PARKER COLUMN TRAY TYPE DEAERATOR SPEC. SHEET D-106DAT
0A4
SPECIFICATIONS
B
Tank
Dia.
Dimensions ***
In.
C
Overall
Width
D
Height
E**
Water
Inlet
F**
Steam
Inlet
Dry Operating Overfull
MODEL NO.
DAT3048 3,500 100 92 184 69 30 40 132 3/4 3/4 1,875 2,650 3,530
DAT3072 6,300 185 128 256 93 30 40 132 1 1 2,000 3,065 4,350
DAT3660 8,100 235 162 327 96 36 46 138 1 1 2,300 3,650 5,200
DAT3696 12,000 350 241 483 123 36 48 138 1 1/2 1 1/2 2,700 4,707 6,930
DAT36132 16,000 466 322 639 160 36 48 138 1 1/2 1 1/2 3,120 5,800 8,650
DAT42120 20,500 594 410 820 154 42 56 144 2 2 3,750 7,200 10,825
DAT48108 25,020 725 501 990 142 48 62 148 2 2 4,000 8,180 12,380
DAT5496 30,000 870 600 1150 133 54 68 154 2 2 5,200 10,200 15,200
DAT54120 35,000 1,015 700 1380 154 54 68 154 2 1/2 2 1/2 6,150 11,985 18,200
* – Capacity based on at least 10 minutes storage capacity.
** – Depends on pressure.
*** – Standard frame height. Height dimensions may vary upon pump specification and job condition.
**** – Weights vary based on pump selection job conditions.
CLEARANCES
Notes: Dimensions are for reference only. Due to continuous improvement, specifications are subject to change without notice.
Pounds
/ hr
Capacity *
Boiler
HP
Reserve
Capacity
(gal)
PANEL TOP SIDE BACK MANHOLE SIDE RECOMMENDED
36-48″ 18″ 24″ 6-24″ 24″
Tank
Volume
(gal)
A
Tank
Length
Weight****
(lbs)
D-106dat.doc