Control Products A4 User Manual

PILOT-OPERATED
REGULATING VALVES
116
428 Jones Boulevard • Limerick Airport Business Center • Pottstown PA • 19464 • Tel: 610-495-5131 • Fax: 610-495-5134
www.watsonmcdaniel.com
Pilot-Operated Regulating Valves
REGULATING VALVES
PILOT-OPERATED
428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134
www.watsonmcdaniel.com
117
HD Series Pilot-Operated Regulators
PILOT-OPERATED REGULATORS
PILOT-OPERATED
HD-Series
REGULATING VALVES
Steam Service
& temperature rating, a large full-port strainer with blow-down valve on pilot adapter which keeps dirt from entering control pilots, and field reversible pilot-mounting for versatile and easy installation.
The HD-Series Regulator features Ductile Iron construction for increased pressure
Page No.
HD Series Pilot-Operated Regulating Valve 120-123
DUCTILE IRON BODY
HD Regulators are used in conjunction with the appropriate Pilot(s) to control Steam Pressure or Process Temperature
PILOTS for HD Regulators 124-135
P” & “P5 Pressure Pilots -
The “P5” is used for special applications requiring 0.5 PSI accuracy.
The “P” is the standard spring-loaded pressure pilot. 124
BP Back Pressure Pilot - Controls system back pressure. 125
T Temperature Pilot - Used for controlling temperature. 126-127
A Air Pilot -
PTR” & “PTL
TRP Temperature Pilot - Special purpose temperature pilot for controlling low temperatures 132
S Solenoid Pilot - Used in conjunction with any of the above pilots for electrical on/off 133
DP DP Pilot - Differential Pressure pilot – used when trying to balance two different 134
Also used for temperature control when used in conjunction with the “PTR” or “PTL” temperature controller.
Temperature Controllers
a wider temperature range than the standard “T” Pilot.
outside the range of the standard “T” Pilot. Also available with special sensing bulbs.
control of HD Regulators.
media sources that are being blended
Normally used for controlling steam pressure using an air signal.
(used with “A” Air Pilot) - The “PTR” or “PTL” will control
128-129
130-131
Over Pressure Protection Methods 135
118
428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134
www.watsonmcdaniel.com
HD Series Regulators (with commonly used Pilots) 136-143
HDP Pressure Regulator 136-137
(HD Regulator with “P” Pressure Pilot)
HDT Temperature Regulator 138-139
(HD Regulator with “T” Temperature Pilot)
HDA Air Controlled Pressure Regulator 140-141
(HD Regulator with “A” Air Pilot)
REGULATING VALVES
PILOT-OPERATED
HDP T Pressure & Temperature Regulator
(HD Regulator with “P” Pressure & “T” Temperature Pilot)
142-143
HSP Series Pilot-Operated Pressure Regulating Valve
CAST STEEL BODY
The Watson McDaniel HSP Pilot-operated Regulating Valve is constructed of Cast Carbon Steel for higher pressure &
Noise Attenuation - Reduces noise in pressure reducing applications 148-151
Noise Attenuators for Pressure Regulators – Series A, H & S 146-149
Capacities for Sizing of HD & HSP Series Regulators 150-151
temperature ratings.
144-145
428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134
www.watsonmcdaniel.com
119
REGULATORS
HD Series
Pilot-Operated Regulating Valve
Ductile Iron
Model HD-Series Sizes 1/2” – 6” Connections Threaded 1/2” - 2”
Flanged 150# 1” - 6” Flanged 300# 1” - 6”
Body Material Ductile Iron PMO Max. Operating Pressure 300 PSIG
Design Pressure/ NPT 450 PSIG @ 650˚ F Temperature Ratings 150# FLG 150 PSIG @ 566˚ F
REGULATING VALVES
PILOT-OPERATED
TMA/PMA 300# FLG 450 PSIG @ 650˚ F
TYPICAL APPLICATIONS
The Watson McDaniel HD-Series pilot operated regulators were designed for extremely accurate control of temperature and
pressure in steam service applications. The HD-Series is made of Ductile-iron for extended pressure and temperature ratings. These
regulators use several different control pilots, which can be attached to the valve to control pressure, temperature, or a combination of both. The different control pilots can be added or removed from the regulator body. This modular design adds to the versatility of this product. The most common options include the P-Pilot for pressure reducing, and the T-Pilot for temperature control.
