Contura Surround C 11, Surround C 21 Installation Instruction

Installation
instruction
Surround C 11
Surround C 21
www.contura.eu
38
CERTIFICATE
PRODUCT
Product type Stove lit with solid biofuels Type designation Contura 11 Manufacturing number See rating plate on the stove Intended area of use Heating of rooms in residential buildings Fuel Wood
MANUFACTURER
Name NIBE AB / Contura Address Box 134, Skulptörvägen 10 SE-285 23 Markaryd, Sweden
CHECKS
According to AVCP System 3 European standard EN 13240:2001 / A2:2004 Test institute Rein-Ruhr Feuerstätten Prüfstelle, NB 1625, has checked declared performance and issued test report no. RRF-40 09 2080
PERFORMANCE DECLARATION
No. C11-CPR-130614-SE-1
DECLARED PERFORMANCE
Essential characteristics Performance Harmonised technical
specification
Reaction to fire A1 WT
Minimum distance to combustible material No minimum distance to rear
400 mm to side Other safety distances according to the installation instructions
Risk of falling embers Approved
Emissions from combustion CO 0.09%
NOx 109 mg/m
3
OGC 50 mg/m3 PM 29 mg/m
3
Surface temperatures Approved
Cleaning options Approved
Mechanical durability Approved
Emissions of hazardous substances Approved
Nominal output 9 kW
Efficiency 81%
Flue gas temperature in connector at nominal output
290°C
EN 13240:2001 / A2:2004
The undersigned is responsible for the manufacture and conformity with the declared performance.
Niklas Gunnarsson,
Business area manager NIBE STOVES
Markaryd, 1st July 2013
39
CERTIFICATE
PRODUCT
Product type Stove lit with solid biofuels Type designation Contura 21 Manufacturing number See rating plate on the stove Intended area of use Heating of rooms in residential buildings Fuel Wood
MANUFACTURER
Name NIBE AB / Contura Address Box 134, Skulptörvägen 10 SE-285 23 Markaryd, Sweden
CHECKS
According to AVCP System 3 European standard EN 13240:2001 / A2:2004 Test institute Rein-Ruhr Feuerstätten Prüfstelle, NB 1625, has checked declared performance and issued test report no. RRF-40 09 1081
PERFORMANCE DECLARATION
No. C21-CPR-130614-SE-1
DECLARED PERFORMANCE
Essential characteristics Performance Harmonised technical
specification
Reaction to fire A1 WT
Minimum distance to combustible material No minimum distance to rear
400 mm to side Other safety distances according to the installation instructions
Risk of falling embers Approved
Emissions from combustion CO 0.07%
NOx 99 mg/m
3
OGC 42 mg/m3 PM 29 mg/m
3
Surface temperatures Approved
Cleaning options Approved
Mechanical durability Approved
Emissions of hazardous substances Approved
Nominal output 10 kW
Efficiency 81%
Flue gas temperature in connector at nominal output
330°C
EN 13240:2001 / A2:2004
The undersigned is responsible for the manufacture and conformity with the declared performance.
Niklas Gunnarsson,
Business area manager NIBE STOVES
Markaryd, 1st July 2013
40
A warm welcome to Contura
A warm welcome to the Contura family. We hope you will
get a great deal of pleasure from your new stove. As a new
owner of a Contura stove you have secured a product
with timeless design and long service life. Contura also
has combustion that is both environmentally friendly and
efficient for the best heat production.
Read through these installation instructions carefully before
installation. Read how to best light your stove in the lighting
instructions.
NOTE!
Report the installation of a stove to your local authority
The owner of the house is personally responsible for ensuring compliance with the mandatory safet y requirements and must have the installation approved by a qualified inspector. Your local chimney sweep must also be informed about the installation as this will affect the routines for regular chimney-sweeping services.
WARNING!
The stove becomes very hot
During operation, certain sur faces of the stove become very hot and can cause burn injur y if touched. Be aware of the strong heat radiated through the hatch glass. Placing flammable material closer than the safe distance indicated may cause a fire. Pyre lighting can cause quick gas ignition with the risk of damage to property and personal injury.
