix bracket, and a main body which clips onto the bracket incorporating the sounder and a detector mounting base in a single composite assembly.
After the body has been clicked into place and connected, a sensor or front cover is then added to complete a very simple quick and neat installation. The cover enables the CAS380 to be used as a discreet stand alone wall or ceiling mounted device. The sounder base design incorporates a mechanism that can be activated if required to lock either the sensor or the cover into place to prevent unauthorised removal.
Dedicated Stand alone sounders
Stand alone sounders are ideal for applications where greater sound outputs are required than can be achieved with a base sounder or for applications requiring a higher level of resilience or ingress protection. Two different versions are available standard version and an IP66 rated version.
CAS380
CAS381
CAS381/WP
CAS380 with sensor fitted
CAS380 with CASC fitted
Compatible Equipment
16
Page 17
Interfaces
CF2000 has been designed to be suitable for a wide range of applications, various interfaces have been developed to enable the simple integration of other fire systems or building control and safety systems. The following devices are available:
3 Channel I/O device. (CIO351)
CIO351 has 3 input channels and 3 output channels, it is used to monitor up to three separate inputs from equipment such as sprinkler flow switches and also to provide 3 separately controlled volt free output contacts which are intended to be used to control external equipment such as air handling plant or access control systems. All inputs and outputs operate completely independently of each other and can be programmed using the sophisticated cause and effect capabilities of CF2000 to operate either globally or in response to activation of specific devices or specific inputs. Inputs are monitored for open and short circuits, a specific resistance is required to activate an alarm condition, fully open or short circuit conditions are monitored and generate a system fault signal. Inputs are suitable for use as fire signal inputs such as from a sprinkler flow switch , however they can also be used to monitor non fire inputs such as external keyswitches. Outputs are rated to switch a maximum of 1A resistive at 30V DC. The CIO351 is supplied in a surface mounting IP65 box.
1 Channel I/O device with mains rated switching capability (CMIO353)
CMIO353 is a single channel input / output unit, the output is capable of switching up to 1A at 230V AC. Commonly used for applications such as door release controls and plant shut down signaling
The input is monitored for open and short circuits, a specific resistance is required to activate an alarm condition, fully open or short circuit conditions are monitored and generate a system fault signal. The input is suitable for use as a fire signal input such as from a sprinkler flow switch, however it can also be used to monitor non fire inputs such as an external keyswitch. The CIO353 is supplied in a surface mounting IP65 box.
CIO351
CMIO353
17
Page 18
Zone monitor unit (CZMU352)
CZMU352 is designed to enable a zone of compatible conventional detectors and callpoints to be connected into the CF2000 loop, it is compatible with up to 20 Cooper Fire Systems conventional detectors connected via CDBB300 bases. Please refer to local standards e.g.BS5839 Pt1:2002 for details of the maximum allowable area to be covered by a single spur / zone. CZMU352 fixes to a standard, deep, double gang back box and can be either surface or semi recess mounted. When semi recessed only the front section protrudes giving a maximum 29mm depth.
Shop unit Interface (CSUM355)
CSUM355 accepts a zone of conventional detectors plus an unlimited number of callpoints which can be connected to the same input as the detectors or a separate callpoint input if required. It also has a 24V 1A rated relay output, and a facility to connect a power supply, which can then be monitored for fault. In addition it has the facility to connect two circuits of conventional polarised sounders, which are monitored by means of an end of line resistor and powered in alarm conditions from the external power supply. The sounder circuits can be programmed to operate in pulsed, continuous or time delayed mode.
Please refer to local standards e.g. BS5839 Pt1:2002 for details of the maximum allowable area to be covered by a single spur / zone. The CSUM355 is supplied in a surface mounting IP65 box.
Interfaces
CSUM355
CZUM352
18
(CZMU352)
Page 19
Spur Isolator (CSI350)
CSI350 enables soft addressing to work when the loop contains spurs, it controls the addressing operation so that when the system reaches a spur, all devices on the spur are allocated an address before it continues addressing the loop. The device also incorporates a short circuit isolator. Because each device contains a short circuit isolator only 1 is required at the start of each spur.
CSI350 is mounted on a standard deep double gang back box (supplied)
Please refer to BS5839 Pt1:2002 for details of the maximum allowable area to be covered by a single spur / zone
4 Way sounder circuit controller (CS354)
CSC354 provides power for 4 separately controllable conventional sounder circuits, each circuit can be separately programmed. CSC354 is designed to greatly simplify installation in applications where specialist sounders or beacons are required since it powers the sounders and allows full control of the sounder operation without having to wire the sounder back to the CF2000 control panel.
A 4 way unit takes up a single address but each circuit can be independently controlled. An CSC354 unit requires a local un-switched 230V supply and incorporates a back up battery to 24 hours of standby operation followed by a minimum of 30 minutes of full alarm ringing. A standby of 72 hours can be achieved at the expense of reduced load capability.
Interfaces
CSI350
CSC354
19
Page 20
Equipment Compatibility
Sensors
Loop wired sensors must be of the Cooper Fire Systems 300 series soft addressed analogue type. Cooper Fire Systems 300 series conventional detectors can be connected via an CZMU352 interface. The connection of other detector types via an CZMU352 interface is not recommended,
Call points
Loop wired call points must be the Cooper Fire Systems 300 series soft addressed analogue type, Cooper Fire Systems 300 series conventional callpoints can be connected via an CZMU352 interface. The connection of other callpoint types via an CZMU352 interface is not recommended,
Sounders
Loop powered addressable sounders must be of the Cooper Fire Systems 300 series soft addressed analogue type.
Conventional sounders can also be connected either to the conventional sounder circuits at the panel or to the loop via a CSC354 addressable sounder controller interface providing they meet the following:
1) They are suitable for operation between 18V and 28V.
2) They are polarised and suppressed.
3) The total alarm load is less than the rating of the panel / Alarm Power Interface.
Note: It is possible to use devices outside these requirements if they are supplied with power from a separate source and switched via a suitable relay.
Relay circuits
Additional relays can be added to the CF2000 system by using either CMIO353 or CIO351 relay units.
Relays / Auto-dialers and auxiliary equipment
A wide variety of relays and other equipment can be connected to the CF2000 system, but you should note the following constraints:
1) CF2000 provides monitored outputs to drive fire and fault relays mounted in external equipment. External relays should be suppressed. If a non-suppressed relay is used then a diode can be connected , to suppress any reverse EMF on the release of the relay which might cause the panel to malfunction.
2) A 24V DC output is provided at the panel to make it easy to connect ancillary equipment. Although the panel can supply a continuous quiescent load of up to 30mA, BS5839 precludes this practice and any ancillary equipment you connect should only consume power in the alarm or fault mode to meet the requirements of BS5839.
20
Page 21
System Overview
Simple user interface
The main element of the user interface with CF2000 is a (60mm x 30mm visible area) display, which provides comprehensive user information.
As well as an LCD display providing full system status information, the panel incorporates 32 traditional zone indication LED's to provide clear information about the status and spread of a fire even to a user who is completely unfamiliar with the operation of the system. In addition there are a number of system status LED's designed to give clear status information to non technical users
User configuration and maintenance facilities
CF2000 has comprehensive facilities for on site system configuration, whereby the user can add or remove simple devices, without the need for a service engineer to visit site. For initial configuration or major system changes special PC configuration software is available enabling Cooper Fire Systems personnel to do this more efficiently than can be achieved using the system screen. Exiting configurations can be uploaded to the PC so that changes can be made to the existing system rather than having to revert to initial files. During the yearly maintenance, all terminal under main supply shall be verified.
21
Page 22
System Overview
Spur tolerant soft addressing
CF2000 utilises intelligent soft addressing technology to greatly simplify the installation and commissioning processes. Once the system has been installed and the autolearn menu selected, the CF2000 control panel will automatically scan the detection loops and allocate each device with an address number corresponding with its position on the loop, this avoids the traditional need for manual addressing of the system devices which is time consuming and provides a potential for error.