Ductile Iron Body
Hardened SST (55 Rc) Seat & Disk
INLET
Self-cleaning stem guide
Spring protected from steam
High Tensile
Diaphragm
Ductile Iron body for higher pressures
Full port strainer & blowdown
Hardened stainless steel trim
Pre-mounted tubing & field reversible
Optional reduced port trim
Low differential pressure option
Low inlet pressure option
Right or Left Pilot Mounting Available
(Non-standard left mounted shown)*
Full Port Pilot Strainer with built-in Blowdown Valve
* Standard pilot mounting is
on the right side of the regulator when looking into the outlet port. Pilot mounting on HD regulators are field reversible.
valve on pilot adapter for ultimate protection from dirt & scale
for extended life
pilot adapter
FEATURES
No external power source is required.
This simplifies the valve and minimizes installation and maintenance costs.
Pressure and temperature pilots can be used
in combination eliminating the need for a separate pressure and temperature regulator
Ductile iron for higher pressure ranges and
increased safety. Ductile Iron is a better choice than cast iron for steam applications.
Full port strainer and blowdown valve on
pilot adapter for ultimate protection against dirt and scale
Hardened stainless steel trim (55 Rc) for
extended life even in the most demanding applications
The innovative design allows the pilot to be
mounted on either side of the regulator and is easily field reversible
Comes fully assembled with tubing and pilot
adapter. The control pilot requires only four bolts to complete the installation.
120
428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134
www.watsonmcdaniel.com
Watson McDaniel reserves the right to change the designs and/or materials of its products without notice. ©2010 Watson McDaniel Company
REGULATORS
HD Series
Pilot-Operated Regulating Valve
TYPICAL PILOTS
PRESSURE
Pilot
AIR
Pilot
TEMPERATURE
Pilot
SOLENOID
Pilot
CONTROL PILOTS
Pilot Mounting
Standard pilot mounting is on the right side of the regulator when looking into the outlet port (see diagrams on next page which are all right mounted). For opposite mounting, please specify when ordering. Pilot mounting on HD regulators are field reversible.
Pressure
When controlling pressure there are several options you can use for a pilot. The P-Pilot and the P5-Pilot are both spring adjusted pressure pilots. The P-Pilot is used on typical general-purpose pressure reducing applications. The P5-Pilot is used when higher accuracy is required and is capable of maintaining a control pressure window of less then 1 PSI. The A-Pilot is air controlled and generally used when adjustment of the regulator and pressure reducing station is done remotely.
Temperature
The T-Pilot is used to control temperature. The T-Pilot is filled with a temperature sensitive liquid, which expands when heated. The expansion of this liquid actuates a bellows that controls the temperature-regulating valve. The T-Pilot is equipped with an overheat bellows that protects the pilot in case of an over temperature condition. The T-Pilot controls temperature through a range of 60-260˚F. Spec: ANSI/FCI 70-2 Class IV shut-off.
TYPICAL APPLICATIONS
Pressure Regulating
Temperature Regulating
Pressure-Temperature Control
Back Pressure Control
Differential Pressure Control
On-Off
On-off control of the regulator is possible by using the S-Solenoid
Pilot. The S-Pilot allows the regulator to be shut off or turned on electrically. Normally the regulator is equipped with either a P-Pressure Pilot or T-Temperature Pilot in addition to the
S-Solenoid Pilot.
Pressure-Temperature
The PT-Pilot combination is used when it is desirable to control both the pressure and temperature of a system with only one regulating valve. The unique features of this modular valve allow this to be accomplished quite easily. When the PT-Pilot combination is used, the downstream pressure is limited to a maximum setting by the pressure pilot, while the temperature pilot maintains the correct temperature.
Back Pressure
When controlling the back pressure in a steam system, the BP-Pilot is used in conjunction with the HD-Series Regulator. This controls the pressure on the upstream side of the regulator.