CONTENTS
Table of contents
Technical details 41
Supply of combustion air 42
Installation distance to walls and ceiling 43
Installation alternatives 45
Installing the surround 47
Installing the height extension 58
Flammable wall and accompanying protective screen
Installing the height extension 62
Non-flammable wall and chimney connection straight back or straight up
Installing the height extension 65
Non-flammable wall and connection with angle back
Installing the woodbox 69
41
Technical details
C11 C21 Power output 6-12 kW 6-12 kW Nominal output 9 kW 10 kW Efficiency 81% 81%
Model C11C C11 A/S Weight (kg) 470 450 Width (mm) 1050 1050 Depth (mm) 620 620 Height (mm) 1620 1620
Model C11C extended C11A/S extended Weight (kg) 575 550 Height (mm) 2305 2305
Model C21C C21A/S Weight (kg) 495 480 Width (mm) 950 950 Depth (mm) 620 620
Building application
Before installing a stove or erec ting a chimney it is necessary for you to make a building application permission to your local authority. Ask your local authority for advice regarding building regulations and the application.
Structural support
If the hearth is to be positioned on a wooden joist, a structural engineer should evaluate the load capacity of the floor. When the gross weight exceeds 400 kg, reinforcement of the wooden joists is usually necessary.
Hearth plate
If the floor under the hearth is flammable, it must be protected by a non-flammable material which covers at least 300 mm to the front and 100 mm on each side. The hear th plate can consist of natural stone, concrete or 0.7 mm thick metal. A painted metal or glass hear th plate is available as an accessory.
Chimney
The insert requires a draft in the chimney of at least –12 Pa. The draft is affected both by the length and area of the chimney, and by how well sealed it is.
Once the lighting phase is complete, this inser t must be operated with the door closed because of the risk of smoke entering the room. Always open the door carefully and slowly to prevent blow back because of the changing pressure in the stove.
• Carefully check that the chimney is sealed and that there is no
leakage around soot hatches and flue connections.
Note that a flue with sharp bends and horizontal routing reduces the draught in the chimney. Maximum horizontal flue is 1 m, on the condition that the vertical flue length is at least 5 m. It must be possible to sweep the full length of the flue and the soot hatches must be easily accessible.
Wall behind
If your Contura 11 / 21 is to be installed against a flammable wall the
wall must be protected by a firewall or by the integrated protective screen that is sold an as accessory for these models. A firewall must be at least the same width and height as the surround. More information about the requirements made of the fire wall material is available in the separate instructions for the insert. Remember that non-flammable walls can also require protection if they are bearing walls or have flammable material behind them.
Concrete
The surface of concrete, by it s nature, is not free of defec ts. In order to achieve a neat end result some of the concrete may need to be filled and sanded. If greater damage occurs to the concrete it can be repaired by mixing water with the cement powder supplied and filling the holes.
Because of the settling in buildings and the fact that concrete shrinks, cracks may occur in the grouting between the block s in the first few months. Scrape out the grout and brush the surfaces clean. Fill with new grout and paint over when dry.
Height (mm) 1755 1755
Model C21C extended C21 A/S extended Weight (kg) 585 560 Height (mm) 2305 2305
Connector diameter Ø200 mm ext.
Tested in accordance with: European standard EN-13240 DIN plus Bauar t 1 Art. 15a B-VG Test report no.
C11: RRF 40 09 2080 C21: RRF 40 09 2081
General
This manual contains instructions about how the Contura 11 and 21
must be constructed and installed. More information about the insert is available in the separate installation instructions. To ensure the function and safety of the hear th, we recommend that installation is carried
out by an authorised technician. Our Contura dealers can recommend
suitable technicians, information about our dealers can be found at www. contura.eu
Instructions for lighting are also supplied with the insert. Read them carefully and keep them safe for future use.