A major innovation with CF2000 is the ability to incorporate spurs of analogue devices which are fed from the main loop by utilising a spur isolator. Whenever the panel detects a spur, it breaks from allocating address numbers to the loop wired devices, allocates address numbers to each of the devices on the spur in sequence and then continues to address the devices on the main loop.
Every CF2000 analogue device incorporates an integral short circuit isolator ensuring maximum system integrity. A single short circuit will not disable any loop-mounted devices, the isolators in the devices each side of the short circuit will operate and the CF2000 control panel will drive communication from both ends of the loop. The spur isolator also incorporates a short circuit isolator such that in the event of a short circuit on the spur, the integrity of the main loop will not be compromised. Please refer to local standards local standard for details of the maximum allowable are to be covered by a single spur.
Integral Power Supply and Battery
The CF2000 panel is designed for ease of installation, the power supply and battery are integral to the main control panel so only a single panel is required.
22
Page 23
Optional printer
System Overview
23
Page 24
Technical Specification
Power Supply (Approved EN54 pt 4)
Mains Nominal Voltage : 230 Vac + 10%, -15% Nominal Current : 40mA Maximum Current : 500mA Input Fuse R1 : Anti Surge 1.6Amp Output Voltage including tolerances : 26V = 18.5 to 29.5Volts
: 26V RAW = 18.5 to 29.5Volts : 5Volt Output = 4.6V to 5.5V
Ripple Voltages : 26V = 800mV
: 26V RAW = 800mV : 5Volt Output = 430mV
Maximum Loadings : 26V O/P = 0.48A
: 26V RAW O/P = 1.2A : 5V = 0.5A
Standby Current (2 Loops Loaded) : 26V = 140mA
: 26V RAW = 50mA : 26V = 140mA : 26V RAW = 50mA : 5V = 30mA
* I max a, I max b & I min = Current as specified in BSEN54-4 Published 2006 (Amendments 1 & 2)
Batteries
Number of Batteries : 2 Manufacturer: :YUASA NP7-12 Capacity : 7 Ah Battery Fuse : 6.3A Anti-Surge (F4) Maximum battery current; : 3.0 Amps Standby current (mA) : 125 (2 loops) Maximum Charging Current to the Batteries : 0.65Amp Float Voltage : 27.4 Volts Final Voltage : 21.0Volts Charging Characteristics : Constant Voltage with 0.65A
limit with temperature compensation Maximum current drawn from the batteries : 3.0Amps when the mains is not available Deep Discharge Protection : 20.6 Volts Battery Internal Impedance Fault : >0.5 ohms
Inputs
Addressable Loops Max Number : 2 Max Loop Load per loop : 200 ma Max Number of Addressable Devices per loop : 200 Class Change : Operated by external volt free contact
24
CAUTION
RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE DISPOSE OF THE USED BATTERIES ACCORDING TO THE INSTRUCTIONS
(Appendix page 113)
}
* I max a
}
* I min
}
* I max b
Page 25
Outputs
Conventional sounder circuits
Number of sounder circuits : 4 Total sounder Load : 1.0Amps (FH1204) Maximum Sounder Circuit Load : 800mA Sounder Circuit Fuses (F1/2/3/4) : 1.6 Amp (Quick Blow) End of line resistor : 6k8
Fire Routing Equipment
Max Load : 60 ma Fused (PTC2) : 100mA polyswitch End of Line resistor : 6k8
Fire Protecting Equipment
Max Load : 60 ma Fused (PTC4) : 100mA polyswitch End of Line resistor : 6k8
Fault Routing equipment
Max Load : 30 ma Fused (PTC1) : 100mA polyswitch End of Line resistor : 6k8
Auxiliary Relays
The auxiliary relays provide fused volt free change over contacts. These contacts are not monitored. Max Load : 24 Volts 1 Amp Fuse (PTC5) : 1.1 Amps polyswitch
Auxiliary 24V Supply
Nominal Voltage : 24 Volts ±10% Fuse (PTC3) : 300 mA Polyswitch Maximum current : 30 mA This output is not to be used for Fire protecting equipment or Fire alarm routing Equipment Any power taken from the alarm system will effect the standby duration
RS485 Port (Mimic Repeater) This is a serial output port for driving CF2000 Repeater panels, mimics etc.. This output is short circuit protected Max Cable Length : 2Km Min Recommended cable size : 1mm² (Screened)
Mechanical Specification
Weight including batteries : 10.6Kg Weight excluding batteries : 5.3Kg Dimensions (Standard batteries) : 400mm(L) x 320mm(H) x 170mm(D) Type of Material (backbox) : Mild Steel (Power Coated) Type of Material (Facia) : PC/ABS Flammability Rating : UL 94 V0 Total Number of knockouts : 24 Diameter of Knock out : 20mm
TERMINAL BLOCKS :
DO NOT USE EXCESSIVE FORCE WHEN TIGHTENING THE SCREWS ON THE TERMINAL BLOCK
Technical Specification
25
Page 26
Optional Functions as per EN54 P2&4
CF2000 is approved to EN54 Parts 2 & 4 including all the following options which can be selected as required
PANEL INPUTS
Class Change: ( OPTION NOT REQUIRED BY EN54) A pair of terminals are provided for class change. By shorting these terminals together (e.g. Switch, Time clock) the alarm will sound (Panel sounders + loop sounders only). The Panel will not indicate a Fire. The alarm will cancel when the short circuit is removed.
WARNING: NO VOLTAGE SHOULD BE APPLIED TO THIS INPUT
PANEL OUTPUTS
Panel Sounders: (OPTION 7.8 EN54 PT 2) Two pairs of outputs are provided. ONLY polarised equipment should be used. Ensure the polarity of the connections are observed at all times and end of line resistors (6K8 5%) are fitted for correct operation. The total alarm load across all sounder outputs = 1.0Amp All outputs are fused with 1.6 Amp Glass fuse Alarm devices should be spread equally across the 4 sounder circuits.
WARNING: DO NOT EXCEED THE RATED OUTPUT CURRENT
OUTPUT FIRE ALARM ROUTING EQUIPMENT (OPTION 7.9 EN54 PT 2)
This output, which is fused, and monitored using a 6.8k end of line resistor, is used for the automatic transmission of the fire signals to fire alarm ROUTING equipment (e.g. Fire brigade). It operates by providing 24 Volt output to an auxiliary device ( e.g. relay). It is current limited to 30 mA using a resettable polyswitch. Class change and test conditions do not operate this output. If operated under a fire alarm condition, the FRE LED will illuminate and will remain illuminated until the fire alarm is reset. Ensure the polarity of the connections are observed at all times and end of line resistors (6K8 (5% ) are fitted for correct operation
OUTPUT TO FIRE ALARM PROTECTING EQUIPMENT ( OPTION 7.10 EN54 PT 2 Option A)
This output, which is fused, and monitored using a 6.8k end of line resisters used for the transmission of the fire signals to controls for automatic fire protecting equipment (e.g. Door released units etc).It operates by providing 24 Volt output to an auxiliary device ( e.g. relay).`
All Sounders must be polarised
Both sounder circuits must Be terminated with a 6800 Ohm end of line resistor
26
Page 27
It is current limited to 30 mA using a resettable. polyswitch. Class change and test conditions do not operate this output. If operated under a fire alarm condition , this output remains energised until the fire alarm is reset. Ensure the polarity of the connections is observed at all times and end of line resistors ( 6K8 5% ) are fitted for correct operation.
OUTPUT TO FAULT WARNING ROUTING EQUIPMENT ( OPTION 8.9 EN54 PT 2)
This output, which is fused and monitored using 6.8k end of line resistor, is used for the transmission of fault signals to fault warning routing equipment This output is monitored using 6k8 end of line resistor and it current limited to 30 mA.Under normal condition it operates by providing 12vdc which can be connected directly to a 12v auxiliary device(It is current limited to 30 mA). Under fault conditions or even if the CF2000 is powered down, this output will be switch to O volts. Ensure the polarity of the connections is observed at all times and end of line resistor 6K8 (5%) are fitted for correct operation.