Differential Pressure
The DP-Pilot is used when trying to balance two different media sources that are being blended.
REGULATING VALVES
PILOT-OPERATED
COMBINATION PILOTS
One of the advantages of the HD-Series regulating valve is that it can be used with many different variations of control pilots. Up to three pilots can be used simultaneously to control the operation of these valves. The most common is the “PT” Pressure­Temperature combination pilots. In addition to these pilots being used together the S-Solenoid Pilot can be used for turning the system on and off. (See next page for combination examples.)
428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134
www.watsonmcdaniel.com
121
REGULATORS
HD Series
Pilot-Operated Regulating Valve
TYPICAL REGULATOR & PILOT COMBINATIONS
Watson McDaniel reserves the
right to change the designs
and/or materials of its
products without notice.
©2010 Watson McDaniel Company
PILOT-OPERATED
Regulator
REGULATING VALVES
Solenoid Pilot
HDA
with
Air Pilot
HDS
Regulator
with
HDP
Regulator
with
Pressure Pilot
HDPS
Regulator
with
Pressure & Solenoid
Pilots
HDT
Regulator
with
Temperature
Pilot
HDTS
Regulator
with Temperature & Solenoid Pilots
HDPT
Regulator
Pressure &
Temperature
122
HDPTS
Regulator
with
Pilots
428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134
with
Pressure,
Temperature &
Solenoid Pilots
OTHER PILOT CONFIGURATIONS USED WITH HD REGULATOR
• Air / Solenoid
• Air / Pneumatic Temperature Controller
• Air / Solenoid / Pneumatic Temperature Controller
• Back Pressure
• Back Pressure / Solenoid
• Differential Pressure
Watson McDaniel’s Pilots will fit other
Manufacturers’ Regulators.
www.watsonmcdaniel.com
REGULATORS
HD Series
Pilot-Operated Regulating Valves
HD-Series DIMENSIONS –
(A) Face-To-Face Weight (lbs) Size NPT 150# 300# B C D NPT 150# 300# 1/2” 4 3/4” 4
11/4 6 11/2 7
21/2 9
3
/8
3
/8
3
1” 5
2” 7
3” 10 10 4” 11 6” 15
1
/8
5
/2
1
/2
1
7
/4
6
/8
1
1
/2
8
/2
3
/8
7
/8
1
/8
7
10 9 5
12
16 14
1
5
/2
1
5
/2
1
66
3
98
/4
3
7
/8
3
/8
7
/8
1
/4
3
7
/4
8
/8
1
7
/2
10
/8
1
/8
inches / pounds
3
3 3 3 4 4 5
6 7
10 19
1
/8
6
/2
3
1
/8
6
/2
1
/2
7 23 40 45
7
3
/8
8
/4
7
3
/8
8
/4
3
3
3
1
7
/8
10
/8
3
/4
11
/4
1
/4
13
/4
3
/2
14
/4
3
/4
18 18
43 43 55 60 65 75 85
100 105 130 145 215 235 420 470
Option: Stainless diaphragms and external tubing - consult factory
MATERIALS
Body Ductile Iron Cover Ductile Iron Gasket Grafoil Cover Screws Steel Pilot Adapter Ductile Iron/Cast Steel Screen Stainless Steel Tubing Copper Valve Seat Hardened SST (55Rc) Valve Disc Hardened SST (55Rc) Diaphragm Phosphor Bronze
MINIMUM OPERATING PRESSURES
Minimum Inlet Pressure (for Valve):
15 PSIG (Standar 5 PSIG (Low Pr
Minimum Differential Pressure
10 PSI (Standar 3 PSI (Low Pr
* Not required for Temperature Pilot applications
d Main Valve)
essure Main Valve)
(for Valve):*
d Main Valve)
essure Main Valve)
HOW TO ORDER
REGULATOR BODY
Specify: • HD regulator body
• Regulator size or capacity of steam required
• End connections (threaded, 150/300# flanged)
PILOT REQUIRED TO OPERA
Note: See “How to Order” in specific Pilot Section
T Temperature Pilot
P Pressure Pilot
A Air Pilot
S Solenoid Pilot
BP Back Pressure Pilot
PD Differential Pressure
TE THIS VALVE
REGULATING VALVES
PILOT-OPERATED
FLOW
A
FLG
A
NPT
Pilot mounting
surface
C
OUT
B
D
428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134
www.watsonmcdaniel.com
Standard pilot mounting is on the right side of the regulator when looking into the outlet port (as shown). Pilot mounting on HD regulators are field reversible.