The hear th is type approved in accordance with EN 13240 and must be
connected to a chimney dimensioned for a flue temperature of 350°C, the external connec tion diameter is Ø200 mm. Supply of combustion air
from the outside must be arranged, see page 42.
Woodbox
135 610 620 465
Woodbox
110 465 620 465
FACT S
42
Knockout
To insert the combustion air hose through the base plate, tap out the knockout from the concrete using a hammer, remember to protect the floor.
HK
HK
HK
HK
Supply of combustion air
Combustion air can be provided directly via a duct from outside, or
indirectly via a vent in the outer wall of the room where the stove is to be placed. The amount of combustion air used for combustion is
approximately 30 m³/h (applies with closed hatch),
Some installation alternatives are shown to the right. The air duct
connection on the stove has an ex ternal diameter of Ø100 mm.
In hot areas the duct should be insulated with 30 mm mineral wool covered with a moisture inhibitor (aluminium tape). It is impor tant that the lead-in between the pipe and the wall (or floor) is sealed using jointing compound.
A 1 m length of condensation insulated ducting for combustion air is available as an accessory.
268
82
Air inlet Ø100
243
105
Air inlet Ø100
SUPPLY AIR/ACCESSORY
43
Installation distance to walls and ceiling
1620
Min 2380
2305
475 450
1050
Combustible roof
265
120
1375
(1210)
1170
620
1880 ±60
Utv. Ø 200
400*
265
925
*If the wood compartment is to be placed between the surround and the wall at least 4 65 / 610 mm is required.
C11
The dimension diagrams only show the minimum permit ted installation distances for the insert. When connecting to a steel flue, also note the safety distance requirements of the flue. The safet y distance between an
uninsulated flue and a combustible part of the building should be at least 300 mm. The minimum distance to combustible par ts of the building or interior decoration in front of the insert must be at least 1.5 m.
Important!
INSTALLATION DISTANCES
44
Installation distance to walls and ceiling
*If the wood compartment is to be placed between the surround and the wall at least 4 65 / 610 mm is required.
C21
1755
2305
Min 2380
475 670
950
Combustible roof
265
120
1595
1965 ±20
(1430)
620
1390
Utv. Ø 200
400*
265
875
The dimension diagrams only show the minimum permit ted installation distances for the insert. When connecting to a steel flue, also note the safety distance requirements of the flue. The safet y distance between an
uninsulated flue and a combustible part of the building should be at least 300 mm. The minimum distance to combustible par ts of the building or interior decoration in front of the insert must be at least 1.5 m.
Important!
INSTALLATION DISTANCES
45
Selection of chimney connection and material in the wall behind mean that different requirements are made of installation. Note that a non-flammable wall or firewall must meet the requirement s stated on page 41. In other cases the accompanying protective screen must be used.
Installation alternatives
Non-flammable wall / Firewall
If the wall behind is non-flammable or protected by a firewall the surround can be installed directly against it. The small, 100x15 mm, air intakes in the protective screen on the surround sides can be filled if so desired. Top and rear connection can be made without any extra insulation or screening of connection pipes.
Protective screen
When the surround is installed together with the integrated protective screen it is important that the airflow is not blocked. For top connection, the gap between the top of the surround and the chimney insulation must be covered by a cuff to shield the radiant heat from the start pipe. It is also possible to connect to the rear through the protec tive screen, on the condition that a fully insulated chimney is used and the necessary safety distances observed. Ensure that there is a seal between the chimney and the protective screen.
Standard surround
CHIMNEY
46
Non-flammable wall / Firewall
When the height ex tension section is installed in the integrated protective screen, the air outlet at the top of the surround nearest to the wall must be sealed and the whole top sur face insulated. It is also possible to connect the chimney with a backward angle through the height extension section that requires a seal above the angle.
Protective screen
When the height ex tension section is installed the protective screen must be extended with a heat deflec tor through the height extension section. Ensure that the heat deflector is also ventilated. The top of the surround is also insulated using the insulation sheet provided.
