GENERAL:
The AMT Multitone Strobe Appliance is UL Listed under Standard 1971 for Emergency Appliances for the Hearing Impaired and UL Standard 464 for Audible
Appliances. The AMT is also ULC Listed under Standard CAN/ULC-S526-02 for Visual Signaling and under Standard CAN/ULC-S525-99 for Audible Signal
Devices for Fire Alarm Systems. The AMT Strobes can provide a non-synchronized strobe appliance when connected directly to a Fire Alarm Control Panel (FACP),
or provide a synchronized strobe appliance when used in conjunction with a Sync Module (SM), Dual Sync Module (DSM) or Wheelock power supplies. They are
listed for wall mount only,
candela under UL Standard 1971 and meet 75 candela intensity on axis with low current draw. The 24MCW model strobe can provide 4 selectable candela settings (15,
30, 75, 110). The AMT Multitone Strobe Appliances use a xenon flashtube with solid state circuitry enclosed in a polycarbonate lens to provide maximum visibility
and reliability for effective visible signaling.
Wheelock's AMT Appliances are unique multitone alarm signals with separate input terminals for each sound. They are the ideal choice for suppression systems and
emergency signaling systems where distinctive multiple alarm conditions are required. Eight groups of three self-prioritized sound outputs are provided with separate
electrically isolated input terminals for each sound (see Table 2 and Table 8 for sound selections). Sound output can be field set to provide either HIGH (HI) dBA or
STANDARD (STD) dBA sound output level.
All AMT Multitone Strobe models are designed for use with either filtered or unfiltered Full-Wave-Rectified (FWR) input voltage. The AMT Multitone Strobe
Appliances have separate input terminals for alarm tone activation and strobe activation. The strobes can be easily field programmed to operate independently or in
unison with all of the audible alarms. All inputs are polarized for compatibility with standard reverse polarity supervision of circuit wiring by a fire alarm control panel
(FACP).
NOTE: All Canadian Installations should be in accordance with the Canadian Standard for the Installation of Fire Alarm Systems - CAN/ULC-S524-01 and Canadian
Electrical Code, Part 1. Final acceptance is subject to Authorities Having Jurisdiction.
WARNING: PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF
THE FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR
OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS
INJURY OR DEATH TO YOU AND/OR OTHERS.
1. Strobes will produce 1 flash per second over the “Regulated Voltage” Range.
2. The strobe meets the required light distribution patterns defined in UL 1971 and ULC-S526-02.
3. All models are UL Listed for indoor use with a temperature range of +32°F to +120°F (0°C to +49°C) and maximum humidity of 93% ± 2% RH. The effect of
shipping and storage temperatures do not adversely affect the performance of the appliances when stored in the original cartons and are not subjected to misuse.
WARNING: THESE APPLIANCES WERE TESTED TO THE REGULATED VOLTAGE LIMITS OF 16.0-33.0 VOLTS FOR 24V MODELS USING
FILTERED DC OR UNFILTERED FULL-WAVE-RECTIFIED VOLTAGE. DO NOT APPLY VOLTAGE OUTSIDE OF THIS RANGE.
WARNING: CHECK THE MINIMUM AND MAXIMUM OUTPUT OF THE POWER SUPPLY AND STANDBY BATTERY AND SUBTRACT THE
VOLTAGE DROP FROM THE CIRCUIT WIRING RESISTANCE TO DETERMINE THE APPLIED VOLTAGE TO THE STROBES. THE MAXIMUM
WIRE IMPEDENCE BETWEEN STROBES SHALL NOT EXCEED 35 OHMS.
CAUTION: These notification appliances are UL Listed as “Regulated”. They are intended to be used with FACPs whose notification circuits are UL Listed as
“Regulated.” These appliances shall not be used on UL Listed “Special Application” notification circuits unless the appliances are identified to be compatible in the
installation instructions of the FACP or unless the FACP is identified to be compatible in this instruction manual.
Copyright 2005 Wheelock, Inc. All rights reserved. P84158 F
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
with the backboxes specified in these instructions (See wiring and mounting information). Models with 1575W strobes are listed at 15
Table 1: UL/ULC Listed Models
UL Ratings ULC Ratings
Regulated
Voltage
(VDC/VRMS)
Voltage
Range
(VDC/VRMS)
Strobe Candela
(cd)
Reverberant
dBA
At 10 Feet
Voltage
Range
(VDC/VRMS)
Strobe Candela
(cd)
Anechoic
dBA
at 10 Feet
* 1575 models are Listed at 15cd and meet 75 on axis.
Table 2: Ratings for AMT Multitone Audible Signals
Tone Tone Description
Horn Broadband Horn (Continuous)
Bell 1560Hz Modulated (0.07 Sec. ON/Repeat)
March Time Horn Horn (0.25 Sec. ON/0.25 Sec. OFF/Repeat)
Code 3 Horn Horn (ANSI S3.41 Temporal Pattern)
Code 3 Tone 500Hz (ANSI S3.41 Temporal Pattern)
Slow Whoop 500-1200Hz Sweep (4.0 Sec. ON/0.5 Sec. OFF/Repeat)
Siren 600-1200Hz Sweep (1.0 Sec. ON/Repeat)
HI/LO 1000/800Hz (0.25 Sec. ON/Alternate)
Vibrating Chime 700Hz (1.0 Sec. Decay/Repeat)
Sheet 1 of 8
Use Tables 3, 3A, 4, and 4A to determine the highest value of “Rated Current” for an individual AMT strobe (across the expected operating voltage range of the AMT
strobe). Add strobe current from Table 3 or 3A to audible appliance current from Table 2 and 2A to obtain total current for each unit, if the strobe and audible are wired
to operate in unison on a single circuit. Be sure to add the currents for any other appliances, including audible signaling appliances, powered by the same source and
include any required safety factors.
NOTE: The maximum number of strobes on a single notification appliance circuit shall not exceed 50.
Table 3: UL Current Ratings for Horn Only (AMPS)
Tone
Horn
Bell
HI/LO
Volume
Maximum RMS Current Per UL 464
DC FWR
HI 0.108 0.092
STD 0.043 0.050
HI 0.053 0.040
STD 0.026 0.028
March HI 0.108 0.092
Time STD 0.035 0.050
Code 3 HI 0.108 0.092
Horn STD 0.043 0.050
Code 3 HI 0.060 0.051
Tone STD 0.030 0.031
Slow HI 0.112 0.092
Whoop STD 0.044 0.050
Siren
HI/LO
Chime
HI 0.102 0.078
STD 0.038 0.043
HI 0.064 0.049
STD 0.030 0.034
HI 0.041 0.033
STD 0.020 0.022
Table 3A: ULC Current Ratings for Horn Only (AMPS)
Tone STD 0.012 0.015 0.02 0.012 0.015 0.020
Slow HI 0.037 0.045 0.062 0.037 0.045 0.062
Whoop STD 0.022 0.026 0.034 0.022 0.026 0.034
Siren
HI/LO
Chime
HI 0.032 0.039 0.048 0.032 0.039 0.048
STD 0.017 0.020 0.027 0.017 0.020 0.027
HI 0.019 0.023 0.030 0.019 0.023 0.030
STD 0.014 0.017 0.022 0.014 0.017 0.022
HI 0.012 0.014 0.018 0.012 0.014 0.018
STD 0.009 0.011 0.014 0.009 0.011 0.014
WARNING: CANDELA SETTING WILL DETERMINE THE CURRENT DRAW OF THE PRODUCT.
Table 4: Current Ratings for 24MCW (Strobe Only)
Maximum RMS Current (AMPS)
Voltage 15cd 30cd 75cd 110cd
DC 16-33VDC 0.060 0.092 0.165 0.220
FWR 16-33VRMS 0.102 0.155 0.253 0.347
Table 4A: Current Ratings for 241575W (Strobe Only)
Maximum RMS Current (AMPS)
Voltage 241575W
DC 16-33VDC 0.090
FWR 16-33VRMS 0.145
WARNING: MAKE SURE THAT THE TOTAL RMS CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE
SYSTEM’S PRIMARY AND SECONDARY POWER SOURCES, APPLIANCE CIRCUITS, SM, DSM SYNC MODULES AND WHEELOCK POWER
SUPPLIES DOES NOT EXCEED THE POWER SOURCES’ RATED CAPACITY OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS
TO WHICH THESE APPLIANCES ARE WIRED. OVERLOADING POWER SOURCES OR EXCEEDING FUSE RATINGS COULD RESULT IN LOSS
OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN PROPERTY DAMAGE AND
SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
P84158 F
Sheet 2 of 8
Table 5: UL/ULC dBA Ratings
Tone
HI/LO
Volume
dBA Reverberant Ratings
Per UL 464
16V 24V 33V 20V 24V 31V
dBA Anechoic Ratings
Per CAN/ULC-S525-99
HI 89 92 94 96 98 99
Horn
STD 82 86 88 90 92 93
HI 80 84 87 89 91 92
Bell
STD 73 78 81 84 86 87