Delays to outputs (Option 7.11 of EN54pt 2)
The CF2000 has the option to delay the operation of panel sounders, the fire routing equipment output and the fire protecting Equipment. This delay is selectable using the CF2000 site installer download software .The delay is configurable in increments of 1 minute up to a maximum of 10 minutes. This delay can be enabled and disabled at access level 2. The CF2000 has the facility for a specific call point to override this delay by programming this call point via an input interface to provide an evacuate signal using CF2000 site Installer.
Dependencies on more than one alarm signal - Type C (Option 7.12.3 of EN54pt 2)
The CF2000 has the facility to inhibit the operation of the output sounders, Output to Fire routing equipment and the output of the fire protecting equipment until one more confirmatory signals are received from different zones. This feature is programmable using CF2000 Site Installer Software.
Optional Functions as per EN54 P2&4
Auxiliary Relay (OPTION NOT REQUIRED BY EN54) This output is a volt free contact, which is protected by a polyswitch. It is rated at 24 Volts DC 1Amp. If operated under a fire alarm condition , this output will remain energised until the fire panel is reset
DO NOT USE TO SWITCH MAINS VOLTAGE
AUXILIARY DC OUTPUT (OPTION NOT DEFINED BY EN54)
A 24 Vdc output is provided. This output is protected by a polyswitch. This output can be used to power fire or fault auxiliary equipment. Please ensure that all equipments connected to this output will only draw current when a fire condition exists.
WARNING:- DO NOT EXCEED THE RATED OUTPUT CURRENT
MIMIC OUTPUT (OPTION NOT REQUIRED BY EN54)
This RS485 output is used to send data to a mimic display or a repeater panel. The maximum distance is 2km.
27
Page 28
External Connections
Mains Supply
The mains supply should be installed in accordance with the current edition of the IEE wiring regulations. Connection to the mains supply must be via an isolating device (e.g.a double pole isolating fuse rated at 2A. In each case you have to comply with local regulations. ) reserved solely for the fire alarm system. The cover should be coloured red and labelled “FIRE ALARM - DO NOT SWITCH OFF”. The isolating protective device should be secure from unauthorised operation and ideally installed in a securely closed box with a breakable cover.
An additional warning label should be provided, depending on whether:-
a) The isolating protective device is fed from the live side of the main isolating
device in which case the label on the isolating protective device, should read in addition - “WARNING: THIS SUPPLY REMAINS ALIVE WHEN THE MAIN SWITCH IS TURNED OFF”. A further label should be placed on the main isolating device reading “WARNING: THE FIRE ALARM SUPPLY REMAINS LIVE WHEN THIS SWITCH IS TURNED OFF.
Or
b) If the isolating protective device is fed from the dead side of the main
isolating device, a label should be fixed to the main isolating device reading “WARNING: THIS SWITCH ALSO CONTROLS THE SUPPLY TO THE FIRE
ALARM SYSTEM”.
Cable Segregation
All cables for the fire alarm system should be segregated from any other cables/wiring/services.
28
Page 29
The panel should be installed in a clean, dry, reasonably well ventilated place, and not in direct sunlight. Temperatures in excess of 40°C and below 5°C may cause problems, if in doubt consult Cooper Fire Systems. The panel should be located away from any potential hazard, in a position where it is readily accessible to authorised staff, and the fire services, ideally on the perimeter of a building near a permanent entrance.
Installation Guide
! Never carry out insulation tests on cables connected to electronic equipment. ! DO NOT OVER TIGHTEN TERMINAL CONNECTOR SCREWS ! Always use the correct type of cables specifically designed for the operation of fire
detection and alarm circuits.
! Always adhere to volt drop limitation when sizing cables ! Always observe polarity throughout. Non colour coded conductors should be
permanently identified.
! Screen continuity must be maintained throughout the entire loop circuit including at
each junction point and at each device, terminals are provided on each device to facilitate this.
! The screen should be earthed at the connection point provided at the CF2000 panel
and not at any other point. Both the loop start and the loop end must be connected to the appropriate earthing points. Care must be taken to avoid connecting the screen to the earthed body of any metal devices, enclosures or cable containment. The screen or drain wire of the loop cables should not be considered as safety earth and therefore should not be connected to terminals marked with the earth symbol, except at the panel, and should not be insulated with green and yellow sleeving.
! CF2000 utilises intelligent soft addressing technology to greatly simplify the
installation and commissioning processes. Once the system has been installed and the loops wired to the panel with all devices fitted, the CF2000 control panel will automatically scan the detection loops on power up and allocate each device with an address number corresponding
with its position on the loop, this avoids the
traditional need for manual addressing of the system devices which is time consuming and provides a potential for error. If no devices can be found the panel
will keep rebooting and performing an auto-learn until a device is found on a loop.
! It is of vital importance that accurate details are kept of the exact wiring route in
order to determine which address has been allocated to each device.
Installation
29
Page 30
Fixing details
Read all the installation instructions before commencing with the installation. The installation of this panel must be carried out by a suitably qualified /trained person. The installation must comply with IEE wiring regulations and with BS5839 part 1 2002
The electronic components within the fire panel are Static Sensitive. Do not touch the electronics directly.
Mounting the Backbox
The CF2000 can be flush mount or surface mounted.
1, Surface Mount; drill four holes and fix the backbox to the wall.
2, Flush mounting the backbox requires a hole 310 x 355 with a depth of 117mm.
Installing Cabling
Once the backbox is mounted the next stage is to install the power and loop cables and fit the glands.
390mm
355mm
310mm
117mm
132mm
30
Page 31
System Wiring
NO
C
NC
FAULT
RELAY
+ 24V
O/P
FIRE R/E
FIRE P/E
CLASS
CHANGE
SOUNDER
CIRCUIT 1
LOOP 1
LOOP 2
AUX
RELAY
LOOP CIRCUITS
0V
S+
F-
F+
S-
-
+26V
+
+
-
-
+
-
+
-
Tx-
Tx+
S+
F-
F+
S-
+ 1 -
+ 2 -
SOUNDER
CIRCUIT 2
MIMIC
REPEATER
+ 1 -
+ 2 -
Any 300 Series Analogue Detector can be Connected to the Loop
Upto 200 Analogue Addressable Devices
31
Page 32
System Wiring ( Optional Board)
E
E
E
E
E
E
+
-
-
+
ADDRESSABLE
CALLPOINTS
ADDRESSABLE
CALLPOINTS
ANALOGUE
SENSORS
ANALOGUE
SENSORS
CONV.
DETECTORS
CONV.
DETECTORS
CONV.
CALLPOINTS
LOOP 1
LOOP 2
CONV.
CALLPOINTS
S+
S+
F-
F-
F+
F+
S-
S-
E
E
E
E
-
-
-
-
+
+
+
+
EOLM-1
EOLR
EOLM
EOLR
Upto 32 Analogue Addressable Callpoints
Upto 32 Analogue Addressable Callpoints
Upto 20 Coventional Detectors
Upto 20 Coventional Detectors
Upto 32 Coventional Callpoints
Upto 32 Coventional Callpoints
Upto 99 Analogue Addressable Devices
Upto 99 Analogue Addressable Devices
This boards is used to extend the flexibility of the CF2000 by splitting each loop into four circuits .One circuit will allow the use of 99 addressable devices wired in a loop. The second circuit can accommodate up to 32 addressable Call point in a spur configuration. Up to 32 conventional call point can be wired in the third circuit where the line is monitored using End of Line Resistor and finally the forth circuit has a maximum capacity of up to 20 Conventional detectors again the line is monitored with an active end of line device EOLM-1.
32
Page 33
Commissioning CF2000
Section 2
33
Page 34
Up/downloading using PC Software
The PC Software enables the address, location text, device type and any comments to be downloaded to the CF2000 panels.
