This publication contains the installation, operation and
maintenance instructions for standard units of the SQI
Square Centrifugal Inline Fans.
Carefully read this publication and any
supplemental documents prior to any
installation or maintenance procedure.
Loren Cook catalog SQI provides additional information
describing the equipment, fan performance, available
accessories, and specification data.
For additional safety information, refer to AMCA
publication 410-96, Safety Practices for Users and Installers of Industrial and Commercial Fans.
All of the publications listed above can be obtained from
Loren Cook Company by phoning (417)869-6474,
extension 166; by FAX at (417)832-9431; or by e-mail at
info@lorencook.com.
For information on special equipment, contact Loren
Cook Company Customer Service Department at
(417)869-6474.
Rotating Parts & Electrical Shock Hazard:
Disconnect electric power before working on unit.
Follow proper lockout / tagout procedures to ensure
the unit cannot be energized while being installed or
serviced.
A disconnect switch should be placed near the fan in
order that the power can be swiftly cut off, in case of
an emergency and in order that maintenance
personnel are provided complete control of the power
source.
Grounding is required. All field-installed wiring must
be completed by qualified personnel. All fieldinstalled wiring must comply with National Electric
Code (NFPA 70) and all applicable local codes.
Failure to follow these instructions could result in
death or serious injury.
Storage
If fan is stored for any length of time, prior to installation,
completely fill bearings with grease or moisture-inhibiting
oil. Refer to page 4. Store the fan in its original crate and
protect from dust, debris, and weather. To maintain good
working condition of a SQL when it’s stored outdoors, or on
a construction site follow the additional steps below.
• Cover the inlet and outlet, and belt tunnel opening to
prevent accumulation of dust and moisture in the
housing.
• Periodically rotate the wheel and operate dampers (if
supplied) to keep a coating of grease on all internal
bearing parts.
• Periodically inspect the unit to prevent damaging
conditions.
Installation
To prevent damage to the fan during shipping, motors 5
HP and larger, and extremely heavy motors (cast iron or
severe duty) are shipped loose and must be field mounted
by bolting the motor on the motor mounting plate in the
existing mounting slots.
Wiring Installation
NOTICE! All wiring should be in accordance
with local ordinances and the National Electrical
Code, NFPA 70. Ensure the power supply
(voltage, frequency, and current carrying
capacity of wires) is in accordance with the
motor nameplate. Refer to the Wiring Diagrams,
on page 3.
Direct drive - Wire the electrical box on the blower
housing.
Belt drive - The motor can be wired directly since the
motor is external to the fan.
Receiving and Inspection
Carefully inspect the fan and accessories for any
damage and shortage immediately upon receipt of the fan.
• Turn the wheel by hand to ensure it turns freely and
does not bind.
• Inspect dampers for free operation of all moving parts.
• Record on the Delivery Receipt any visible sign of
damage.
Handling
Lift the fan by the base or lifting eyes. NOTICE! Never
lift by the shaft, motor, or housing.
SQI-B
Motor Plate
Motor Plate
Adjustment Nut
Tolerance
Center Distance
Up thru 12”1/16”
12” up through 481/8”
Over 48”1/4”
Maximum
Gap
OFFSETANGULAROFFSET/ANGULAR
A
W
Motor Plate Adjustment
Wiring Installation (continued)
Leave enough slack in the wiring to allow for motor movement when adjusting belt tension. Some fractional motors
have to be removed in order to make the connection with
the terminal box at the end of the motor. To remove motor,
remove bolts securing motor base to power assembly. Do
not remove motor mounting bolts.
Belt and Pulley Installation
Belt tension is determined by the sound the belts make
when the fan is first started. Belts will produce a loud
squeal which dissipates after the fan is operating at full
capacity. If the belt tension is too tight or too loose, lost efficiency and possible damage can occur.
1/4 inch
1 foot
Figure 2
X
Y
Z
B
CENTER
DISTANCE
(CD)
GAP
GAP
Final Installation Steps
a. Ensure that all accessories are
installed.
b. Ensure that the blower is secured to
ductwork.
c. Inspect wheel-to-inlet clearance.
Ensure wheel does not rub against the
inlet.
d. Test the fan to ensure the rotation of
the wheel is the same as indicated by
the rotation label.
e. Inspect for correct amperage with
Figure 3
an ammeter and correct voltage with a voltmeter.
NOTICE! Do not allow the fan to run in the wrong
direction. This will overheat the motor and cause serious damage. For 3-phase motors, if the fan is running
in the wrong direction, check the control switch. It is
possible to interchange two leads at this location so
that the fan is operating in the correct direction.