HI 84 88 91 96 98 99 March
Time
STD 79 82 85 90 92 93
HI 84 88 90 96 98 99 Code 3
Horn
STD 78 81 84 90 92 93
HI 81 84 87 92 94 95 Code 3
Tone
STD 75 78 82 87 89 90
HI 85 88 90 96 98 99 Slow
Whoop
STD 79 83 86 91 93 94
HI 85 89 91 95 97 98
Siren
STD 79 83 85 90 92 93
HI 82 86 88 90 92 93
HI/LO
STD 77 81 83 85 87 88
HI 74 78 81 86 88 89
Chime
STD 66 71 74 80 82 87
Table 5A: ULC Directional Characteristics
24VDC
Horizontal
Vertical
-3dBA: 45 degrees left and right
-6dBA: 70 degrees left, 65 degrees right
-3dBA: 80 degrees upward, 50 degrees downward
-6dBA: 90+ degrees upward, 75 degrees downward
WARNING: THE AMT MULTITONE STROBE APPLIANCE MUST BE FIELD SET TO THE DESIRED dBA SOUND OUTPUT LEVEL AND
ALARM TONE BEFORE THEY ARE INSTALLED. THIS IS DONE BY PROPERLY ADJUSTING A FOUR POSITION SWITCH IN ACCORDANCE
WITH THESE INSTRUCTIONS. INCORRECT SETTINGS WILL RESULT IN IMPROPER PERFORMANCE AND MAY DAMAGE THE PRODUCT,
WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
AMT MULTITONE SETTINGS:
The Switch (SW1) of the AMT Multitone Strobe Appliances, shown in Figure 2, is used to set the desired alarm tone and dBA sound output level. The factory settings
are shown below. Read these instructions carefully before changing any of these factory settings.
Figure 1: PC Board Layout Showing Location
of Candela Selector and Switch (SW1)
SLIDE HERE FOR (1)
TOP
S
S
ON
24
W
1
1 2 3 4
DP2
+
+
PRI 1
-
DP3
PRI 2
-
+
STB -+ PRI 3
-
ON
W
1
1 2 3 4
CANDELA SELECTOR
24
SLIDE HERE FOR (0)
15
75
30
110
CANDELA
POINTER
The factory settings for the 24VDC models are:
HIGH dBA: SW1 POS 1 = 1
Priority 1 (PRI 1) HORN TONE:
Priority 2 (PRI 2) BELL TONE:
Priority 3 (PRI 3) SIREN TONE:
SW1 POS 2, 3, 4 = 1, 1, 1
}
STEP 1: (AMT-24MCW ONLY)
Factory setting is on 15 Candela.
Move the candela selector to the desired setting.
The setting is indicated by the pointer and can be seen on the bottom side of the lens.
WARNING: THE CANDELA SELECT SWITCH MUST BE FIELD SET TO THE REQUIRED CANDELA INTENSITY BEFORE INSTALLATION.
WHEN CHANGING THE SETTING OF THE CANDELA SELECT SWITCH, MAKE CERTAIN THAT IT “CLICKS” IN PLACE. AFTER CHANGING
THE CANDELA SETTING, THE APPLIANCE MUST BE RETESTED TO VERIFY PROPER OPERATION. IMPROPER SETTING OF THE CANDELA
SELECT SWITCH MAY RESULT IN OPERATION AT THE WRONG CANDELA, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS
INJURY OR DEATH TO YOU AND/OR OTHERS.
STEP 2:
Set desired dBA sound output level as follows (Refer to Figure 2):
AMT Multitone Appliances cannot be field set for input voltage. AMT Multitone Strobe Appliances are field set for dBA sound output level by adjusting a four
position Switch (SW1) as shown in Table 6 and Figure 2. Use SW1 Position 1 to select the dBA sound output level.
Table 6: dBA Sound Output Level Settings
Decibel Level SW1 Settings
HIGH dBA:
STD dBA:
Set SW1 POS 1 on 1 (Factory Setting)
Set SW1 POS 1 on 0
P84158 F
Sheet 3 of 8
Figure 2:
WARNING: DOUBLE CHECK THE SWITCH (SW1) SETTINGS TO MAKE SURE THEY ARE CORRECT. IMPROPER SETTINGS CAN
DAMAGE THE UNIT OR RESULT IN NO SOUND OUTPUT OR A dBA SOUND OUTPUT LEVEL THAT IS BELOW THE MINIMUM CODE
REQUIREMENTS FOR PUBLIC MODE FIRE PROTECTION. THIS COULD RESULT IN PROPERTY DAMAGE, SERIOUS INJURY OR DEATH TO
YOU AND/OR OTHERS.