Commissioning
34
Page 35
PC Comissioning Software
Device Input Programming
Fire -> panel reports fire from device. Fault -> panel reports fault from device. Reset -> panel resets. Silence -> silence all currently active sounders. Pre-Alarm -> panel reports pre-alarm from device.
Non-Latching -> device won't latch in alarm condition, used in conjunction with isolates.
Optical-Heat -> mode changes between heat or optoheat mode
Heat -> mode changes between Heat A1R and Heat CS
Isolate Zone / Address
user can define between zones or addresses to be isolated on activation of the device. The isolate list button enables the user to enter upto 8 unique zones or addresses.
If non-latching has been enabled, Isolated devices can be un-isolated as the triggered device returns to normal operation. (a call point keyswitch is an example for this application)
35
Page 36
PC Comissioning Software
Device Outputs
Delay configuration
The output of a device when triggered can be delayed - based on a user defined value in minutes. This programming option is enabled when a value other than zero is entered inside the 'Delay' window.
Delay Override
This option is a manual intervention override, when enabled (check in box) the delay can be overridden from any call point on the loop when triggered.
36
One of these will be ticked
Page 37
PC Comissioning Software
Panel Outputs
Dependence detection
Each panel output can be assigned a unique list of zones derived from the zones available on the loop, to activate this output, two unique zones from this list have to be be in fire or alternatively any zone outside this list will trigger the output also. When the 'dependence' box is checked - the 'Allocate device' button allows the user to populate this list.
37
Ticked by Default
Page 38
Panel Fault Finding
NO
C
NC
FAULT
RELAY
+ 24V
O/P
FIRE R/E
FIRE P/E
CLASS
CHANGE
SOUNDER
CIRCUIT 1
LOOP 1
LOOP 2
AUX
RELAY
LOOP CIRCUITS
0V
S+
F-
S-
-
+26V
+
+
-
-
+
-
+
-
Tx-
Tx+
S+
F-
F+
S-
+ 1 -
+ 2 -
SOUNDER
CIRCUIT 2
MIMIC
REPEATER
+ 1 -
+ 2 -
V
V
V
V
V
V
F+
V
V
V
V
V
V
V
V
V
W
W
= 28V (Open Circuit, No Input)
= -0.6V Mon +28V Fire (Depends on Programming)
= -0.6V Mon +28V Fire (Depends on Programming)
= -0.6V Mon +28V Fire (Depends on Programming)
= -0.6V Mon +28V Fire (Depends on Programming)
=0V (No Data)
See Scope Plots for Monitoring Conditions
= O/C Normal S/C Fire
= +5.5V ± 0.5V (No Printer Attached)
= S/C Normal O/C Fire
= 12V No Fault 0V (short CCT) Fault
= 28.5V (No Load Connected)
= -O.6V-No Fire 28V Fire
No Fires See Scope Plots for Monitoring Condition
See Protocol Section for Scope Plots
= -O.6V-No Fire 28V Fire
= 22V (Device Fitted) 0V (Unused)
= 22V (Device Fitted) 0V (Unused)
= 22V (Device Fitted) 0V (Unused)
= 22V (Device Fitted) 0V (Unused)
}
}
}
38
Page 39
Byte 1
Byte 2
Byte 3
Parity
Command
2ms
300us
300us
Start
Fig. 1 Full Protocol Format (Not in cluding Repeaters)
Panel to Device Device to Panel
Response
8 bits
ID
5 bits
Flags 3 bits
Address
8 bits
Loop Current
24v
typ
7.5v 0v
Mode
See Fig 4 for detail
1.1 ms
Each Packet of Comms above must be separated by a gap of 20ms minimum where the line is held at 24v
Last Bit Only
1.36 ms
Protocol Format
Normal Communications to Devices:
With the command bits set for the 'Normal' command and the MSB of the three mode bits set at 0, this shortened version of the Normal communications to each device allows the analogue reply or status from each device to be read. This format of communication is generally used throughout all background supervision of the addressable loop.
Alarm Interrogate Command:
This command is seen by all devices on the loop, so no address byte is required, and is periodically sent out during normal communications. This command allows any device experiencing an alarm condition to respond, with call points given the highest priority, reporting their address. This causes the control panel to break off from general background supervision of the loop and focus directly on the device in question.
Full Protocol Format:
With the command bits set for the 'Normal' command and the MSB of the three mode bits set at 1, the long version of the Normal communications can be sent to any device. This would normally be done by the panel following a response to the Alarm Interrogate command, allowing the panel to check the device address, ID and confirm that the analogue reply, or status, is truly an alarm condition before actioning the panel sounder outputs, for example.
Viewing the Voltage and Current waveforms at the panel:
Loop 1: Using a Digital Storage Oscilloscope, connect one channel to R84 on the Loop Driver Card; probe 0V clip to the 'Bottom' side of the resistor; I/P to the 'out-board' side. This will display the loop current. Connect the other channel to Loop 1, S+ terminal on the main mother board. DO NOT connect the 0v clip of this probe.
Loop 2: Using a Digital Storage Oscilloscope, connect one channel to R82 on the Loop Driver Card; probe 0V clip to the 'Bottom' side of the resistor.This will display the loop current.Connect the other channel to Loop 2, S+ terminal on the main mother board. DO NOT connect the 0v clip of this probe
39
Page 40
Panel Controls & Indicators
Section 3
40
Page 41
1. LCD Display
2. System LED’s
3. Zonal LED's
4. Buttons
Panel Controls & Indicators
LED Name Function Action
1 Power On Shows Panel is On (Mains Healthy) Check Indicator is Illuminated 2 Fire Indicators Panel has Detected a Fire Impliment Fire Action Procedure 3 General Fault Monitors Devices for Faults e.g. Smoke detectors/Sounders Report to System Supervisor 4 General Disable Monitors panel for disablements Report Fault to Service Dept 5 Test Supervisor/Engineer is Testing the System Check with System Supervisor 6 Delay Active Part of the System has been Disabled Check with System Supervisor 7 FRE On Fire Routing Equipment relay activated Report t o System Supervisor 8 FPE Indicateds Fire Protecting Equipment Status Check with System Supervisor
9 Power Fault Indicated PSU Fault Check with System Supervisor 10 Sounder Indicates the Sounder Status Check with System Supervisor 11 FRE Indicateds Fire Routing Equipment Status Check with System Supervisor 12 System Fault Panel has a Fault Report to Sy stem Supervisor
41
1
2
3
4
FPE
1
5
7
2
6
8
3
4
9
10
11
12
FPE
Page 42
System Healthy
System Healthy
1 Zone(s) Active
Reset
Cancel
Mute
OK
hh.mm.ss
dd.mm.yy
000AC
CF2000 is operated via an 8 button keypad. The default healthy screen is shown below. From this screen all the panels functions can be operated. Press any key to prompt the passcode screen
42
Page 43
View Event
The "View Events" screen is shown below. The events screens are accessed from the healthy screen by first pressing any button. You will then be prompted to enter the passcode which will show the screen below by default. Press "OK" and scroll through the list of events using the UP and Down arrow buttons.
Reset
Cancel
Mute
OK
View Events
Fire
View Pre-Alarm
View Fault
View Disable
View Log
Scroll through the events list using the scroll buttons as shown
Press "OK"
43
Page 44
Fire Event
View Fire
The "Fire" screen is shown below. From this screen all the panels functions can be operated. Press any key to prompt the passcode screen
1.1
Time PA LP AD ZN Type
Fire List
i
44
FPE
Power ON
Test
FIRE
General FAULT
General DISABLE
FRE ON
Delay ACTIVE
Power FAULT
Sounder
FRE
System FAULT
Disable Fault
Disable Fault
FPE
Page 45
View Fires
The "View Fires" screen is accessed as shown below. The events screens are accessed from the healthy screen by first pressing any button. You will then be prompted to enter the passcode which will show the screen below by default. Press "OK" and scroll through the list of events using the UP and Down arrow buttons.
