6.6 Other webmodules ................................................................................................ 15
7 Example of locating a luminaire failure ..................................................... 16
8 Data gets synchronized .............................................................................. 19
CEAG Notlichtsysteme GmbH3
Operating Instructions
Webmodule ZB-S
Service
Störung
Failure
24V
+
-
PE
1 Safety
Instructions
The Webmodule ZB-S shall
only be used for its intended
purpose and in undamaged
and perfect condition!
When working on the elec-
tronic device make sure that
it is disconnected from the
voltage! Pay attention to the
different power supplies in
mains or battery operation.
Observe the national safety
rules and regulations for
prevention of accidents as
well as the safety instructions included in these operating instructions marked
with !
2 Conformity with
standards
Conform to: EN 60950-1.
Developed, manufactured and tested acc. to ISO
9001.
3 Technical data
Supply
voltage: 24 V DC
Power
consumption: < 1.5 W
Connection: RJ45
Insulation class: III
Degree of protection acc. to
EN 60529: IP 20
Ambient temperature:
-10 °C .. +55 °C
Connection
terminal: 1,5 mm²
Weight: 0,1kg
Dimensions:
90 x 35 x 58mm
3.1 Description /
Scope of application
The webmodule ZB-S for
visualisation and monitoring
of a central battery system
ZB-S via local ethernet (LAN)
with a customary WEB-browser (e. g. Internet Explorer
TM).
Integrated mail-client for a
comfortable and event based
failure notification for up to 5
email addressees. Password
protected access accounts
capable of parametrisation.
Note:
For operation of the webmodule with a ZB-S system
the following software-state
must be installed in the controle module:
P/F/H (Mega 128/RS485/
FTT 10A)
4 Installation
For the mounting
and operation of
electrical apparatus, the
respective national safety
regulations as well as the
general rules of engineering
will have to be observed!
4.1 Mounting
Pay attention to temperatures outside the permitted
range during operation. The
permissible ambient temperature may not exceed
55°C.
The module was designed for
DIN rail mounting (2TE) to be
only mounted in the cabinet.
An external mounting outside the ZB-S cabinet is not
permitted.
4.2 Electrical connection
Status/
Failure LED
Network
connection
RJ45
Service
Pin
Connection of
the 6-pole
data cable to
the control
unit ST-S
+ - PE
24 V DC from
DC/DC inverter
The webmodule ZB-S is
supplied with 24V DC of the
DC-DC inverter of the ZB-S.
The PE connector must be
connected to the protection
earth (PE) in the ZB-S.
Note: The DC-DC inverter
can supply max. 20 pcs.
further DLS/3Ph-busmodules/TLS-modules!
The 6-pole data cable connects the webmodule with
the ST-S control unit:
CEAG Notlichtsysteme GmbH
4
Operating Instructions
Webmodule ZB-S
Connection of the data
cable to the control unit
ST-S
Note:
Keep the distance of the
data cable between the
webmodule and the control unit ST-S as short as
possible. Please avoid a
wiring around the charging unit.
4.3 Commissioning the
Webmodule on the
ZB-S
After connection of the
power supply (24V DC), the
webmodule needs approx.
1.5 minutes for booting.
After the booting, the red
LED of the webmodule
flashes slowly. To log on
the webmodule on the ST-S
control unit, the service pin
of the webmodule must
be pressed for approx. 1
second.
The menu „webserver
setup“ appears in the
display of the control unit
of the ZB-S. During the log
on procedure the display
shows a lot of question
marks.
After approx. 3-5 seconds
the display shows the
standard settings of the
webmodule:
The webmodule gets
automatically activated to
the control unit, which is
displayed by the red LED
(some seconds) of the control unit and the webmodule. After 1-2 minutes the
procedure is finished and
the webmodule is ready to
operate.
LED-display of the webmodule:
LED flashes slowly:
webmodule is not activated
on the control unit.
Status-LED flashes fastly
3x :
when pushing the service
pin for approx. 10 seconds
the webmodule will be set
back into delivery status.
Service pin of the webmodule:
Pressing the service pin for:
1 sec.: login/logout of the
webmodule on the control
unit ST-S
> 10 sec.: resets the module to the delivery status
Attention!
All programmed data get
lost!
4.4 Deactivate the
webmodule on the
control unit ZB-S
The webmodule can be
deactivated on the control
unit. For this, the service
pin of the webmodule has
to be pressed for approx. 1
sec. The screen showed in
the picture above appears.
With the push button „arrow
left“ or „arrow right“ the
webmodule can be set as
„not installed“. Press o.k.
and back with menu button.
Now the webmodule is offline and the red LED flashes
slowly.
CEAG Notlichtsysteme GmbH5
Operating Instructions
Webmodule ZB-S
During activities on the control unit of the ZB-S, e.g.
programming of luminaires,
it is possible that the connection between the control
unit and the webmodule is
interrupted for a short time.
This gets displayed by a red
LED on the control unit or
rather on the webmodule.
Direct access via IP-address:
. g.: 192.168.100.5
e
Furthermore the webbrowser shows „data is synchronized“. The connection will
automatically be restored
after a short time.
4.5 Monitoring via an
internet browser
Functional schematic:
with HTTP via TCP
The webmodule allows a
visualisation of a ZB-S/
US-S central battery system
via ethernet.
If the device shall be installed in a factory intranet
it is necessary to get all
required information, like
network settings or mail
settings from the IT-department in charge (see chapter
6.4, Settings)
CEAG Notlichtsysteme GmbH
6
Operating Instructions
Webmodule ZB-S
5 Homepage / Login
By entering the TCP/IPaddress (s. 5.a: ex works: