COOK CP User Manual

CA/CF/CP
Centrifugal Blowers
INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
This publication contains the installation, operation and maintenance instructions for standard units of the CA, CF, and CP Centrifugal Blowers.
• CA / CF SWSI • CA DWDI
• CA-4 SWSI • CA-4 DWDI
• CPFD • CPFB
• CAF-DW
• CPA / CPA-A / CPS / CPS-A / CPV
Carefully read this publication and any supplemental documents prior to any installation or maintenance procedure.
Loren Cook Company’s catalog CA/CF & CP provides additional information describing the equipment, fan performance, available accessories, and specification data.
For additional safety information, refer to AMCA publication 410-96, Safety Practices for Users and Installers of Industrial and Commercial Fans.
All of the publications listed above can be obtained from Loren Cook Company by phoning (417)869-6474, extension 166; by FAX at (417)832-9431; or by e-mail at info@lorencook.com.
For information on special equipment, contact Loren Cook Company Customer Service Department at (417)869-6474.

Handling

Lift the fan by the base or lifting eyes. NOTICE! Never lift
by the shaft, motor, or housing.

Storage

If the fan is stored for any length of time prior to installation, completely fill the bearings with grease or moisture-inhibiting oil (refer to Lubricants on page 6). Rotate the wheel several revolutions every three to five days to keep a coating of grease on all internal bearing parts.
Store the fan in its original crate and protect it from dust, debris and the weather.
To maintain good working condition of the fan when it is
stored outdoors, follow the additional instructions below.
• Coat the shaft with grease or a rust preventative compound.
• Wrap bearings for weather protection.
• Cover the inlet and outlet to prevent the accumulation of dirt and moisture in the housing.
• Periodically rotate the wheel and operate dampers (if supplied).
• Periodically inspect the unit to prevent damaging conditions.
Rotating Parts & Electrical Shock Hazard:
Disconnect electric power before working on unit. Follow proper lockout / tagout procedures to ensure
the unit cannot be energized while being installed or serviced.
A disconnect switch should be placed near the fan in order that the power can be swiftly cut off, in case of an emergency and in order that maintenance personnel are provided complete control of the power source.
Grounding is required. All field-installed wiring must be completed by qualified personnel. All field­installed wiring must comply with National Electric Code (NFPA 70) and all applicable local codes.
Failure to follow these instructions could result in death or serious injury.

Receiving and Inspection

Carefully inspect the fan and accessories for any damage
and shortage immediately upon receipt of the fan.
• Turn the wheel by hand to ensure it turns freely and does not bind.
• Inspect dampers (if supplied) for free operation of all moving parts.
• Record on the delivery receipt any visible sign of
damage.

Installation

Motor Installation
Most motors are shipped mounted on the fans with belts and drives installed. However, extremely heavy motors and drives are shipped separately . These motors and drives will require field installation.
CA SWSI
The attachment of roof mounted fans to the roof curb as well as the attachment of roof curbs to the building structure must exceed the structural requirements based on the environmental loading derived from the applicable building code for the site. The local code official may require variations from the recognized code based on local data. The licensed engineer of record will be responsible for prescribing the correct attachment based on construction materials, code requirements and environmental effects specific to the installation.
Failure to follow these instructions could result in death or serious injury.

Foundation

This fan requires a strong, level foundation of reinforced poured concrete. A correctly designed concrete foundation provides the best means for mounting floor units. The foundation’s size is determined by fan size and arrangement, motor size and position, and the specific location of the installation.
Use the following guidelines to calculate foundation size:
• The overall dimensions of the foundation should extend at least 6 inches beyond the outline of the fan and its motor.
• The weight of the foundation should be 2 to 3 times the weight of the unit and its motor.