CAUTION: If Multitone Strobe Appliances are operated within 15 inches of a person’s ear, they can produce a sound pressure level that exceeds the maximum
120 dBA permitted by ADA and OSHA rules. Exposure to such sound levels can result in damage to a person’s hearing.
STEP 3:
Set the desired alarm tones as follows (Refer to Figure 2 and Table 7):
AMT Multitone Strobe Appliances are field set for any one of eight groups of self-prioritized tones by setting a four position switch (SW1) as shown in Figure 2 and
Table 7. Use SW1 POS 2,3,4 to select the desired alarm tones.
Table 7: Alarm Tones
Tones Switch Settings
PRI 1 PRI 2 PRI 3 POS 2 POS 3 POS 4
Horn Bell Siren 1 1 1
Code 3 Horn Siren Vibrating Chime 1 0 1
Slow Whoop March Time Horn HI/LO 0 0 1
March Time Horn HI/LO Vibrating Chimes 1 1 0
Code 3 Horn Bell Siren 0 1 1
Siren Horn Vibrating Chime 0 1 0
Bell March Time Horn Siren 1 0 0
NOTE: The prioritized tones contained in each group is factory pre-set which can not be changed.
Code 3 Tone HI/LO Siren 0 0 0
NOTE: The Code 3 Horn and Code 3 Tone (set on HIGH dBA) incorporate the temporal pattern specified by ANSI/NFPA for standard emergency evacuation
signaling. They should be used only for fire evacuation signaling and not for any other purpose.
The Horn and Bell Tones can be used on coded systems with a minimum On-Time of 1/4 second if the audible and strobe are wired to operate independently. All other
tones are recommended for use only on continuous (non-coded) systems.
CAUTION: Strobes are not designed to be used on coded systems in which the applied voltage is cycled on and off.
STROBE SETTINGS:
The jumper plugs (DP2 and DP3), shown in Figure 3, are used to set for simultaneous actuation of the strobe with all 3 of the audible inputs or for independent actuation
of the strobe.
For independent strobe actuation, set the jumper plugs DP2 and DP3 as shown.
Figure 4: Independent Strobe Actuation Setting
DP2
DP3
DP2
DP3
+
PRI 2
+
PRI 1
-
-
PRI 3
+
PRI 4
-
-+
The factory setting is for simultaneous actuation of the strobe with all 3 audible
inputs.
NOTE: The strobe input is required only for independent actuation of the
strobe.
P84158 F
Sheet 4 of 8
WIRING DIAGRAMS:
Supervised System
PRI 1PRI 2PRI 3
(+) (-) (+) (-)(-)(-)
(+)
(+)
PRI 1
PRI 2
PRI 3
Isolated inputs are provided for independent supervision and actuation of the three audible inputs and strobe.
Unsupervised System
Common Positive
PRI 1 PRI 2 PRI 3
(+) (-)
PRI 1
PRI 2
PRI 3
For applications not requiring supervision: Connect all positive (+) terminals
to the power source. The negative (-) terminal for each signal will actuate the
appliance.
In case of simultaneous inputs, the three audible outputs are self-prioritized as follows: 1st priortiy= PRI 1; 2nd priority = PRI 2; 3rd priority = PRI 3.
(+) (-)
(+) (-) (+) (-)
PRI 1
PRI 2
PRI 3
For applications not requiring supervision: connect all
negative (-) terminals to the power source. The positive (+) terminal for each
signal will actuate the appliance.
PRI 1
PRI 2
PRI 3
Unsupervised System
PRI 1 PRI 2 PRI 3
(+) (-)
PRI 1
PRI 2
PRI 3
Common Negative
(+) (-)
(+) (-)
(+) (-)
PRI 1
PRI 2
PRI 3
Leave any unused inputs disconnected.
WARNING: NFPA CODES REQUIRE SIGNALING DEVICES TO BE SUPERVISED. CHECK TO BE CERTAIN THAT UNSUPERVISED
SIGNALING DEVICES DO NOT VIOLATE ANY APPLICABLE CODES.
1. AMT Multitone Strobe models have in-out wiring terminals that accept two #12 to #18
American Wire Gauge (AWG) wires at each screw terminal. Strip leads 3/8 inches and
connect to screw terminals.
