Elec tronic Controller TR860 Series
Features PID and Auto-Tuning
The Trerice TR860 Series Electronic PID
Controller is designed for use on applications
where large load changes are expected, or the
need for extreme accuracy and fast response
time exists. With full auto-tune capabilities and
a large selection of available inputs, the
TR860 Series is ideally suited for use with a
Trerice Control Valve.
How to Order
Sample Order Number: TR8632A900301
TR863 2 A 90 03 0 1
Model Input Control Output Power Supply Alarms Analog Output Setback Function
TR862 72x72 mm 1 Thermocouple A 4-20 mA 90 100-240 Vac 50/60 Hz 00 None 0 None 0 None
TR863 96x96 mm 2 RTD C On/Off Contact 10 24 Vac 50/60 Hz 03 High/Low 3 0-10 mVdc 1 Included
(
1
/4DIN) 3 mV D SSR Driver 02 24 Vdc 12 High/Low/Event 4 4-20 mA
TR864 96x48 mm 4 mA E 0-10 Vdc Output 6 0-10 Vdc
(
1
/8DIN) 5 Vdc 14 30AHeater Break
16 50AHeater Break
13 High/Low
30A Heater Break
15 High/Low
50A Heater Break
Specifications
Model
TR862: 72 x 72 mm
TR863: 96 x 96 mm (
1
/4DIN)
TR864: 96 x 48 mm (
1
/
8
DIN)
Control
Control Mode: Auto-tuning PID
with manual output override
Action: Reverse acting
(field switchable to direct acting)
Proportional Band:
Off, 0.1-999.9% Full Scale
Integral Time: Off, 1-6000 sec.
Derivative Time: Off, 0-3600 sec.
Accuracy
0.3%
Display
Process Value: 4 digit, 12.7 mm
red LED
Set Value: 4 digit, 10.2 mm
green LED
Sampling Cycle: 0.25 seconds
Inputs
Thermocouple: B, E, J, K, L, N,
PLII, R, S, T, U, WRe5-26
RTD: Platinum, 100Ω, 3-wire
Voltage: (scaleable) -10-10, 0-10,
0-20, 0-50, 10-50, 0-100 mVdc or
-1-1, 0-1, 0-2, 0-5, 1-5, 0-10 Vdc
Current:
(scaleable) 4-20, 0-20 mA
Control Output
Current: 4-20 mA (load
resistance: 600Ω maximum)
Contact: Proportional cycle,
1-120 sec. (capacity: 240 Vac
2.5 A/resistive load)
SSR Drive Voltage: Proportional
cycle, 1-120 sec. (output rating:
15±3 Vdc / 20 mAmaximum)
Voltage: 0-10 Vdc (load current:
2 mA maximum)
Power Requirements
Supply Voltage:
100-240 Vac, 50/60 Hz (24 Vac,
50/60 Hz or 24 Vdc optional)
Consumption:
Maximum 8 VA(AC), 8 W (DC)
Data Storage
Nonvolatile EEPROM memory
Case Material
Polyphenylene oxide
Ambient T empera ture
14°F (-10°C) to 122°F (50°C)
Humidity
Maximum: 90% RH
Approximate Shipping
Weight
0.7 lbs [0.32 kg]
Optional Features
Alarms
Event Output
Heater Break Alarm
Analog Output
Setback Function
Multiple Sizes
±0.3% Accuracy
Keyboard
Programmable
Reverse or
Direct Acting
Manual Output
Override
The Trerice No.TA987 Air Filter/Regulator is
recommended for filtering and regulating the
pressure of plant compressed air and delivering
clean,dry air at the proper pressure to pneumatic
control devices.
TR863 pictured
Requires
Control Output
C or D
Controllers