123
PILOTS
Pressure Pilot for HD Regulating Valves
P
&
P5”Pilot
Pressure Pilot
Max Inlet Pressure: 300 PSIG
Reduced Outlet Pressure Range: 3-200 PSIG
Minimum Inlet Pressures:
15 PSIG when used with standard main valve
5 PSIG when used with low pressure main valve
P-Pilot (Standard)
P5-Pilot (Special)
REGULATING VALVES
PILOT-OPERATED
PRESSURE-ADJUSTING SPRING RANGES
“P” Pressure Range “P5” Pressure Range Identifying Colors
3-25 PSIG 1-10 PSIG yellow 20-100 PSIG 10-25 PSIG blue 80-200 PSIG red
+
1 PSIG accuracy
+
0.5 PSIG accuracy
Watson McDaniel reserves the
right to change the designs
and/or materials of its
products without notice.
©2010 Watson McDaniel Company
MATERIALS
Pilot Body & Cover Ductile Iron or Cast Steel Gasket Grafoil Diaphragm Phosphor Bronze Head & Seat Assembly Hardened SST (55 Rc)
TYPICAL APPLICATIONS
The “P” & “P5” Pressure Pilots are used with the HD Regulator
to control steam pressure in steam mains or for process equipment. Pilot operated regulators will maintain constant downstream pressure even when the inlet pressure to the valve fluctuates or steam usage varies.
FEATURES
The “P” Pilot can maintain downstream pressure to ±1 PSIG
“P5” Pilot can maintain downstream pressure to ±0.5 PSIG
Choic
es of three overlapping pressure ranges
Pressure control spring can be changed in line
Pilot is easily installed using only four bolts
Full port strainer and blowdown valve on pilot adapter for
ultimate protection from dirt and scale Can be used with temperature and solenoid control pilot
Solid floating diaphragm is more failure resistant
Watson McDaniel's pilots can be used with other
manufacturers’ regulators
OPTIONS
Pressure pilot can be used with temperature pilot to eliminate
the need for two separate regulators Solenoid pilot can be added for remote on/off control
of regulator “P5” Pilot will maintain +0.5 PSIG accuracy
HOW TO ORDER
“P”, “P5” PRESSURE PILOT
Specify: • Reduced pressure range – Example: “P” Pilot at 3-25 PSIG, yellow
REGULA Specify: HD regulator body
TOR BODY
• Regulator size or capacity
• End connections (threaded, 150/300# flanged)
Steam Sensing Line
Connection
1/4” NPT
91/2
12
MINIMUM OPERATING PRESSURES
Minimum Inlet Pressure:
15 PSIG (Standar
5 PSIG (Low Pr
Minimum Differential Pressure:
10 PSI (Standar
3 PSI (Low Pr
124
428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134
d Main Valve)
essure Main Valve)
d Main Valve)
essure Main Valve)
Units: inches
5
8
www.watsonmcdaniel.com
P
P5
Back Pressure Pilot for HD Regulating Valves
Back Pressure
PILOTS
BP”Pilot
Pilot
Max Inlet Pressure: 300 PSIG
Back Pressure Range: 10-200 PSIG
Minimum Inlet Pressures:
15 PSIG when used with standard main valve
5 PSIG when used with low pressure main valve
PRESSURE-ADJUSTING SPRING RANGES
Pressure Range Identifying Colors
10-25 PSIG yellow 20-100 PSIG blue 80-200 PSIG red
TYPICAL APPLICATIONS
The “BP” Back-Pressure Pilot used with the HD regulator, maintains upstream pressure in steam systems. These regulators are commonly used to supply flash steam to low pressure mains.