2. Break all in-out wire runs on supervised circuits to assure integrity of circuit supervision as
shown on left. The polarity shown in the wiring diagrams is for operation of the appliances.
The polarity is reversed by the FACP during supervision.
P84158 F
Sheet 5 of 8
MOUNTING OPTIONS:
CAUTION: The following figures show the maximum number of field wires (conductors) that can enter the backbox used with each mounting option. If these
limits are exceeded, there may be insufficient space in the backbox to accommodate the field wires and stresses from the wires could damage the product.
Although the limits shown for each mounting option comply with the National Electrical Code (NEC), Wheelock recommends use of the largest backbox option shown
and the use of approved stranded field wires, whenever possible, to provide additional wiring room for easy installation and minimum stress on the product from wiring.
Figure A
FLUSH (4" BOX)
4" SQ. X 2-1/8"
DEEP BACKBOX
Figure B
2-GANG x 3-1/2"
DEEP BACKBOX
FLUSH (2-GANG BOX)
Figure C
BACKBOX
(IOB)
SURFACE MOUNTING
Figure D
CONCEALED CONDUIT MOUN TING
BACKBOX
(IOB)
EXISTING
BOX IN WALL
#8-32 SCREWS
SCREW COVERS
MAXIMUM NUMBER OF CONDUCTORS
AWG #18 AWG #16 AWG #14 AWG #12
10488
MAXIMUM NUMBER OF CONDUCTORS
AWG #18 AWG #16 AWG #14 AWG #12
10488
#6-32 SCREWS
SCREW COVERS
MAXIMUM NUMBER OF CONDUCTORS
AWG #18 AWG #16 AWG #14 AWG #12
16161616
Figure E
RETROFIT PLATE MOUNTING
EXISTING FSB
BOX IN WALL
RETROFIT
PLATE
#8-32 SCREWS
SCREW COVERS
MAXIMUM NUMBER OF CONDUCTORS
AWG #18 AWG #16 AWG #14 AWG #12
16161616
Figure F
SURFACE OR SEMI-FLUSH (4" X 2-1/8" BOX)
DBB OR 4" SQ. X 2-1/8"
ISP EXTENDER
MAXIMUM NUMBER OF CONDUCTORS
AWG #18 AWG #16 AWG #14 AWG #12
DEEP BACKBOX
#8-32 SCREWS
SCREW COVERS
1681012
WOOD SCREWS
#8-18 SCREWS
SCREW COVERS
MAXIMUM NUMBER OF CONDUCTORS
AWG #18 AWG #16 AWG #14 AWG #12
16161616
Figure G
SURFACE OR SEMI-FLUSH (4" X 1-1/2" BOX)
DBB OR 4" SQ. X 1-1/2"
ISP EXTENDER
MAXIMUM NUMBER OF CONDUCTORS
AWG #18 AWG #16 AWG #14 AWG #12
DEEP BACKBOX
#8-32 SCREWS
SCREW COVERS
10488
#8-18 SCREWS
SCREW COVERS
MOUNTING NOTES:
CAUTION: Check that the installed product will have sufficient clearance and wiring room prior to installing backboxes and conduit, especially if sheathed
multiconductor cable or 3/4" conduit fittings are used.
1. AMT Multitone Strobe models can be flush mounted to a standard 4 inch square by 2-1/8 inch deep electrical box (Figure A) or a standard 2-gang by 3-1/2" inch
minimum deep electrical box (Figure B).
2. All models can also be surface mounted to Wheelock's model IOB backbox (Figure C or D) or to a 4" square backbox (model DBB or BB) with Wheelock's model
ISP extender (Figure F and G).
3. AMT Multitone Strobe models can also be retrofitted to an existing FSB backbox to replace Wheelock's model 7001 Strobe Horn when used with Wheelock
adaptor plate model RP (Figure E).
4. All models are supplied with four snap-in covers to hide the mounting holes and provide an attractive installation. The snap-in covers are interchangeable and have
slots on each end so they can be removed if necessary (by prying them up with a thin blade screwdriver). To insert snap-in cover, slide the outside edge of the
cover (furthest edge from the strobe lens) partially into the mounting hole recess; then align the cover so it is parallel to the grille (not tilted) and snap cover into
place.
5. The IOB surface backbox has 1/2 inch conduit knockouts on two sides. It has a variety of knockouts on the back for mounting it to recessed electrical boxes and
for wire entrances (Figure D). It can also be mounted to a surface with the two mounting ears that are supplied. The ears slide into slots on the back of the box
(Figure C). Use appropriate anchors for the wood screws that are supplied with the box (if necessary).
