12950 W.Eight Mile Road • Oak Park,MI 48237-3288 • 248/399-8000 • FAX:248/399-7246 • www.trerice.com
1/1/2001
47
Elec tronic Controller TR870 Series
Features PID and Auto-Tuning
The Trerice TR870 Series Electronic PID
Controller is designed for use on applications
where large load changes are expected, or the
need for extreme accuracy and fast response
time exists. With full auto-tune capabilities and
a large selection of available inputs, the
TR870 Series is ideally suited for use with a
Trerice Control Valve.
Specifications
How to Order
Sample Order Number: TR8728A00
TR872 8 A 00
Model Input Control Output Optional Functions*
TR871 48 x 48 mm (1/16DIN) 8 Multi (T/C, RTD, mVdc) A 4 to 20 mA 00 None
TR872 72 x 72 mm 4 mA C On/Off Contact 01 High/Low Alarms
TR873 96 x 96 mm (
1
/4DIN) 6 Vdc D SSR Driver 04 Setback Function
TR874 96 x 48 mm (
1
/8DIN) E 0 to 10 Vdc 05 High Alarm/Setback Function
02 High Alarm/30A Heater Break
03 High Alarm/50A Heater Break
06 High Alarm/30A HB/Setback
07 High Alarm/50A HB/Setback
Model
TR871: 48 x 48 mm (1/16DIN)
TR872: 72 x 72 mm
TR873: 96 x 96 mm (
1
/
4
DIN)
TR874: 96 x 48 mm (
1
/8DIN)
Control
Control Mode: Auto-tuning PID
Action: Reverse acting (field
switchable to direct acting)
Proportional Band:
Off, 0.1-999.9% Full Scale
Integral Time: Off, 1-6000 sec.
Derivative Time: Off, 0-3600 sec.
Accuracy
0.5%
Display
Process Value: 4 digit, 12.7 mm
green LED
Set Value: 4 digit, 10.2 mm
red LED
Sampling Cycle: 0.5 seconds
Inputs
Multi (switchable between)
Thermocouple: B, E, J, K, L,
N, R, S, T, U; or
RTD: Platinum, 100Ω, 3-wire;
or
Voltage: 0-10, 10-50, 0-100
mV
Current: 4-20 mA (fixed)
Voltage: 0-1, 1-5, 0-10 Vdc (fixed)
Control Output
Current: 4-20 mA (load
resistance: 600Ω maximum)
Contact: Fixed proportional cycle,
20 sec. (capacity: 240 Vac 2.5 A
{TR871 = 2A} / resistive load)
SSR Drive Voltage: Fixed
proportional cycle, 2 sec.
(output rating: 15±3 Vdc / 20 mA
maximum)
Voltage: 0-10 Vdc (load current:
2 mA maximum)
Power Requirements
Supply Voltage: 100-240 Vac
50/60 hz
Consumption: Approx. 11 VA
Data Storage
Nonvolatile EEPROM memory
Case Material
Polyphenylene oxide
Ambient T empera ture
14°F (-10°C) to 122°F (50°C)
Humidity
Maximum: 90% RH
Approximate Shipping
Weight
TR871: 0.4 lbs [0.18 kg]
TR872: 0.6 lbs [0.27 kg]
TR873: 0.7 lbs [0.32 kg]
TR874: 0.6 lbs [0.27 kg]
Optional Features
Alarms
Heater Break Alarm
Setback Function
Multiple Sizes
±0.5% Accuracy
Keyboard
Programmable
Reverse or
Direct Acting
TR873 pictured
Requires
Control Output
C or D
*Setback function (codes 04, 05,
06, 07) not available on TR871.
Controllers