Isolation

NOTICE! Although a certain amount of vibration is
inherent in operating centrifugal fans, extreme vibration is a serious problem that may cause structural and mechanical failure.
Isolation Base: To prevent vibration and noise from being transferred to the building isolators are recommended. Arrangement 1, 2, & 3 (CA or CF) fans require an isolation base to effectively isolate the fan system which includes the fan, base, motor, drive, guards, etc. Bases must have sufficient rigidity to resist belt pull and prevent drive distortion which can lead to excessive belt and bearing wear; its perimeter should contain all base angles and rotating parts. Arrangement 9 or 10 fans (CA, CF, and CP) above size 270 require isolation rails. Please consult factory for isolation of arrangement 9 fans due to the potential of uneven loading caused by the motors and drives. Isolators should be located between the fan system and the support structure.
Ceiling Mounted Isolators: Some applications require fan systems designed for floor mounting to be suspended from ceiling supports. In such cases, all CA, CF, or CP fans of all arrangements should be installed on either rails or bases in the classical orientation. Typically, these systems are hung from the corners by rods, which include isolation hangers of either spring or rubber-in-shear design. NOTICE! Under no
circumstances is the fan to be inverted and hung by its base angles.
Ceiling Mounted Spring Isolator
Figure 1 - Ceiling Mount Isolators
Rubber-In-Shear Ceiling Isolators
Floor Mounted Spring Isolators
1. Mount fan and motor on isolation base (if supplied).
2. Elevate fan (or isolation base) to operating height and insert blocks to hold in position.
3. Position isolators under the fan and vertically align by inserting leveling bolt through mounting holes in the fan or the base. The isolator must be installed on a level surface.
4. Adjust the isolators by turning the leveling nut counter clockwise several turns at a time alternately on each isolator until the fan weight is transferred onto the isolators and the fan raises uniformly off the blocks. Then remove the blocks.
5. Turn lock nut onto leveling bolt and secure firmly in place against the top of the mounting flange or frame.
6. Secure isolators to mounting surface.
Spring Isolator
Figure 2 -Floor Mount Isolators
Rubber-In-Shear Isolator
Floor Mounted Rubber-In-Shear (RIS) Isolators
1. Mount fan and motor on an isolation base (if supplied).
2. Elevate fan to provide room to insert isolators between the base and foundation and block in position.
3. Position isolators under fan and secure bolts.
4. Remove blocks and allow fan to rest on floor. Isolators must be installed on a level surface (leveling should not be required).
5. Secure isolators to mounting surface.
2
Duct Installation
Efficient fan performance relies on the proper installation of inlet and discharge ducts. Be sure your fan conforms to the following guidelines.
Non-Ducted Inlet Clearance: If your fan has an open inlet (no duct work), the fan must be placed 1 fan wheel diameter away from walls and bulkheads.
Non-ducted Inlet
Clearance
MIN 1 DIA
The installation diagram below has a solid curb cap duct adapter placed over the top of the curb. The welded grease duct with recommended transition is either welded or sealed with UL recognized fire caulk to both the curb cap duct adapter and the bottom of the fan. A minimum of two separate outlines of caulk is recommended at the outer portion of the curb cap duct adapter.
Free Discharge: Avoid a free discharge into the plenum. This will result in lost efficiency because it doesn’t allow for a static regain.
Correct
Free Discharge
Incorrect
Inlet Duct Turns: For ducted inlets, allow at least 3 fan wheel diameters between duct turns or elbows and the fan inlet.
MIN 3
Correct
Incorrect
Inlet Duct Turns
DIA
Discharge Duct Turns: Where possible, allow 3 duct diame­ters between duct turns or elbows and the fan outlet. Refer to figure above.
MIN 3
DIA
Correct
Discharge Duct Turns
Incorrect