6. The IOB includes a prefastened gasket and four hole plugs. Make sure the condensation drain holes on the box face down and that the box is vertical to permit
drainage of any moisture. Use the mounting ears to secure the box (do not use the back knockouts). Use the hole plugs to seal the unused mounting holes on the
AMT Multitone grille (press them in securely from the back side of the grille). Mount the unit to the IOB with the four #8-18 screws supplied with the box.
7. Mounting hardware for each mounting option is supplied.
8. Conduit entrances to the backbox should be selected to provide sufficient wiring clearance for the installed product. When extension rings are required, conduit
should enter through the backbox, not the extension ring. Use Steel City #53151 (1-1/2" deep) or #53171 (2-1/8" deep) extension rings (as noted in the mounting
options) or equal with the same cut-out area.
9. When terminating field wires, do not use more lead length than required. Excess lead length could result in insufficient wiring space for the signaling device.
10. Use care and proper techniques to position the field wires in the backbox so that they use minimum space and produce minimum stress on the product. This is
especially important for stiff, heavy gauge wires and wires with thick insulation or sheathing.
11. Do not pass additional wires (used for other than the signaling device) through the backbox. Such additional wires could result in insufficient wiring space for the
signaling device.
P84158 F
Sheet 6 of 8
WARNING: WHEN INSTALLING STROBES IN AN OPEN OFFICE OR OTHER AREAS CONTAINING PARTITIONS OR OTHER VIEWING
OBSTRUCTIONS, SPECIAL ATTENTION SHOULD BE GIVEN TO THE LOCATION OF THE STROBES SO THAT THEIR OPERATING EFFECT
CAN BE SEEN BY ALL INTENDED VIEWERS, WITH THE INTENSITY, NUMBER, AND TYPE OF STROBES BEING SUFFICIENT TO MAKE SURE
THAT THE INTENDED VIEWER IS ALERTED BY PROPER ILLUMINATION, REGARDLESS OF THE VIEWER'S ORIENTATION. FAILURE TO
DO SO COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
The AMT-24MCW’s 110cd setting is Listed for use in sleeping or non-sleeping areas when installed in accordance with appropriate NFPA Standards and the Authority
Having Jurisdiction.
WARNING: INSTALLATION OF WHEELOCK 110 CANDELA STROBE PRODUCTS IN SLEEPING AREAS SHOULD BE WALL MOUNTED AT
LEAST 24" BELOW THE CEILING AS FOLLOWS: (1) THE ON AXIS (DIRECTLY IN FRONT OF LENS) LIGHT OUTPUT SHOULD BE DIRECTED
AT THE EYE-LIDS OF THE SLEEPING PERSON, E.G. PILLOW END OF BED, BED HEAD; (2) NO PART OF THE BED SHALL BE MORE THAN
SIXTEEN (16) FEET FROM THE STROBE NOTIFICATION APPLIANCE. INSTALLERS MUST ADVISE OWNERS AND OPERATORS OF
BUILDINGS WITH SLEEPING OCCUPANTS, E.G. HOTELS AND MOTELS, TO WARN GUESTS, RESIDENTS AND EMPLOYEES TO NOT MOVE
THE BED LOCATION TO A POSITION VIOLATING POINTS (1) AND (2) ABOVE OR SERIOUS INJURY AND/OR LOSS OF LIFE MAY OCCUR
DURING A FIRE EMERGENCY.
WARNING: A SMALL POSSIBILITY EXISTS THAT THE USE OF MULTIPLE STROBES WITHIN A PERSON'S FIELD OF VIEW, UNDER
CERTAIN CIRCUMSTANCES, MIGHT INDUCE A PHOTO-SENSITIVE RESPONSE IN PERSONS WITH EPILEPSY. STROBE REFLECTIONS IN A
GLASS OR MIRRORED SURFACE MIGHT ALSO INDUCE SUCH A RESPONSE. TO MINIMIZE THIS POSSIBLE HAZARD, WHEELOCK
STRONGLY RECOMMENDS THAT THE STROBES INSTALLED SHOULD NOT PRESENT A COMPOSITE FLASH RATE IN THE FIELD OF VIEW
WHICH EXCEEDS FIVE (5) Hz AT THE OPERATING VOLTAGE OF THE STROBES. WHEELOCK ALSO STRONGLY RECOMMENDS THAT THE
INTENSITY AND COMPOSITE FLASH RATE OF INSTALLED STROBES COMPLY WITH LEVELS ESTABLISHED BY APPLICABLE LAWS,
STANDARDS, REGULATIONS, CODES AND GUIDELINES.