Raised surround
CHIMNEY
47
Installation instructions surround C11, C21
Position the base plate against the wall. Ensure that it is level, add steel shims to the thickest sections of the base plate if possible. If the accompanying protective screen is to be installed, install it now. See the separate instruc tions.
Installation of the surround is the same for Contura 11 respec tively 21. Contura 11 is illustrated.
The ty pe plate must be positioned under the bottom insulation of the ash-pan.
ASSEMBLY
48
Lift the inser t on to the base plate and adjust the feet so that the distance from the floor to the underside of the shelf is 469 mm.
Check that it is straight and stable.
430 mm
40 mm
If the insert is to be rear connected, connect it now.
ASSEMBLY
49
Loosen the screws holding the side panels and remove them. Use the same screws and screw holes
to instead screw the hatch frame into place. Check
that the bottom corners line up with the shelf.
Hatch frame
Shelf
ASSEMBLY
50
Install the heat deflectors on the sides of the insert. Use the six installation screws supplied in the screw bag, and the screws that are already in the upper corner of the insert.
Apply a bead of silicone on the base plate and then lift in the lower section sides.
ASSEMBLY
51
90°
Control measurements
When both the sides are in position the safety rail is hung from the side washers to prevent them falling out to the sides.
Check measure that the distance between the
sides is the same at the front edge as at the rear edge and check that the sides are straight. Draw a horizontal check line on the wall to simplif y fur ther installation. Also check that the front edge of the hatch surround aligns with the inner edge of the concrete edges.
Applies to C 11C and C 21C (Concrete)
Applies to C 11A, C 11S, C 21A, C21S (Sheet metal)
ca 33 mm
80 mm
80 mm
ASSEMBLY
52
The panel variants’ front are adjusted for height using two adjustment screws
In the event of removal and height adjustment, use the following hook and pull out the lower door.
ASSEMBLY
53
Continue with the second section’s sides and
bond them with silicone.
3 mm
3 mm
3 mm
Check that the second section is straight and
that there is an even gap of approximately 3 mm between the frame and the concrete. If necessary, remove the lower front and adjust the insert.
ASSEMBLY
54
Apply a bead of silicone on the upper edge of the second section and then lift in the third section sides. Support the first side using a piece of tape so that it does not fall while the other side is installed.
Control measurements
Control measurements
Hang the safet y rail between the third section sides and
ensure that they are straight. Check that the width is the
same as section 1 at the front and rear edges.
ASSEMBLY
55
Apply silicone beads along the front edge of the sides and bond the upper front.
When top connecting through the top sheet of concrete the knock out in the top disc must be knocked out with a hammer. Secure the top with a few blobs of silicone and press it forward so that it is tight to the front panel.
Bond the lower front with silicone. Use the supplied installation angle to keep the front panel in position while the silicone cures.
ASSEMBLY
56
10
10
VANADIUM
No. 7
CHROME
On aluminium and steel fronts there are adjustment screws that can be used to adjust the front panel by height. When the front panel is set the outer Torx screws are screwed until they support against the concrete. The top rests on the turned down angles at the rear edge, these can be adjusted to get the top to the level of the concrete.
When installing the height extension section:
• with an integrated protective screen, go to page 58.
• in combination with a non-flammable wall and
chimney connection straight backwards, go to page 62.
• in combination with a non-flammable wall and
chimney connection angled backwards through the height ex tension section, go to page 65.
For installations without height extensions, top connection to stainless steel flues is now possible; follow the chimney manufacturer ’s instructions. Then continue on page 57 with joining and painting.
Final inspection of the installation
Before the stove is used, it must be inspected by an authorised chimney sweep. Read the “Instructions for
Lighting the CI 10 / CI 20 series” before lighting the fire for the first time.
ASSEMBLY
57
The gap between the concrete and the wall behind can be grouted if so desired. It is important that the air inlet, 100x15 mm, at the bottom of the section two is not blocked if the integrated protective screen is installed. If the surround is installed against a normal firewall the air intake can be blocked if so desired.