CP with Optional Curb Cap & Inlet Box

UL 762 / NFPA96 and local codes may dictate additional or modifications to this installation.
Wheel-to-Inlet Clearance
The correct wheel-to-inlet clearance is critical to proper fan performance. This clearance should be verified before initial start-up since rough handling during shipment could cause a shift in fan components. Refer to wheel/inlet draw­ing for correct overlap.
Adjust the overlap by loosening the wheel hub and mov­ing the wheel along the shaft to obtain the correct value.
A uniform radial gap (space between the edge of the cone and the edge of the inlet) is obtained by loosening the inlet cone bolts and repositioning the inlet cone.
CA, CF, & CP
Size Overlap
60 - 165 3/16” 180 - 245 1/4” 270 - 300 5/16” 330 - 365 3/8”
402 7/16” 445 - 490 1/2” 540 - 730 13/16”
CAF-DW
Size Overlap
120
135 - 165
180 195 210 225 245
270 - 445
490 17/32” 540 - 600 660 - 730
1/8”
5/32”
1/4”
5/32”
1/4” 5/32” 9/32”
1/4”
27/32” 25/32”
3
1 foot
1/4 inch
Wiring Installation
NOTICE! All wiring should be in accordance with local ordinances and the National Electrical Code, NFPA 70. Ensure the power supply (voltage, frequency, and current carrying capacity of wires) is in accordance with the motor nameplate.
(See page 5 for diagram)
Leave enough slack in the wiring to allow for motor movement when adjusting belt tension. Some fractional motors have to be removed in order to make the connection with the terminal box at the end of the motor. To remove motor, remove bolts securing motor base to power assembly. Do not remove motor mounting bolts.
Units with Arrangement 10 have a hole provided at the base of the bearing pedestal to accommodate wiring.
Follow the wiring diagram in the disconnect switch and the wiring diagram provided with the motor. Correctly label the circuit on the main power box and always identify a closed switch to promote safety (i.e., red tape over a closed switch).
tension. This will result in a different fan speed than desired.
1. Loosen motor plate adjustment nuts on L-bolts and move motor plate in order that the belts can easily slip into the grooves on the pulleys. Never pry , roll, or force the belts over the rim of the pulley.
2. Slide the motor plate back until proper tension is reached. For proper tension a deflection of approximately 1/4” per foot of center distance should be obtained by firmly pressing the belt. Refer to Figure 3.
3. Lock the motor plate adjustment nuts in place.
4. Ensure pulleys are properly aligned. Refer to Figure 4.
Tolerance
Center
Distance
Up thru 12” 1/16”
12” up through 48 1/8”
Over 48” 1/4”
Maximum
Gap
OFFSET ANGULAR OFFSET/ANGULAR
A
W
X Y
CENTER
DISTANCE
(CD)
Airfoil
Backward Inclined
Forward Curved

Wheel Rotation

Test the fan to ensure the rotation of the wheel is the same as indicated by the arrow marked Rotation.
For 115 and 230 Single Phase Motors: Fan wheel rotation is set correctly at the factory. Changing the rotation of this type of motor should only be attempted by a qualified electrician.
For 208, 230, and 460, 3 Phase Motors: These motors are electrically reversible by switching two of the supply leads. For this reason, the rotation of the fan cannot be restricted to one direction at the factory. See Wiring Diagrams above for specific information on reversing wheel direction.
NOTICE! Do not allow the fan to run in the wrong direction. This will overheat the motor and cause serious damage. For 3-phase motors, if the fan is running in the wrong direction, check the control switch. It is possible to interchange two leads at this location so that the fan is operating in the correct direction.
Belt and Pulley Installation
Belt tension is determined by the sound the belts make when the fan is first started. Belts will produce a loud squeal which dissipates after the fan is operating at full capacity. If the belt tension is too tight or too loose, lost efficiency and possible damage can occur.
Do not change the pulley pitch diameter to change
Figure 3
Figure 4
Z
B
GAP
GAP
Pulley Alignment
Pulley alignment is adjusted by loosening the motor pulley setscrew and by moving the motor pulley on the motor shaft.
Figure 4 indicates where to measure the allowable gap for the drive alignment tolerance. All contact points (indicated by WXYZ) are to have a gap less than the tolerance shown in the table. When the pulleys are not the
Figure 5
same width, the allowable gap must be adjusted by half of the difference in width (As shown in A & B of Figure 4). Figure 5 illustrates using a carpenter’s square to adjust the position of the motor pulley until the belt is parallel to the longer leg of the square.
Final Installation Steps
1. Inspect fasteners and setscrews, particularly fan mounting and bearing fasteners, and tighten according to the recommended torque shown in the following table.
2. Inspect for correct voltage with voltmeter.
3. Ensure all accessories are installed.
Recommended T orque for Setscrews & Hold Down Bolts
Setscrews Hold Down Bolts
Key
Size
No.10 3/32” 28 33 3/8”-16 240
1/4” 1/8” 66 80 1/2”-13 600
5/16” 5/32” 126 156 5/8”-11 1200
3/8” 3/16” 228 275 3/4”-10 2100
7/16” 7/32” 348 384 7/8”- 9 2040
1/2” 1/4” 504 600 1”- 8 3000 5/8” 5/16” 1104 1200 1-1/8” - 7 4200 3/4” 3/8” 1440 1800 1-1/4” - 7 6000
4
Hex
Across
Flats
Recommended
Torque
(inch/lbs)
Min. Max.
Size
Wrench Torque
(inch/lbs)