FEATURES
The “BP” Pilot can maintain upstream pressure to ±1 PSIG
Choices of three overlapping pressure ranges
Pressure adjusting spring can be changed with
regulator in line
Pilot is easily installed using only four bolts
Full port strainer and blowdown valve on pilot adapter for
ultimate protection from dirt and scale Solid floating diaphragm is more failure resistant
Watson McDaniel's pilots can be used with other
manufacturers’ regulators
MATERIALS
Pilot Body & Cover Ductile Iron Gasket Grafoil Diaphragm Phosphor Bronze Head & Seat Assembly Hardened SST (55 Rc)
HOW TO ORDER
“BP” BACK PRESSURE PILOT
Specify: • Reduced pressure range – Example: “BP” Pilot at 20-100 PSIG, blue
REGULA Specify: HD regulator body
TOR BODY
• Regulator size or capacity
• End connections (threaded, 150/300# flanged)
REGULATING VALVES
PILOT-OPERATED
OPTIONS
Can be used with solenoid pilot for on/off control
MINIMUM OPERATING PRESSURES
Minimum Inlet Pressure:
15 PSIG (Standar
5 PSIG (Low Pr
Minimum Differential Pressure:
10 PSI (Standar
3 PSI (Low Pr
d Main Valve)
essure Main Valve)
d Main Valve)
essure Main Valve)
428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134
www.watsonmcdaniel.com
Steam Sensing Line
Connection
1/4” NPT
Units: inches
91/2
5
125
PILOTS
Temperature Pilot for HD Regulating Valves
T
Pilot
Temperature Pilot
Max Inlet Pressure: 300 PSIG
Temperature Control Range: 60-260 F
Minimum Inlet Pressures:
15 PSIG when used with standard main valve
5 PSIG when low pressure temperature pilot is used
with low pressure main valve
Low Pressure Temperature Pilot must be used
PILOT-OPERATED
REGULATING VALVES
in conjunction with a low pressure main valve for applications where inlet steam pressure is less than 15 PSIG.
SPECIFY WHEN ORDERING.
TYPICAL APPLICATIONS
The “T” Temperature Pilot is used with the HD regulator to control temperature in various processes and systems. Some examples are:
Oil heaters Ovens
Process heaters Vats
Dryers Jacketed Kettles
FEATURES
Temperature adjustment made simple and easy by rotating
an adjustment knob to the desired temperature setting Thermostatic sensing bulb comes with an 8-ft. or 15-ft.
length capillary
Capillary is armor-protected to resist damage
Overheat protection bellows is incorporated into sensing
bulb; 200˚F overheat protection up to 350˚F Full port strainer and blowdown valve on pilot adapter for
ultimate protection from dirt and scale
OPTIONS
Temperature Pilot can be combined with Pressure and
Solenoid pilots Additional capillary lengths can be ordered in 5-ft. increments;
up to 25-ft. maximum length Wells* for isolating sensing bulb from process liquid are
available in 316 stainless steel or brass Extended length wells are available
316 Stainless Steel Sensing Bulb
Other options available; consult factory
* Thermowells:
Wells isolate sensing bulb from the process liquid and are available in Brass or Stainless Steel. When placed on the side of a tank or vessel, the sensing bulb can be removed without having to drain the process fluid.
TEMPERATURE-ADJUSTING RANGES
Temperature Ranges* Identifying Colors
60 - 120 °F (16 - 49 °C) yellow 100 - 160 °F (38 - 71 °C) black 120 - 180 °F (49 - 82 °C) blue 160 - 220 °F (71 - 104 °C) red 200 - 260°F (93 - 127 °C) green
* Other ranges available; consult factory.