When the paint is dr y the grilles can be installed. The top grilles* are placed in position on the upper side, and the lower grille pins are installed using the springs and lugs supplied. * (not used when installing the height extension section).
Even off the edges between the concrete blocks by applying a little grout in the joint s and then using the corner of a filling knife to scrape out the excess and retain the marked edges.
Fill and sand small scratches and pores in the concrete. As soon as the silicone, grout and any repairs to the concrete are dry the surround can be painted with a silicate paint.
ASSEMBLY
58
Install the protective screen according to the separate instruction and the surround at ordinar y height according to page 47-56. Then apply silicone to the top of the surround and lift up the concrete sides of the height extension section. Support the first side so that it does not fall while the other side is installed.
Hang the safet y rail between the sides and ensure
that they are straight. Check that the width is the
same as section 1 at the front and rear edges.
Note the different installation methods of the height extension section. When using a protective screen the airflow must not be restricted at any point.
Installation height extension sections C11, C21
In combination with flammable wall and accompanying protec tive screen
!
ASSEMBLY
59
Install the right half of the heat deflec tor by inserting sideways and hooking the tabs around the concrete. Note that the heat deflector at the bottom edge must be positioned in front of the protective screen’s heat deflector.
Install the lef t half of the heat deflector in the same way, and screw the two halves together.
ASSEMBLY
60
For top connection
Check that the measurement between the top and the
chimney mantle is 25-30 mm. Then position the small insulation plate over the chimney hole in the top and connect the chimney. The chimney must press the insulation together approx 5 mm so that it is tight, but the weight must be on the insert and not the top panel. If the start pipe has a diameter greater than 150 mm the hole in the insulation must be cut out to fit.
25 mm
• The joint between the top and the chimney mantel must be
tight to prevent convec tion air from the surround leaking out at the change height.
• The weight of the chimney must be on the insert, not the
surrounding.
• If the chimney is designed in another way the seal must be
adapted to it.
Cut the large sheet of insulation so that it fits
around the chimney mantle and position it so that it covers the whole of the top of the surround.
Press in the rectangular insulation pieces at the rear edge and seal carefully to prevent convection air leaking out at the height extension section.
!
TOP CONNECTION
61
The sweeping hole in the concrete front is plugged using the concrete plug. Bond it into place using silicone and fill it before painting.
To avoid gaps in the panel lines of the front area, the height ex tension panel must be hung first without silicone. Adjust the components so that the joints between them look good, use shims where necessar y.
Apply silicone along the front edge of the sides and bond the front in position. If necessary, use the adjustment screws to adjust the height of the panel variants.
The surround can now be joined and painted according to page 57, after which the grilles can be put in place.
ASSEMBLY
Final inspection of the installation
Before the stove is used, it must be inspected by an authorised chimney sweep. Read the “Instructions for
Lighting the CI 10 / CI 20 series” before lighting the fire for the first time.
62
Install the surround at ordinary height according to page 47-56 in the instructions. Block the air outlet at the rear edge of the top panel using the seal plate that is bonded into position using silicone.
Then apply silicone to the top of the surround and lift up the concrete sides of the height extension section. Support the first side so that it does not fall while the other side is installed.
Note the different installation methods of the height extension section. When the protective screen provided is not used the air outlet at the rear edge of the top panel must be plugged.
Installation height extension sections C11, C21
In combination with non-flammable wall and chimney connection straight back or straight up
Hang the safet y rail between the sides and ensure
that they are straight. Check that the width is the
same as section 1 at the front and rear edges.
!
ASSEMBLY
63
Press in the rectangular insulation pieces at the rear edge and seal carefully to prevent convection air leaking out at the height extension section.
Cut the large sheet of insulation so that it fits around the chimney
mantle and position it so that it covers the whole of the top of the surround.