Operation

Pre-Start Checks
1. Lock out all the primary and secondary power sources.
2. Ensure fasteners and setscrews, particularly those used for mounting the fan, are tightened.
3. Inspect belt tension and pulley alignment.
4. Inspect motor wiring.
5. Ensure belt touches only the pulleys.
6. Ensure fan and ductwork are clean and free of debris.
7. Inspect wheel-to-inlet clearance. The correct wheel­to-inlet clearance is critical to proper fan performance.
8. Close and secure all access doors.
9. Restore power to the fan.
Start Up
Turn the fan on. In variable speed units, set the fan to its
lowest speed and inspect for the following:
• Direction of rotation.
• Excessive vibration.
• Unusual noise.
• Bearing noise.
• Improper belt alignment or tension (listen for squealing).
• Improper motor amperage or voltage.
NOTICE! If a problem is discovered, immediately shut the fan off. Lock out all electrical power and check for the cause of the trouble. See Troubleshooting.

Wiring Diagrams

Single Speed, Single Phase Motor
Ground A
L
T-1
T-4
Ground B
When ground is required, attach to ground A or B with no. 6 thread forming screw. To reverse, interchange T-1 and T-4.
2 Speed, 2 Winding, Single Phase Motor
Ground A
T-1 T-4
Ground B
When ground required, attach to ground A or B with No. 6 thread forming screw. To reverse, interchange T-1 and T-4 leads.
Single Speed, Single Phase, Dual Voltage
Ground A
L
Line
L
1
2
T-5
J-10
Ground B
When ground required, attach to ground A or B with No. 6 thread forming screw. To reverse, interchange T-5 and J-10 leads.
Link A Link B
Low Voltage
Typical Damper Motor Schematic
Fan
Motor
Transformer**
Line L
T-5
J-10
Ground B
1
2
High Speed
L
1
L
2
Low Speed
Ground A
L3 L2 L1
Transformer**
Line
L
Line
L
1
2
Link A & B
For 3 phase, damper motor voltage should be the same between L1 and L2. For single phase application, disregard L3. *Damper motors may be available in 115, 230 and 460 volt models. The damper motor nameplate voltage should be verified prior to connection. ** A transformer may be pro­vided in some installations to correct the damper motor voltage to the specified voltage.
Wiring Diagrams
3 Phase, 9 Lead Motor Y-Connection
Low Voltage
208/230 Volts
4
5
6
1
728
To reverse, interchange any 2 line leads.
3 9
L2L
L
3
1
High Voltage
460 Volts
456
789
12
L2L
L
1
2 Speed, 1 Winding, 3 Phase Motor
High Speed
1
Together
2
Motor
To reverse, interchange any 2 line leads. Motors require magnetic control.
3
L
4
1
L
5
2
6
Line
L
3
2 Speed, 2 Winding, 3 Phase
To reverse: High Speed-interchange leads T11 and T12. Low Speed-interchange leads T1 and T2. Both Speeds-interchange any 2 line leads.
3 Phase, 9 Lead Motor Delta-Connection
Low Voltage
208/230 Volts
8
7
4
6
2
1
3
L
1
3
L
2
Low Speed
Motor
L
High Voltage
9 5
3
3
1 2 3
4 5
6
460 Volts
789 456
12
L
1
L
1
L
2
Line
L
3
Open
3
L
L
3
2
Damper
Motor*
Second Damper
Motor
5
Loading...
+ 11 hidden pages