View Events
Enter Passcode
Fire
Reset
Cancel
Mute
OK
Scroll through the events list using the scroll buttons as shown
Using to scroll keys show to the left scroll to the Fire screen
Press "OK"
Time PA LP AD ZN Type
Fire List
i
System Healthy
1 Zone(s) Active
hh.mm.ss
dd.mm.yy
000AC
45
FPE
Page 46
FPE
View Pre-Alarm
The "View Fires" screen is accessed as shown below. The events screens are accessed from the healthy screen by first pressing any button. You will then be prompted to enter the passcode which will show the screen below by default. Press "OK" and scroll through the list of events using the UP and Down arrow buttons.
View Events
Enter Passcode
Reset
Cancel
Mute
OK
Scroll through the events list using the scroll buttons as shown
Using to scroll keys show to the left scroll to the Pre-Alarm screen
View Pre-Alarm
i
Pre Alarm List
Time
Type
PA
LP AD
ZN
System Healthy
1 Zone(s) Active
hh.mm.ss
dd.mm.yy
000AC
46
Press "OK"
23:59 01 2 009 1 Repeater
Page 47
FPE
View Fault
The "View Fault" screen is accessed as shown below. The events screens are accessed from the healthy screen by first pressing any button. You will then be prompted to enter the passcode which will show the screen below by default. Press "OK" and scroll through the list of events using the UP and Down arrow buttons.
View Events
Enter Passcode
Reset
Cancel
Mute
OK
Scroll through the events list using the scroll buttons as shown
Using to scroll keys show to the left scroll to the View Fault screen
Press "OK"
View Faults
i
Fault List
Time
23:59
01
2
009
1
Repeater
Type
PA
LP AD
ZN
System Healthy
1 Zone(s) Active
hh.mm.ss
dd.mm.yy
000AC
47
Page 48
FPE
View Disabled(Address)
The "View Disabled" screen is accessed as shown below. The events screens are accessed from the healthy screen by first pressing any button. You will then be prompted to enter the passcode which will show the screen below by default. Press "OK" and scroll through the list of events using the UP and Down arrow buttons.
View Events
Enter Passcode
Reset
Cancel
Mute
OK
Scroll through the events list using the scroll buttons as shown
Using to scroll keys show to the left scroll to the View Disabled screen
Press "OK"
View Disabled
Disabled Address
1:4:1
System Healthy
1 Zone(s) Active
hh.mm.ss
dd.mm.yy
000AC
PTO
48
Page 49
FPE
Loop 1
Loop 2
Use the scroll up and down buttons to highlight the device and the "OK" button to switch between "Enabled" and "Disabled"
Reset
Cancel
Mute
OK
Switch between Loop 1 and Loop2 by using these buttons. Press OK to select.
Switch between Loop 1 and Loop2 by using the sideways scroll buttons shown to the left and press "OK" to select.
Disabled Devices (67)
A
Device Status
001
HtA1R HtA1R HtA1R
HtA1R
002 003 004
DISABLED
DISABLED DISABLED
DISABLED
View Disabled(Address)
49
Page 50
FPE
View Disabled(Zone)
The "View Disabled" screen is accessed as shown below. The events screens are accessed from the healthy screen by first pressing any button. You will then be prompted to enter the passcode which will show the screen below by default. Press "OK" and scroll through the list of events using the UP and Down arrow buttons.
View Events
Enter Passcode
Reset
Cancel
Mute
OK
Scroll through the events list using the scroll buttons as shown
Using to scroll keys show to the left scroll to the View Disabled screen
Press "OK"
View Disabled
Disabled Zone
1:4:2
1:4
1
System Healthy
1 Zone(s) Active
hh.mm.ss
dd.mm.yy
000AC
Disabled Zones (000)
Zone
001
Status
DISABLED
50
Page 51
FPE
View Disabled (I/O)
The "View Disabled" screen is accessed as shown below. The events screens are accessed from the healthy screen by first pressing any button. You will then be prompted to enter the passcode which will show the screen below by default. Press "OK" and scroll through the list of events using the UP and Down arrow buttons.
View Events
Enter Passcode
Reset
Cancel
Mute
OK
Scroll through the events list using the scroll buttons as shown
Using to scroll keys show to the left scroll to the View Disabled screen
Press "OK"
View Disabled
Disabled I/O
1:4:3
1:4
1
System Healthy
1 Zone(s) Active
hh.mm.ss
dd.mm.yy
000AC
Disable Panel IO
Aux Relay
FRE
ENABLED ENABLED ENABLED
ENABLED
ENABLED ENABLED
FPE Sounder 1 Sounder 2
Delay
51
Page 52
FPE
View Log
The "View Log" screen is accessed as shown below. The events screens are accessed from the healthy screen by first pressing any button. You will then be prompted to enter the passcode which will show the screen below by default. Press "OK" and scroll through the list of events using the UP and Down arrow buttons.
View Events
Enter Passcode
Reset
Cancel
Mute
OK
Scroll through the events list using the scroll buttons as shown
Using to scroll keys show to the left scroll to the View Disabled screen
Press "OK"
View Log
View
1:5:1
1:5
System Healthy
1 Zone(s) Active
hh.mm.ss
dd.mm.yy
000AC
i
Time Event PA LP AD Type
Log (000)
52
Page 53
FPE
Operations (Soft Reset)
The "Soft Reset" screen is accessed as shown below. The Operations screens are accessed from the healthy screen by first pressing any button. You will then be prompted to enter the passcode which will show the events screen by default, press the "Scroll Down" button until the "Soft Reset" screen is shown as illustrated below. Press "OK" and scroll through the list of options using the UP and Down arrow buttons and pressing "OK" to select.
Enter Passcode
Operations
3
Soft Reset
3.1
Soft Reset
Reset
Cancel
Mute
OK
Scroll through the events list using the scroll buttons as shown
System Healthy
1 Zone(s) Active
hh.mm.ss
dd.mm.yy
000AC
Press "OK"
Press "OK"
53
OR Press 8
Page 54
FPE
Operations (Evacuate)
The "Evacuate" screen is accessed as shown below. The Operations screens are accessed from the healthy screen by first pressing any button. You will then be prompted to enter the passcode which will show the events screen by default, press the "Scroll Down" button until the "Evacuate" screen is shown as illustrated below. Press "OK" and scroll through the list of options using the UP and Down arrow buttons and pressing "OK" to select.
Enter Passcode
Operations
3
Evacuate
3.2
Evacuate Activated
Reset
Cancel
Mute
OK
Scroll through the events list using the scroll buttons as shown
System Healthy
1 Zone(s) Active
hh.mm.ss
dd.mm.yy
000AC
Press "OK"
Press "OK"
54
Page 55
FPE
Operations (Silence Alarms)
The "Silence Alarms" screen is accessed as shown below. The Operations screens are accessed from the healthy screen by first pressing any button. You will then be prompted to enter the passcode which will show the events screen by default, press the "Scroll Down" button until the "Silence Alarms" screen is shown as illustrated below. Press "OK" and scroll through the list of options using the UP and Down arrow buttons and pressing "OK" to select.
Enter Passcode
Operations
3
Silence Alarms
3.3
Reset
Cancel
Mute
OK
Scroll through the events list using the scroll buttons as shown
System Healthy
1 Zone(s) Active
hh.mm.ss
dd.mm.yy
000AC
Press "OK"
Press "OK"
55
Page 56
FPE
Operations (Lamp Test)
The "Lamp Test" screen is accessed as shown below. The Operations screens are accessed from the healthy screen by first pressing any button. You will then be prompted to enter the passcode which will show the events screen by default, press the "Scroll Down" button until the "Lamp Test" screen is shown as illustrated below. Press "OK" and scroll through the list of options using the UP and Down arrow buttons and pressing "OK" to select.
