Control Products BD1648 User Manual

BLOWOFF TANKS
For Parker Steam Boilers 1 1/2 to 150 H.P.
115 Blowoff Tanks
The Parker Blowoff Tank
The Parker Blowoff Tank is a high­quality, heavy-duty tank properly designed with adequate volume to provide a safe and effective blowoff which is necessary for flushing steam boilers.
All tanks have been tested for the sizes of Parker Boilers listed and approved by the Manufacturer for safe and proper blowoff.
The Parker Blowoff Tank is recommended with all steam boilers. It is required by most local inspection jurisdictions.
ADVANTAGES
1. Safe Blowoff
The tank is properly designed for Parker Boilers to prevent unsafe pressure buildup and to eliminate the hazard of discharging steam and hot water to the atmosphere. Do not confuse the Parker with small tanks or separators that discharge steam unsafely out drain and vent.
2. Non-Restrictive
The tank has the proper size vent and generous storage capacity equal to at least double the amount of blowoff water. On Parker Boilers, this permits complete blowoff from full pressure so that scale and sediment can be thoroughly flushed from the boiler.
3. Special Drain Fitting
The internal drain pipe with syphon breaker is arranged to maintain a water storage equal to no less than the blowoff water volume when applied to Parker Boilers. The tank drains from the cooler lower level so that drain water does not normally exceed 140°F.
4. Blowoff Cooling Assembly
(Optional) When multiple boilers feed one Blowoff Tank, (or for special circumstances), the Parker Blowoff Cooling Assembly can be fitted to the tank outlet to cool blowoff discharge water to meet UPC standards.
5. Heavy Internal Baffle
The blowoff inlet baffle distributes the discharge uniformly to protect the tank shell for long life.
6. Heavy Construction
All tanks are designed for a minimum of 125 PSI even though they are vented to the atmosphere. Tank shell and heads are standardly 3/16” thick on tanks up to 20” diameter and 1/4” thick on larger tanks. Heavier tanks are available when specified.
7. Easily Cleaned
Convenient inspection and clean-out openings are provided so that the tank can be very easily inspected and cleaned.
8. Compact & Attractive
The tanks are designed to minimum diameters and with openings arranged so installation can be made against the wall or in the corner of the room for minimum floor space. Tanks are painted with an attractive, durable finish.
9. Codes
All tanks are manufactured and furnished in accordance with the ASME Boiler and Pressure Vessel code and American National Standard, ANSI/ASME BVP-VIII-1. Inspection and registration are with The National Board of Boiler and Pressure Vessel Inspectors. Blowoff Tanks also comply with the International Association of Plumbing and Mechanical Officials’ Uniform Plumbing Code.
Inlet
Outlet
115 Blowoff Tanks
National Board
PARKER
B O I L E R C O.
NEVER A COMPROMISE FOR QUALITY OR SAFETY
5930 Bandini Boulevard
Los Angeles CA 90040
www.parkerboiler.com
Phone (323) 727-9800
BROCHURE 115 OA3
BLOWOFF TANKS
For Parker Steam Boilers 1 1/2 to 150 H.P.
115 Blowoff Tanks
32-Vent
Front View Side View
4”
Manhole only on 4272 tank
24”
33H11H
4”
No. ITEM UNITS BLOWOFF TANK MODEL
PART NUMBER BD1248 BD1648 BD2048 BD2448 BD3048 BD3672 BD4272
Parker Boiler Size, Maximum HP 12 16 30 40 50 115 150 Maximum Working Pressure PSI 125 125 125 125 125 125 125 Blowoff Capacity (1/2 tank) Gal 12 24 39 57 92 189 266 Shell and Head Thickness In 3/16 3/16 3/16 1/4 1/4 1/4 1/4
Diameter In 12 16 20 24 30 36 42 L1 Shell Length In 48 48 48 48 48 72 72 L3 Height Overall In 66 68 71 73 76 103 106 11 Blowoff Inlet Size In 1 1 1-1/4 1-1/4 1-1/2 2 2 11H Blowoff Inlet Height In 47 48 49 50 52 67 69 32 Vent Size - NPT In 2-1/2 2-1/2 3 3 4 5 5
*
33 Water Outlet Size In 1 1 1-1/4 1-1/4 1-1/2 2 2 33H Water Outlet Height In 35 36 37 38 40 53 55 34 Drain/Cleanout Size In 2 2 2 2 2 2 2 35 Inspection Opening Size In 1-1/2 1-1/2 2 2 2 2 2
Size for up to 150 PSI-NPT
Shipping Weight Lbs 180 220 295 435 575 930 1095
Minimum Reduced Vent Line
32L
In 2 2 2-1/2 2-1/2 3 4 4
35-Inspection
11-Blowoff (Inlet)
33-Water Outlet
35-Inspection Opening
34-Drain/Cleanout
Internal Baffle
Syphon Breaker
L3L1
Notes
Standard Tanks comply with A.S.M.E., Uniform Plumbing, State of
California, and City of Los Angeles Codes. Tanks are registered with the National Board.
Tank sizes shown are for Parker Boilers only. For other makes of boilers,
the blowoff capacity of the tank must be at least one Blowoff volume.
115 Blowoff Tanks
5930 Bandini Boulevard Los Angeles CA 90040
www.parkerboiler.com
Phone (323) 727-9800
BROCHURE 115 OA3
Tanks that comply with the National Board “Boiler Blowoff Equipment
Recommendations” are available with heavier construction and special openings at additional cost. Add *NB after part number.
Consult local inspection authority for approval before reducing vent line to
*
size shown above.
PARKER
B O I L E R C O.