For top connection
Check that the measurement between the top and the
chimney mantle is 25-30 mm. Then position the small insulation plate over the chimney hole in the top and connect the chimney. The chimney must press the insulation together approx 5 mm so that it is tight, but the weight must be on the insert and not the top panel. If the start pipe has a diameter greater than 150 mm the hole in the insulation must be cut out to fit.
25 mm
• The joint between the top and the chimney mantel must be
tight to prevent convec tion air from the surround leaking out at the change height.
• The weight of the chimney must be on the insert, not the
surrounding.
• If the chimney is designed in another way the seal must be
adapted to it.
!
TOP CONNECTION
64
Apply silicone along the front edge of the sides and bond the front in position. If necessar y, use the adjustment screws to adjust the height of the panel variants.
To avoid gaps in the panel lines of the front area, the height extension panel must be hung first without silicone. Adjust the components so that the joints between them look good, use shims where necessary.
The sweeping hole in the concrete front is plugged using the concrete plug. Bond it into place using silicone and fill it before painting.
The surround can now be joined and painted according to page 57, after which the grilles can be put in place.
Final inspection of the installation
Before the stove is used, it must be inspected by an authorised chimney sweep. Read the “Instructions for
Lighting the CI 10 / CI 20 series” before lighting the fire for the first time.
ASSEMBLY
65
Installation height extension sections C11, C21
Note the different installation methods of the height extension section. When the protective firewall provided is not used the air outlet at the rear edge of the top panel must be plugged.
In combination with non-flammable wall and chimney connection angled back through the height extension section.
Install the surround at ordinary height according to page 47-56. Block the air outlet at the rear edge of the top panel using the seal plate that is bonded into position using silicone.
Apply silicone to the top of the surround and lif t up the concrete sides of the height ex tension section. Support the first side so that it does not fall while the other side is installed.
Hang the safet y rail between the sides and ensure
that they are straight. Check that the width is the
same as section 1 at the front and rear edges.
!
Connect the insert upwards and backwards
within the given heights.
ASSEMBLY
66
Insulate the rear edge of the top surface using one of the two smaller insulation pieces.
Cut the large sheet of insulation so that it fits around
the chimney flue and position it so that it covers the whole of the top sur face.
Place the left sealing plate so that it rests on the washer at the rear edge, and the lock rail at the front.
Lift in the right sealing plates and screw them into place in each other. Which holes are used depends on whether it is a
Contura 11 or 21.
ASSEMBLY
67
Cut the insulation sheets and seal above the seal
plates.
Place the top plate in position between the concrete
sides. For the top panel to fit the Contura 21 the
breakouts in the side must be removed.
To avoid gaps in the panel lines of the front area, the height extension panel must be hung first without silicone. Adjust the components so that the joints between them look good, use shims where necessar y.
Concrete variant
Apply silicone along the front edge of the sides and bond the front in position. Position the soot hatch loosely without silicone to make it possible to sweep through the front.
ASSEMBLY
68
Steel variant
Apply silicone beads along the front edge of the sides and bond the inner front panel. Hang the soot hatch in place. The normal front panel then hangs loosely over the inner front panel and can be removed when sweeping.
The surround can now be joined and painted according to page 57, after which the grilles can be put in place.
Final inspection of the installation
Before the stove is used, it must be inspected by an authorised chimney sweep. Read the “Instructions for
Lighting the CI 10 / CI 20 series” before lighting the fire for the first time.
ASSEMBLY
69
The woodbox consists of four pieces that are bonded to each other and the surround using silicone. First bond the base plate and then the back, sides and upper section. The woodbox can be turned both ways for positioning on either the left or right side.
If the surround has been raised using shims, the log box must also be raised to align with the surround.
Installing the woodbox
ASSEMBLY
Cont ura reserv es the right t o change dimen sions and
proce dures desc ribed in thes e instruct ions at any time wi thout speci al notice. Th e current ed ition can be downloaded from www.contura.eu
NIBE AB · Box 134 · 285 23 Markaryd · Sweden www.contura.eu
811041 IAV SE-EX C11/C21- 8
20 14-11-04
Loading...