Enter Passcode
Operations
3
Lamp Test
3.4
Lamp Test
Reset
Cancel
Mute
OK
Scroll through the events list using the scroll buttons as shown
System Healthy
1 Zone(s) Active
hh.mm.ss
dd.mm.yy
000AC
Press "OK"
Press "OK"
56
Page 57
FPE
Operations (Weekly Test)
The "Weekly Test" screen is accessed as shown below. The Operations screens are accessed from the healthy screen by first pressing any button. You will then be prompted to enter the passcode which will show the events screen by default, press the "Scroll Down" button until the "Weekly Test" screen is shown as illustrated below. Press "OK" and scroll through the list of options using the UP and Down arrow buttons and pressing "OK" to select.
Enter Passcode
Operations
3
Weekly Test
Weekly Test:
Waiting for Fire...
3.5
Soft Reset
Reset
Cancel
Mute
OK
Scroll through the operations list using the scroll buttons as shown
System Healthy
1 Zone(s) Active
hh.mm.ss
dd.mm.yy
000AC
Press "OK"
Put Fire on System or Time Out
Press "OK"
57
Features outside EN54 spec
Page 58
Access Level 2
Section 4
58
Page 59
FPE
Commissioning
The "Commissioning" screen is accessed as shown below. The events screens are accessed from the healthy screen by first pressing any button. You will then be prompted to enter the passcode which will show the screen below by default. Press "OK" and scroll through the list of events using the UP and Down arrow buttons.
Commission
Enter Passcode
Reset
Cancel
Mute
OK
Scroll through the events list using the scroll buttons as shown
Using to scroll keys show to the left scroll to the Commission screen
Press "OK"
PC to Panel
Panel to PC
Autolearn
1:2
1:1
1
1:3
System Healthy
1 Zone(s) Active
hh.mm.ss
dd.mm.yy
000AC
59
Page 60
FPE
Panel Settings (Erase Log)
The "Erase Log" screen is accessed as shown below. The events screens are accessed from the healthy screen by first pressing any button. You will then be prompted to enter the passcode which will show the screen below by default. Press "OK" and scroll through the list of events using the UP and Down arrow buttons.
Panel Settings
Enter Passcode
Reset
Cancel
Mute
OK
Scroll through the events list using the scroll buttons as shown
Using to scroll keys show to the left scroll to the View Disabled screen
Press "OK"
Press "OK"
Press "OK"
Erase Log
Erase Entire Log?
Erase Entire Log?
Erasing....
2:1
2
System Healthy
1 Zone(s) Active
hh.mm.ss
dd.mm.yy
000AC
60
OK to continue
CANCEL to exit
OK to continue
CANCEL to exit
Page 61
FPE
Panel Settings (Change Password)
The "Change Password" screen is accessed as shown below. The events screens are accessed from the healthy screen by first pressing any button. You will then be prompted to enter the passcode which will show the screen below by default. Press "OK" and scroll through the list of events using the UP and Down arrow buttons.
Panel Settings
Enter Passcode
Reset
Cancel
Mute
OK
Scroll through the events list using the scroll buttons as shown
Using to scroll keys show to the left
scroll to the Change Password screen
Press "OK"
Change Password
Enter New Password
2:3
2
System Healthy
1 Zone(s) Active
hh.mm.ss
dd.mm.yy
000AC
Press "OK"
61
Page 62
FPE
Panel Settings (Change Language)
The "Change Language" screen is accessed as shown below. The events screens are accessed from the healthy screen by first pressing any button. You will then be prompted to enter the passcode which will show the screen below by default. Press "OK" and scroll through the list of events using the UP and Down arrow buttons.
Panel Settings
Enter Passcode
Reset
Cancel
Mute
OK
Scroll through the events list using the scroll buttons as shown
Using to scroll keys show to the left
scroll to the Change Language screen
Press "OK"
Change Language
2:3
2
System Healthy
1 Zone(s) Active
hh.mm.ss
dd.mm.yy
000AC
Press "OK"
English
62
French Italian Portugese
Select Language
Page 63
FPE
Panel Settings (Date / Time)
The "Change Date/Time" screen is accessed as shown below. The events screens are accessed from the healthy screen by first pressing any button. You will then be prompted to enter the passcode which will show the screen below by default. Press "OK" and scroll through the list of events using the UP and Down arrow buttons.
Panel Settings
Enter Passcode
Reset
Cancel
Mute
OK
Scroll through the events list using the scroll buttons as shown
Using to scroll keys show to the left
scroll to the Change Date/Time screen
Press "OK"
Set Date/Time
2:5
2
System Healthy
1 Zone(s) Active
hh.mm.ss
dd.mm.yy
000AC
Change Date
Change Hours
OK confirms change
Use up/down/left/right
09:38
63
Press "OK"
Page 64
FPE
Panel Settings (Systems Details)
The "System Details" screen is accessed as shown below. The events screens are accessed from the healthy screen by first pressing any button. You will then be prompted to enter the passcode which will show the screen below by default. Press "OK" and scroll through the list of events using the UP and Down arrow buttons.
Panel Settings
Enter Passcode
Reset
Cancel
Mute
OK
Scroll through the events list using the scroll buttons as shown
Using to scroll keys show to the left
scroll to the System Details screen
Press "OK"
System Details
2:5
2
System Healthy
1 Zone(s) Active
hh.mm.ss
dd.mm.yy
000AC
Scroll to other details
System Details
Prog Ver
V01.01.00 11-11-05 0x0000A5B7 0x0000A5B7
Date Chksum
CDR
CDR Csum
64
Press "OK"
Page 65
FPE
Testing (Test Device)
The "Test Device" screen is accessed as shown below. The events screens are accessed from the healthy screen by first pressing any button. You will then be prompted to enter the passcode which will show the screen below by default. Press "OK" and scroll through the list of events using the UP and Down arrow buttons.
Testing
Enter Passcode
Reset
Cancel
Mute
OK
Scroll through the events list using the scroll buttons as shown
Using to scroll keys show to the left
scroll to the Test Device screen
Press "OK"
Test Device
4:1
4
System Healthy
1 Zone(s) Active
hh.mm.ss
dd.mm.yy
000AC
Press "OK"
Loop 1
Loop 2
Use the scroll up and down buttons to highlight the device and the "OK" button to switch between "Test" and "Not in Test"
Switch between Loop 1 and Loop2 by using the sideways scroll buttons shown to the left and press "OK" to select.
Devices in Test
AD
Device
Status
65
Page 66
FPE
Testing (Test Zone)
The "Test Device" screen is accessed as shown below. The events screens are accessed from the healthy screen by first pressing any button. You will then be prompted to enter the passcode which will show the screen below by default. Press "OK" and scroll through the list of events using the UP and Down arrow buttons.
Testing
Enter Passcode
Reset
Cancel
Mute
OK
Scroll through the events list using the scroll buttons as shown
Using to scroll keys show to the left
scroll to the Test Zones screen
Press "OK"
Test Zone
4:2
4
System Healthy
1 Zone(s) Active
hh.mm.ss
dd.mm.yy
000AC
Press "OK"
Use the scroll up and down buttons to highlight the device and the "OK" button to switch between "Test" and "Not Test"
Zones in Test
Zone
Status
66
Page 67
FPE
Testing (Test Sound Levels)
The "Test Sound Levels" screen is accessed as shown below. The events screens are accessed from the healthy screen by first pressing any button. You will then be prompted to enter the passcode which will show the screen below by default. Press "OK" and scroll through the list of events using the UP and Down arrow buttons.
Enter Passcode
Reset
Cancel
Mute
OK
Scroll through the events list using the scroll buttons as shown
Using to scroll keys show to the left
scroll to the Test Sound Levels screen
Press "OK"
Test Sound Levels
4:3
4
System Healthy
1 Zone(s) Active
hh.mm.ss
dd.mm.yy
000AC
Press "OK"
Testing
Testing Sounder Levels
15secs ON - 30secs OFF
67
Page 68
FPE
Testing (One Man Walk Test)
The "One Man Walk Test" screen is accessed as shown below. The events screens are accessed from the healthy screen by first pressing any button. You will then be prompted to enter the passcode which will show the screen below by default. Press "OK" and scroll through the list of events using the UP and Down arrow buttons.