WARNING: THE AMT STROBE APPLIANCE IS A "FIRE ALARM DEVICE - DO NOT PAINT."
WARNING: NFPA CODES REQUIRE SIGNALING APPLIANCES TO BE SUPERVISED. CHECK TO BE CERTAIN THAT UNSUPERVISED
SIGNALING APPLIANCES DO NOT VIOLATE ANY APPLICABLE CODES.
NOTE: NFPA 72/ANSI 117.1 Conform to ADDAAG Equivalent Facilitation Guidelines in using fewer, higher intensity strobes within the same protected area.
These appliances can produce a distinctive three pulse Temporal Pattern Fire Alarm Evacuation Signal (For total evacuation in accordance with NFPA 72.
CAUTION: Check the installation instructions of the manufacturers of other equipment used in the system for any guidelines or restrictions on wiring and/or
locating Notification Appliance Circuits (NAC) and notification appliances. Some system communication circuits and/or audio circuits, for example, may require
special precautions to assure immunity from electrical noise (e.g. audio crosstalk).
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital appliance, pursuant to Part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in residential installation. This equipment generates, uses and can radiate radio frequency energy
and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that
interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by
turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: 1) Reorient or relocate the
receiving antenna, 2) Increase the separation between the equipment and receiver, 3) Connect the equipment into an outlet on a circuit different from that to which the
receiver is connected, and 4) Consult the dealer or an experienced radio/TV technician for help.
The AMT Multitone Strobe products and these instructions are copyrighted by Wheelock and the AMT Multitone Strobe products contain proprietary, confidential and
trade secrets of Wheelock. No part of the AMT Multitone Strobe products and these instructions may be photocopied, printed or reproduced in any form or modified,
adapted, changed or enhanced, or converted to another programming language, or used to create updated, related or derivative works, without the prior written consent
of Wheelock. No part of the AMT Multitone Strobe products shall be decompiled, disassembled or reverse engineered.
ANY MATERIAL EXTRAPOLATED FROM THIS DOCUMENT OR FROM WHEELOCK MANUALS OR OTHER DOCUMENTS DESCRIBING THE
PRODUCT FOR USE IN PROMOTIONAL OR ADVERTISING CLAIMS, OR FOR ANY OTHER USE, INCLUDING DESCRIPTION OF THE
PRODUCT'S APPLICATION, OPERATION, INSTALLATION AND TESTING IS USED AT THE SOLE RISK OF THE USER AND WHEELOCK WILL
NOT HAVE ANY LIABILITY FOR SUCH USE.
IMPORTANT: READ SEPARATE "GENERAL INFORMATION" SHEET FOR INFORMATION ON THE PLACEMENT, LIMITATIONS,
INSTALLATION, FINAL CHECKOUT, AND PERIODIC TESTING OF NOTIFICATION APPLIANCES.
P84158 F
Sheet 7 of 8
Limited Warranty
Wheelock products must be used within their published specifications and must be PROPERLY specified, applied, installed, operated, maintained and operationally
tested in accordance with these instructions at the time of installation and at least twice a year or more often and in accordance with local, state and federal codes,
regulations and laws. Specification, application, installation, operation, maintenance and testing must be performed by qualified personnel for proper operation in
accordance with all of the latest National Fire Protection Association (NFPA), Underwriters' Laboratories (UL), Underwriters’ Laboratories of Canada (ULC), National
Electrical Code (NEC), Occupational Safety and Health Administration (OSHA), local, state, county, province, district, federal and other applicable building and fire
standards, guidelines, regulations, laws and codes including, but not limited to, all appendices and amendments and the requirements of the local authority having
jurisdiction (AHJ). Wheelock products when properly specified, applied, installed, operated, maintained and operationally tested as provided above are warranted
against mechanical and electrical defects for a period of three years from date of manufacture (as determined by date code). Correction of defects by repair or
replacement shall be at Wheelock's sole discretion and shall constitute fulfillment of all obligations under this warranty. THE FOREGOING LIMITED WARRANTY
SHALL IMMEDIATELY TERMINATE IN THE EVENT ANY PART NOT FURNISHED BY WHEELOCK IS INSTALLED IN THE PRODUCT. THE
FOREGOING LIMITED WARRANTY SPECIFICALLY EXCLUDES ANY SOFTWARE REQUIRED FOR THE OPERATION OF OR INCLUDED IN A
PRODUCT. WHEELOCK MAKES NO REPRESENTATION OR WARRANTY OF ANY OTHER KIND, EXPRESS, IMPLIED OR STATUTORY WHETHER AS
TO MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE OR ANY OTHER MATTER.
