Unidrive SP Panel Mount Ratings and Specifi cations
200-240VAC +/- 10% Single Phase (kW@220V) (HP@230V)
Normal Duty Heavy Duty
Frame Size Modules
SP0201 - - - 2.2 0.37 0.5
0
SP0202 - - - 3.1 0.55 0.75
SP0203 - - - 4 0.75 1
SP0204 - - - 5.7 1.1 1.5
SP0205 - - - 7.5 1.5 2
Max Cont
Current (A)
200-240VAC +/- 10% (kW@220V) (HP@230V)
Frame Size Modules
SP0201 - - - 2.2 0.37 0.5
0
1
2
3
4
5
SP0202 - - - 3.1 0.55 0.75
SP0203 - - - 4 0.75 1
SP0204 - - - 5.7 1.1 1.5
SP0205 - - - 7.5 1.5 2
SP1201 5.2 1.1 1.5 4.3 0.75 1
SP1202 6.8 1.5 2 5.8 1.1 1.5
SP1203 9.6 2.2 3 7.5 1.5 2
SP1204 11 3 3 10.6 2.2 3
SP2201 15.5 4 5 12.6 3 3
SP2202 22 5.5 7.5 17 4 5
SP2203 28 7.5 10 25 5.5 7.5
SP3201 42 11 15 31 7.5 10
SP3202 54 15 20 42 11 15
SP4201 68 18.5 25 56 15 20
SP4202 80 22 30 68 18.5 25
SP4203 104 30 40 80 22 30
SP5201 130 37 50 105 30 40
SP5202 154 45 60 130 37 50
Max Cont
Current (A)
Typical Motor Output Power
(kW) (HP)
Normal Duty Heavy Duty
Typical Motor Output Power
(kW) (HP)
Max Cont
Current (A)
Max Cont
Current (A)
Typical Motor Output Power
(kW) (HP)
Typical Motor Output Power
(kW) (HP)
380-480VAC +/- 10% (kW@400V) (HP@460V)
Frame Size Modules
SP0401 - - - 1.3 0.37 0.5
0
1
2
3
4
5
6
SP0402 - - - 1.7 0.55 0.75
SP0403 - - - 2.1 0.75 1
SP0404 - - - 3 1.1 1.5
SP0405 - - - 4.2 1.5 2
SP1401 2.8 1.1 1.5 2.1 0.75 1
SP1402 3.8 1.5 2 3 1.1 1.5
SP1403 5 2.2 3 4.2 1.5 3
SP1404 6.9 3 5 5.8 2.2 3
SP1405 8.8 4 5 7.6 3 5
SP1406 11 5.5 7.5 9.5 4 5
SP2401 15.3 7.5 10 13 5.5 7.5
SP2402 21 11 15 16.5 7.5 10
SP2403 29 15 20 25 11 20
SP2404 29 15 20 29 15 20
SP3401 35 18.5 25 32 15 25
SP3402 43 22 30 40 18.5 30
SP3403 56 30 40 46 22 40
SP4401 68 37 50 60 30 50
SP4402 83 45 60 74 37 60
SP4403 104 55 75 96 45 75
SP5401 138 75 100 124 55 100
SP5402 168 90 125 156 75 125
SP6401 205 110 150 180 90 150
SP6402 236 132 200 210 110 150
Max Cont
Current (A)
Normal Duty Heavy Duty
Typical Motor Output Power
(kW) (HP)
Max Cont
Current (A)
Typical Motor Output Power
(kW) (HP)
21
500-575VAC +/- 10% (kW@575V) (HP@575V)
Frame Size Modules
SP3501 5.4 3 3 4.1 2.2 2
SP3502 6.1 4 5 5.4 3 3
SP3503 8.4 5.5 7.5 6.1 4 5
3
4
5
6
SP3504 11 7.5 10 9.5 5.5 7.5
SP3505 16 11 15 12 7.5 10
SP3506 22 15 20 18 11 15
SP3507 27 18.5 25 22 15 20
SP4603* 36 22 30 27 18.5 25
SP4604* 43 30 40 36 22 30
SP4605* 52 37 50 43 30 40
SP4606* 62 45 60 52 37 50
SP5601* 84 55 75 63 45 60
SP5602* 99 75 100 85 55 75
SP6601* 125 90 125 100 75 100
SP6602* 144 110 150 125 90 125
Max Cont
Current (A)
500-690VAC +/- 10% (kW@690V) (HP@690V)
Frame Size Modules
SP4601 22 18.5 25 19 15 20
SP4602 27 22 30 22 18.5 25
4
5
6
SP4603 36 30 40 27 22 30
SP4604 43 37 50 36 30 40
SP4605 52 45 60 43 37 50
SP4606 62 55 75 52 45 60
SP5601 84 75 100 63 55 75
SP5602 99 90 125 85 75 100
SP6601 125 110 150 100 90 125
SP6602 144 132 175 125 110 150
Max Cont
Current (A)
Normal Duty Heavy Duty
Typical Motor Output Power
(kW) (HP)
Normal Duty Heavy Duty
Typical Motor Output Power
(kW) (HP)
Max Cont
Current (A)
Max Cont
Current (A)
Typical Motor Output Power
(kW) (HP)
Typical Motor Output Power
(kW) (HP)
Notes: Select model on actual motor full load current. *The same model can be used on a 575V or a 690V supply, and has two different output
ratings. For example: At Normal Duty, SP4603 is suitable for a 22kW output motor on a 575V supply and a 30kW output motor on a
690V supply. Can be used on IT supplies - all voltages, Grounded delta supplies - all voltages except 690V
Normal Duty Suitable for most applications, current overload of 110% for 165 seconds is available. Where motor rated current is less than the drive
rated continuous current, higher overloads are achieved.
Heavy Duty Suitable for demanding applications, current overload of 175% for 40 seconds is available for frame size 0 - 5 in closed loop, 150%
for 60 seconds in open loop. For frame size 6 current overload of 150% for 60 seconds is available in closed loop and 129% for 97
seconds in open loop. Where the motor rated current is less than the drive rated continuous current higher overloads (200% or greater)
are achieved.
Environmental Safety and Electrical Conformance
• IP20/Nema 1 rating, IP54 (NEMA 12) through panel mount
• Ambient temperature -15 to +40°C, 50°C with derating
• Humidity 95% maximum (non condensing) at 40°C
• Altitude: 0 to 3000m, derate 1% per 100m between 1000m
and 3000m
• Vibration: Tested in accordance with IEC 60068-2-34
• Mechanical Shock Tested in accordance with IEC 60068-2-27
• Storage temperature -40°C to 50°C
• Electromagnetic Immunity complies with EN 61800-3
and EN 61000-6-2
• With on board EMC fi
lter, complies with EN 61800-3
(2nd environment)
• EN 61000-6-3 and EN 61000-6-4 with optional footprint EMC fi lt
• IEC 61000-3-4 Supply conditions
• IEC 60146-1-1 Supply conditions
• IEC 61800-5-1 (Power Drive Systems)
• IEC 61131-2 I/O
• EN 60529 Ingress protection
• EN 50178 / IEC 62103 Electrical safety
• Safe Torque Off (formally secure disable), independently assessed by
BGIA t
o EN 954-1 cat 3
• EN 81-1 assessed by TÜV
• EN 61000-6-2, EN 61000-6-4 EMC, UL508C, UL840
er
22