MATERIALS
Body Ductile Iron/Cast Steel Head & Guide Stainless Steel Seat Stainless Steel Sensing Bulb:
T Copper Bulb TU Copper Bulb w/Brass Union Hub TUBW Copper Bulb w/Brass Well TUSW Copper Bulb w/Stainless Steel Well TBW Copper Bulb w/Brass Well & Grommet TSW Copper Bulb w/Stainless Steel Well & Grommet
Pressure & Temperature
Pilot
combination
Controls downstream
pressure and process
temperature, eliminating
the need for a separate
pressure regulator
Watson McDaniel reserves the
right to change the designs
and/or materials of its
products without notice.
©2010 Watson McDaniel Company
126
428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134
www.watsonmcdaniel.com
PILOTS
Temperature Pilot for HD Regulating Valves
SENSING BULBS AVAILABLE
81/2
T
TU
TUBW
TUSW
TBW
5/8
51/2
5/8
3/4” NPT
57/8
3/4
3/4” NPT
61/8
3/4
3/4” NPT
18
3/4
3/4” NPT
Units: inches
*Most common
T Plain copper bulb
TU Union connected copper bulb that can be
screwed into the side of tank * most common selection
TUBW Type TU bulb with a brass well. The well, which
isolates bulb from process fluid, can be placed in the side of a tank allowing the sensing bulb to be removed without having to drain the tank of liquid
TUSW Type TU bulb with a corrosion resistant stainless
steel well. The well, which isolates bulb from
process fluid, can be placed in the side of a tank allowing the sensing bulb to be removed without having to drain the tank of liquid
TBW Type T bulb with an extended length brass
well. The extended well allows deeper insertion
of sensing bulb into tanks.
TSW Type T bulb with extended length stainless
steel well. The extended well allows deeper
insertion of sensing bulb into tanks.
Other options available; consult factory.
T
Pilot
REGULATING VALVES
PILOT-OPERATED
TSW
18
3/4
3/4” NPT
Diagram below shows “T” Pilot TU Option for Bulb
63/4
See bulb
chart above
Units: inches
Union Nut
Union Hub 3/4” NPT
HOW TO ORDER
“T” TEMPERATURE PILOT
Specify:
• Temperature range from the chart or indicate the temperature of the process you wish to control
• The length of capillary required; 8-ft. is standard
• Bulb type needed: T, TU, TUBW, TUSW, TBW & TSW
Example: TU, 8 FT CAP, 60-120˚F, yellow
REGULA
Specify:
HD regulator body
• Regulator size or capacity of steam required
• End connections (threaded, 150/300# flanged)
TOR BODY
MINIMUM OPERATING PRESSURES
Minimum Inlet Pressure:
15 PSIG (Standar
5 PSIG (Low Pr
Low Pressure Temperature Pilot must be used in conjunction with a Low Pressure Main Valve for applications where inlet steam pressure is below 15 PSIG. SPECIFY WHEN ORDERING.
d Main Valve)
essure Main Valve with
Low Pressure Temperature Pilot)
428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134
www.watsonmcdaniel.com
127
PILOTS
A”Pilot
Watson McDaniel reserves the
right to change the designs
and/or materials of its
products without notice.
©2010 Watson McDaniel Company
Air Pilot for HD Regulating Valves
Air Pilot
Max Inlet Pressure: 300 PSIG
Reduced Outlet Pressure Range: 3-200 PSIG
Minimum Inlet Pressures:
15 PSIG when used with standard main valve
5 PSIG when used with low pressure main valve
Note: Temperature Range: 0-350F when used with
REGULATING VALVES
PILOT-OPERATED
TYPICAL APPLICATIONS
The “A” Air Pilot is used with the HD Regulator to control steam pressure on steam mains and process equipment. The “A” Air Pilot can also be used in conjunction with the PTL or PTR pneumatic temperature controllers for controlling temperature in process applications. The principal advantage the “A” Air Pilot over standard spring loaded pilots is that pressure adjustments to the regulator can be made from a remote location. A regulator that is placed in a difficult to reach or inaccessible location can be adjusted by a remote control panel board placed in an accessible location.
HOW IT WORKS
When air pressure is applied to the upper chamber of the air pilot it exerts a downward force on the air pilot’s diaphragm. This force controls the outlet pressure of the steam through the regulating valve. The control process is similar to a spring loaded pressure pilot except that the air pressure takes the place of the spring. There are three separate models of air pilots that make up the complete range depending on the steam pressure that needs to be controlled and the control air pressure available. See Pressure Adjusting Ranges chart.