Figure 1
Do not change the pulley pitch diameter to change ten-
sion. This will result in a different fan speed.
a. Loosen motor plate adjustment nuts on stud bolts and
move motor plate in order that the belts can easily slip into
the grooves on the pulleys. Never pry , roll, or force the belts
over the rim of the pulley.
b. Adjust the motor plate until proper tension is reached.
For proper tension, a deflection of approximately 1/4” per
foot of center distance should be obtained by firmly pressing the belt. Refer to Figure1.
c. Lock the motor plate adjustment nuts in place.
d. Ensure pulleys are properly aligned. Refer to Figure 2.
Pulley Alignment
Pulley alignment is adjusted by loosening the motor pulley
setscrew and by moving the motor pulley on the motor
shaft.
Figure 2 indicates where to measure the allowable gap for
the drive alignment tolerance. All contact points (indicated
by WXYZ) are to have a gap less than the tolerance shown
in the table. When the pulleys are not the same width, the
allowable gap must be adjusted by half of the difference in
width. Figure 3 illustrates using a carpenter’s square to
adjust the position of the motor pulley until the belt is parallel to the longer leg of the square.
Operation
Pre-Start Checks
a. Lock out all the primary and secondary power sources.
b. Inspect and tighten fasteners and setscrews, particularly fan mounting and bearing fasteners. Refer to Torque chart.
c. Inspect belt tension and pulley alignment.
d. Inspect motor wiring.
e. Ensure fan and ductwork are clean and free of debris.
f. Close and secure all access doors.
g. Restore power to the fan.
Start Up
Turn the fan on. In variable speed units, set the fan to its
lowest speed and inspect for the following:
• Direction of rotation.
• Excessive vibration.
• Unusual noise.
• Bearing noise.
• Improper belt alignment or tension (listen for squealing).
• Improper motor amperage or voltage.
NOTICE! If a problem is discovered, immediately shut
the fan off. Lock out all electrical power and check for
the cause of the trouble. See Troubleshooting.
Inspection
Inspection of the fan should be conducted at the first 30
minute, 8 hour and 24 hour intervals of satisfactory opera-
tion. During the inspections, stop the fan and inspect as per
the chart below.
2
Wiring Diagrams
Single Speed, Single Phase Motor
When ground is required, attach to ground A or B with no. 6 thread forming
screw. To reverse, interchange T-1 and T-4.
2 Speed, 2 Winding, Single Phase Motor
Ground A
L
T-5
J-10
Link A
Link B
Low Voltage
Ground B
Line
L
1
T-5
J-10
2
Ground B
When ground required, attach to ground A or B with No. 6 thread forming
screw. To reverse, interchange T-1 and T-4 leads.
Single Speed, Single Phase, Dual Voltage
Ground A
T-1
T-4
Ground B
When ground required, attach to ground A or B with No. 6 thread forming
screw. To reverse, interchange T-5 and J-10 leads.
High Speed
Low Speed
Typical Damper Motor Schematic
Fan
Motor
Transformer**
Damper
Motor*
Second
Damper
Motor
Transformer**
Ground A
Link A & B
L
1
Line
L
2
For 3 phase, damper motor voltage should be the
L3
same between L1 and L2.
L2
For single phase applica-
L1
tion, disregard L3.
*Damper motors may be
available in 115, 230 and
460 volt models. The
damper motor nameplate
voltage should be verified prior to connection.
**A transformer may be
provided in some installations to correct the
damper motor voltage to
the specified voltage.
L
Line
L
Wiring Diagrams
3 Phase, 9 Lead Motor
Y-Connection
Low Voltage
208/230 Volts
4
5
6
3
1
9
728
L2L
L
1
3
High Voltage
460 Volts
456
789
12
L
1
To reverse, interchange any 2 line leads.
2 Speed, 1 Winding, 3 Phase Motor
High Speed
1
Together
1
Motor
2
2
3
L
4
L
5
6
L
To reverse, interchange any 2 line leads. Motors require magnetic control.
2 Speed, 2 Winding, 3 Phase
To reverse: High Speed-interchange leads T11 and T12.
Low Speed-interchange leads T1 and T2. Both Speeds-interchange any 2
line leads.
SQI-D 70-90
WhiteLine
Black (High)
Blue (Medium)
Red (Low)
NOTE: Insulate Unused Leads Separately
FSC
SQI-D
FAN*
3 Phase, 9 Lead Motor
Delta-Connection
Low Voltage
208/230 Volts
8
7
4
6
2
1
3
L
L
1
L2L
3
2
1
2
Line
3
WHITE
9
5
3
L
3
Low Speed
Motor
High Voltage
460 Volts
789
456
12
L1L
1
2
3
4
5
6
*
*
*
3
L
3
2
L
1
L
2
Line
L
3
Open
Line
FSC
BLACK
*See SQI Wiring Diagram for correct lead.
3
Loading...
+ 5 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.