Enter Passcode
Reset
Cancel
Mute
OK
Scroll through the events list using the scroll buttons as shown
Using to scroll keys show to the left
scroll to the One Man Walk Test screen
Press "OK"
Press "OK"
One Man Walk Test
One Man Walk Test
4:4
4
System Healthy
1 Zone(s) Active
hh.mm.ss
dd.mm.yy
000AC
Press "OK"
Testing
Status
Disabled
68
Page 69
FPE
Testing (Global Flashing LED)
The "Global Flashing LED" screen is accessed as shown below. The events screens are accessed from the healthy screen by first pressing any button. You will then be prompted to enter the passcode which will show the screen below by default. Press "OK" and scroll through the list of events using the UP and Down arrow buttons.
Testing
Enter Passcode
Reset
Cancel
Mute
OK
Scroll through the events list using the scroll buttons as shown
Using to scroll keys show to the left
scroll to the Global Flashing screen
Press "OK"
Global Flashing LED
4.5
4
System Healthy
1 Zone(s) Active
hh.mm.ss
dd.mm.yy
000AC
69
Press "OK"
Press "OK"
Global flashing LED's
Status
Disabled
Page 70
FPE
Testing (Analogue Levels)
The "Analogue Levels" screen is accessed as shown below. The events screens are accessed from the healthy screen by first pressing any button. You will then be prompted to enter the passcode which will show the screen below by default. Press "OK" and scroll through the list of events using the UP and Down arrow buttons.
Testing
Enter Passcode
Reset
Cancel
Mute
OK
Scroll through the events list using the scroll buttons as shown
Using to scroll keys show to the left scroll to the Analogue Levels screen
Analogue Levels
4.6
4
System Healthy
1 Zone(s) Active
hh.mm.ss
dd.mm.yy
000AC
Press "OK"
Loop 1
Loop 2
Switch between Loop 1 and Loop2 by using the sideways scroll buttons shown to the left and press "OK" to select.
Device List
Analogue valve sceen
Device
Use the scroll up and down buttons to highlight the device and the "OK" to view Device Values
70
Address
Page 71
FPE
Device Config (Add Device)
The "Add Device" screen is accessed as shown below. The events screens are accessed from the healthy screen by first pressing any button. You will then be prompted to enter the passcode which will show the screen below by default. Press "OK" and scroll through the list of events using the UP and Down arrow buttons.
Device Config
Enter Passcode
Reset
Cancel
Mute
OK
Scroll through the events list using the scroll buttons as shown
Using to scroll keys show to the left
scroll to the Add Device screen
Add Device
5:1
5
System Healthy
1 Zone(s) Active
hh.mm.ss
dd.mm.yy
000AC
Press "OK"
Loop 1
Loop 2
Switch between Loop 1 and Loop2 by using the sideways scroll buttons shown to the left and press "OK" to select.
Searching..........
71
Page 72
FPE
Device Config (Delete Device)
The "Delete Device" screen is accessed as shown below. The events screens are accessed from the healthy screen by first pressing any button. You will then be prompted to enter the passcode which will show the screen below by default. Press "OK" and scroll through the list of events using the UP and Down arrow buttons.
Device Config
Enter Passcode
Reset
Cancel
Mute
OK
Scroll through the events list using the scroll buttons as shown
Using to scroll keys show to the left
scroll to the Add Device screen
Delete Device
5:2
5
System Healthy
1 Zone(s) Active
hh.mm.ss
dd.mm.yy
000AC
Press "OK"
Loop 1
Loop 2
Switch between Loop 1 and Loop2 by using the sideways scroll buttons shown to the left and press "OK" to select.
Device List
Address
Device
Use the scroll up and down buttons to highlight the device and the "OK" to select device
72
Page 73
Appendix
Section 4
73
Page 74
Spur Isolator CSI350
Installation
1. Fit the unit in position.
2. Connect the unit according to the diagram below.
Notes: A Spur Isolator must be used when making spurs from the analogue addressable panel loop. Without this unit, the self addressing features of the system will not function correctly. No addressing of the interface is required. See control panel operation for details.
Standard Connections
Notes:
1. Only connect cable screen to its adjacent earth terminal.
2. For maximum spur length / load see BS5839 Pt1:2002.
3. This unit can only be used with Cooper CAB300 detector bases and compatible sensors.
E
OUT
IN
SPUR
E
E
-
-
-
+
+
+
ANALOGUE ADDRESSABLE LOOP
NO END OF LINE RESISTOR REQUIRED
74
Page 75
L
N
E
E
+
-
E
+
-
E
+
-
E
+
-
E
E
-
-
-
-
+
+
+
+
N/O
BATT
C
N/C
BACK UP BATTERY
230V AC MAINS
ANALOGUE ADDRESSABLE LOOP
OUT
IN
6k8
6k8
6k8
6k8
FIRE RELAY
Installation
1. Remove the cover of the unit.
2. Fit the back-plate in position and pass the wires into it taking care not to damage the circuit board.
3. Connect the unit according to the diagram below.
Notes: No addressing of the interface is required. See control panel operation for details. This unit requires a permanent 230V AC supply.
Standard Connections
4 Way Sounder Controller CSC354
Notes:
1. Only connect cable screen to its adjacent earth terminal.
2. The end of line resistors must always be fitted, even if the sounder circuits are
Unused
75
Page 76
E
LOOP
OUT
IN
CALL POINT ZONE
DETECTOR ZONE
E
E E
-
-
- -
+
+
+ +
- OUT +
- IN +
- OUT +
- IN +
12K
EOLM-1
Analogue Addressable Loop
Zone Monitor Unit CZMU352
Installation
1. Separate the two halves of the unit.
2. Drill out (or knock out) the required cable entries in the surface mounting back-
box.
3. Fit the back-box in position and pass the wires into it.
4. Connect the unit according to the diagram below.
Notes: No addressing of the interface is required. See control panel operation for details.
Standard Connections
Notes:
1. This unit can only be used with CDBB300 detector base and compatible detectors.
2. Only connect cable screen to its adjacent earth terminal.
3. The end of line resistor must always be fitted, even if the spur is unused.
4. Maximum spur length - See BS5839 Pt1:2002 for Zone Coverage.
5. Maximum number of call points allowed is unlimited.
6. Detector zone end of line device is EOLM-1 (supplied)
7 Callpoint zone has end of line resistor
Callpoints can be connected with detectors on detector zone if preferred
76
Page 77
Shop Monitor Unit CSUM355
Installation
1. Separate the two halves of the unit.
2. Drill out (or knock out) the required cable entries in the surface mounting back-
box.
3. Fit the back-box in position and pass the wires into it.
4. Connect the unit according to the diagram below.
Notes: No addressing of the interface is required. See control panel operation for details.
Standard Connections
E
LOOP
OUT
IN
CALL POINT ZONE
DETECTOR ZONE
SOUNDER
EXTERNAL PSU MONITOR
24V EXTERNAL PSU INPUT
1
2
FIRE RELAY
E
E E
E
E
N/O
Fault Contact N/O
24V DC OUTPUT POWER SUPPLY UNIT
24V O/P
C
N/C
-
-
- -
+
+
+ +
+
+
-
-
+
+
+
+
-
-
-
-
- OUT +
- IN +
- OUT +
- IN +
6K8
12K
12K
12K
EOLM-1
Analogue Addressable Loop
Notes:
1. This unit can only be used with CDBB300 detector base and compatible detectors.
2. Only connect cable screen to its adjacent earth terminal.
3. The end of line resistor must always be fitted, even if the spur is unused.
4. Maximum spur length - See BS5839 Pt1:2002 for Zone Coverage.
5. Maximum number of call points allowed is unlimited.
6. Detector zone end of line device is EOLM-1
7 Callpoint zone has end of line resistor
Callpoints can be connected with detectors on detector zone if preferred
77
Page 78
1 way Input Output Unit CMIO353
Installation
1. Separate the two halves of the unit.
2. Drill out (or knock out) the required cable entries in the surface mounting back-
box.