USERS ARE SOLELY RESPONSIBLE FOR DETERMINING WHETHER A PRODUCT IS SUITABLE FOR THE USER'S PURPOSES, OR WHETHER IT WILL
ACHIEVE THE USER'S INTENDED RESULTS. THERE IS NO WARRANTY AGAINST DAMAGE RESULTING FROM MISAPPLICATION, IMPROPER
SPECIFICATION, ABUSE, ACCIDENT OR OTHER OPERATING CONDITIONS BEYOND WHEELOCK'S CONTROL.
SOME WHEELOCK PRODUCTS CONTAIN SOFTWARE. WITH RESPECT TO THOSE PRODUCTS, WHEELOCK DOES NOT WARRANTY THAT THE
OPERATION OF THE SOFTWARE WILL BE UNINTERRUPTED OR ERROR-FREE OR THAT THE SOFTWARE WILL MEET ANY OTHER STANDARD OF
PERFORMANCE, OR THAT THE FUNCTIONS OR PERFORMANCE OF THE SOFTWARE WILL MEET THE USER'S REQUIREMENTS. WHEELOCK
SHALL NOT BE LIABLE FOR ANY DELAYS, BREAKDOWNS, INTERRUPTIONS, LOSS, DESTRUCTION, ALTERATION, OR OTHER PROBLEMS IN THE
USE OF A PRODUCT ARISING OUT OF OR CAUSED BY THE SOFTWARE.
THE LIABILITY OF WHEELOCK ARISING OUT OF THE SUPPLYING OF A PRODUCT, OR ITS USE, WHETHER ON WARRANTIES, NEGLIGENCE, OR
OTHERWISE, SHALL NOT IN ANY CASE EXCEED THE COST OF CORRECTING DEFECTS AS STATED IN THE LIMITED WARRANTY AND UPON
EXPIRATION OF THE WARRANTY PERIOD ALL SUCH LIABILITY SHALL TERMINATE. WHEELOCK IS NOT LIABLE FOR LABOR COSTS INCURRED
IN REMOVAL, REINSTALLATION OR REPAIR OF THE PRODUCT BY ANYONE OTHER THAN WHEELOCK OR FOR DAMAGE OF ANY TYPE
WHATSOEVER, INCLUDING BUT NOT LIMITED TO, LOSS OF PROFIT OR INCIDENTAL OR CONSEQUENTIAL DAMAGES. THE FOREGOING SHALL
CONSTITUTE THE SOLE REMEDY OF THE PURCHASER AND THE EXCLUSIVE LIABILITY OF WHEELOCK.
IN NO CASE WILL WHEELOCK'S LIABILITY EXCEED THE PURCHASE PRICE PAID FOR A PRODUCT.
Limitation of Liability
WHEELOCK'S LIABILITY ON ANY CLAIM OF ANY KIND, INCLUDING NEGLIGENCE AND BREACH OF WARRANTY, FOR ANY LOSS OR DAMAGE
RESULTING FROM, ARISING OUT OF, OR CONNECTED WITH THIS CONTRACT, OR FROM THE MANUFACTURE, SALE, DELIVERY, RESALE,
REPAIR OR USE OF ANY PRODUCT COVERED BY THIS ORDER SHALL BE LIMITED TO THE PRICE APPLICABLE TO THE PRODUCT OR PART
THEREOF WHICH GIVES RISE TO THE CLAIM. WHEELOCK'S LIABILITY ON ANY CLAIM OF ANY KIND SHALL CEASE IMMEDIATELY UPON THE
INSTALLATION IN THE PRODUCT OF ANY PART NOT FURNISHED BY WHEELOCK. IN NO EVENT SHALL WHEELOCK BE LIABLE FOR ANY
CLAIM OF ANY KIND UNLESS IT IS PROVEN THAT OUR PRODUCT WAS A DIRECT CAUSE OF SUCH CLAIM. FURTHER, IN NO EVENT, INCLUDING
IN THE CASE OF A CLAIM OF NEGLIGENCE, SHALL WHEELOCK BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES. SOME STATES
DO NOT ALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE PRECEDING LIMITATION MAY NOT
APPLY TO ALL PURCHASERS.
11/05
P84158 F
Sheet 8 of 8
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.