3. Fit the back-box in position and pass the wires into it.
4. Connect the unit according the diagram below.
Notes: No addressing of the interface is required. See control panel operation for details.
Standard Connections
E
E
22k
5k6
E
C
N/C
N/O
IN
OUT
-
-
-
+
+
+
Analogue Addressable Loop
Volt-Free Output 230V Rated
SPUR INPUT
Notes:
1. Only connect cable screen to its adjacent earth terminal.
2. The end of line resistor must always be fitted, even if the spur is unused.
78
Page 79
+
S+
F
F+
S
_
_
_
_
_
_
_
_
_
_
Remote Indicator LED (optional)
+VIN
- VE COM OUT
Supply Voltage 18 - 30 V DC Cable Size 0.5 - 2.5mm² Recommended cable types FIRETUF,FP200 or MICC Mounting Hole Centres 50 - 80mm
Wiring Hints
! Each terminal is suitable for clamping up to 2 wires ! Clamping of 2 wires of very different diameters under one screw is not
recommended.
! Suitable for mounting to mounting boxes with 50-80mm fixing centres.
General
If difficulty is experienced when mounting the sensor, this may be due to the following:
! Wiring causing an obstruction - move or shorten wires. ! Although the base is tolerant to uneven mounting surfaces, a very uneven
surface may cause the base to deform when the mounting screws are tightened down - loosen screws to reduce this or slide base to a flat position.
WARNING: DO NOT USE HIGH VOLTAGE TESTERS WHEN SENSORS OR CONTROL PANEL ARE CONNECTED TO THE SYSTEM.
CF2000
Analogue Addressable
Fire Alarm Panel
Earth screen of cable to be continuous between sensors
Loop Start
Loop Finish
- VE COM IN
SensorBase Wiring CAB300
79
Page 80
NO
C
NC
FAULT
RELAY
+ 24V
O/P
FIRE R/E
FIRE P/E
CLASS
CHANGE
SOUNDER
CIRCUIT 1
LOOP 1
LOOP 2
AUX
RELAY
LOOP CIRCUITS
0V
S+
F-
F+
S-
-
+26V
+
+
-
-
+
-
+
-
Tx-
Tx+
S+
F-
F+
S-
+ 1 -
+ 2 -
SOUNDER
CIRCUIT 2
MIMIC
REPEATER
+ 1 -
+ 2 -
System Wiring
Any 300 Series Analogue Sensor can be Connected to the Loop
80
Page 81
Internal wall Sounder CAS381
Installation
1.Fix to mounting surface using two suitable screws - the rear gasket fits underneath the base and the sounder gasket fits inside the base.
Connection
WARNING: Do NOT use high voltage testers if ANY equipment is connected to the system. Earth scrreen must be continuous along entire length of loop.
NOTE
Care should be taken to ensure the cable does not put stress on the circuit board
E
E
IN
OUT
-
-
+
+
Analogue Addressable Loop
81
Page 82
IP66 Wall Sounder CAS381/WP
Installation
1.Drill required holes for the cable gland fixing
2.Drill out the required fixing holes
3.Fix to mounting surface using two suitable screws
Connections
WARNING: Do NOT use high voltage testers if ANY equipment is connected to the system. Earth scrreen must be continuous along entire length of loop.
E
E
IN
OUT
-
-
+
+
Analogue Addressable Loop
82
Page 83
+
+
-
-
+
+
-
-
S+
F
F+
S
_
_
_
_
_
_
_
_
_
_
CF2000
Analogue Addressable
Fire Alarm Panel
Loop Start
Loop Finish
Base Sounder (CAS380 + CASC)
Supply Voltage : 17 ~ 32 Vdc Cable Size / type : 0.5 ~ 2.5mm/ FIRETUF, FP200 or MICC Standby current : < 320 uA Operating temperature : -10 to +55 degrees C (95%RH)
Sound output @ +/-3dB : Low volume : 84dB @ <4mA (set by panel) : Medium volume : 92dB @ <8mA
: High volume : 95dB @ <12mA
Tones : Continuous 910Hz (set by panel) : Pulsed 910Hz / 0Hz pulse 1Hz
: Two tone 610 / 910Hz @ 1Hz cycle : Slow whoop 500-1200Hz in 3.5 seconds /
0.5secs gap
83
Page 84
3 way Input output unit CIO351
E
E
22k
22k
5k6
5k6
-
-
-
-
-
+
+
+
+
+
LOOP
IN
OUT
ANALOGUE ADDRESSABLE LOOP
INPUTS
OUTPUTS
N/O
N/O
N/O
C
C
C
N/C
N/C
N/C
22k
5k6
Installation
1. Separate the two halves of the unit.
2. Drill out (or knock out) the required cable entries in the surface mounting back-box.
3. Fit the back-box in position and pass the wires into it.
4. Connect the unit according to the diagram below.
Notes: No addressing of the interface is required. See control panel operation for details.
Standard Connections
Notes:
1. Only connect cable screen to its adjacent earth terminal.
2. The end of line resistor must always be fitted, even if the inputs are unused.
3. Monitored inputs can detect open or short circuit faults.
4. Output relays are volt-free contacts and are not monitored.
84
Page 85
Loop Powered Beacon (CAB382)
E
E
IN
OUT
-
-
+
+
Analogue Addressable Loop
LOOP IN
LOOP OUT
Connection Details
Earth screen of cable to be continuous between beacons
Warning:
Do NOT use high voltage testers if any equipment is connected to the system.
85
Page 86
Call Point (CBG370, CBG370/S, CBG370/WP)
E
E
IN
OUT
-
-
+
+
Analogue Addressable Loop
LOOP IN
LOOP OUT
86
Page 87
87
PINSTCF2000
CE Marking
0832 – CPD – 1089
0832 – CPD – 1089
714h/02
714h/02
EN 54-2 1997 & A1:2006
CF2000
Control and indicating equipment for fire detection and fire
alarm systems for buildings
EN 54-2 Clause
Options Provided
7.8 Output to fire alarm devices
7.9.1 Output to fire alarm routing equipment
7.10.1 Output to automatic fire protection equipment (type A)
7.11 Delays to outputs
7.12.3 Dependencies on more than one alarm signal-Type C
7.13 Alarm counter
8.9 Output to fault routing equipment
9.5 Disablement of each point 10 Test condition
Other technical data: see Doc. PR202-50-502 held by the
manufacturer
EN 54-4 1997 & A1:2002 A2:2006
CF2000
Power supply equipment for fire detection and fire alarm
systems for buildings
Other technical data: see Doc. PR202-50-502 held by the
manufacturer
Cooper Lighting and Safety Ltd
Wheatley Hall Road
Doncaster
South Yorkshire
DN2 4NB
09
Cooper Lighting and Safety Ltd
Wheatley Hall Road
Doncaster
South Yorkshire
DN2 4NB
09
E
R
C
T
I
F
N
I
C
O
A
I
T
T
I
N
O
E
N
V
E
B
R
O
P
A
S
R
S
D
O
L
LPCB
E
R
C
T
I
F
N
I
C
O
A
I
T
T
I
N
O
E
N
V
E
B
R
O
P
A
S
R
S
D
O
L
LPCB
Page 88
Battery Disposal Instructions
Although batteries contain lead and small amounts of antimony and arsenic, they are safe if handled according to the accompanying guide. The battery cells must not be dismantled as this involves several hazards, which are best handled under controlled conditions, using specialised equipment. No attempt should be made to repair any batteries; they should be treated as disposable when they have outlived their use.
Batteries must be disposed of in accordance with current waste disposal and pollution legislation and in particular; The Environment Protection Act 1990, Special Waste Regulation 1996. It is recommended that the following authorities are contacted before any attempt is made to dispose of batteries; Environment Agency Local office, Local Authority Environmental Health or Waste Handling department.
88
PINSTCF2000
Loading...