FEATURES
PTL & PTR temperature controllers
Pressure adjustments to the regulator can be done from a remote location using an air signal
Air-operated pilot ensures instant response and extremely accurate control
Full port strainer and blowdown valve on pilot adapter for
ultimate protection from dirt and scale
Controls pressure settings within ±1 PSIG
Controls Pressure & Temperature
MAXIMUM CONTROL AIR PRESSURE ON AIR PILOT IS 125 PSIG
PRESSURE ADJUSTING RANGES
Model
A1 3-125 PSIG 1:1 ratio of steam pressure
A4 3-200 PSIG 4:1 ratio of steam pressure
A6 20-200 PSIG 6:1 ratio of steam pressure
The larger Diaphragm area of the “A4” & “A6” Air Pilots allow the use of lower control air pressure to regulate higher pressure steam.
MATERIALS
Pilot Body & Cover Ductile Iron Gasket Grafoil Cover Screws Steel, GR5 Head & Seat Assembly Hardened SST (55 Rc)
Pressure
Ranges
Description
to control air pressure
to control air pressure
to control air pressure
Control Air Connection 1/4” NPT
B
DIMENSIONS –
Model A B
A1 5
A4 5
A6 5
128
428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134
inches
1
/4 5
1
/4 77/8
1
/4 91/2
Steam
Sensing Line
Connection
1/4” NPT
A
www.watsonmcdaniel.com
PILOTS
A”Pilot
Controls Pressure & Temperature
Air Pilot for HD Regulating Valves
REMOTE CONTROL PANEL BOARDS
Three different options of remote control panel boards can be used along with the "A" Air Pilots. Supply air is fed directly through the control panel board to the air pilot. You can choose one of the three options of control panel boards when using the air piloted regulators. Minimum 5 PSIG air supply pressure is required.
AIR SIGNAL
PL1
AIR SUPPLY
AIR SIGNAL
PL2
STEAM PRESSURE
AIR SUPPLY
AIR SIGNAL
PL1
The PL1 is made up of an air pressure regulator with adjustment knob and pressure gauge that measures the amount of air pressure going to the pilot (air signal). Steam pressure of the system is controlled by adjusting the air pressure regulator.
PL3
HOW TO ORDER
“A” AIR PILOT
Specify:
• Air Pilot A1, A4 or A6
• Remote Control Panel Board
PL1, PL2 or PL3
REGULA
Specify:
HD regulator body
• Regulator size or capacity and pressure range
• End connections (threaded, 150/300# flanged)
TOR BODY
of steam required
MINIMUM OPERATING PRESSURES
Minimum Inlet Pressure:
15 PSIG (Standar
5 PSIG (Low Pr
Minimum Differential Pressure:
10 PSI (Standar
3 PSI (Low Pr
d Main Valve)
essure Main Valve)
d Main Valve)
essure Main Valve)
REGULATING VALVES
REGULATING VALVES
PILOT-OPERATED
PL2
The PL2 is the same as the PL1 with the addition of an extra air pressure gauge for measuring the air supply pressure to the control panel board.
PL3
The PL3 is the same as the PL2 with the addition of a Steam Pressure Gauge for measuring steam pressure on the outlet side of the regulating valve.
Pressure Reducing Station Using HD Regulator with an Air Pilot
INLET
STEAM
AIR SIGNAL (control air)
BYPASS
AIR PILOT
HD
REGULATOR
HDA
(REGULATOR
with AIR PILOT)
PL2
FLOW
CONTROL AIR PRESSURE RANGE
A-Pilot Control Pressure:
AIR SUPPLY
SENSING LINE
SLOPED DOWN
FROM PILOT
OUTLET
STEAM
3-125 PSIG (depending on pilot selected and
desired outlet pressure)
DESCRIPTION OF OPERATION
The “A” Air Pilot is being used in conjunction with the PL2 Control Panel Board to regulate steam pressure. A small air regulator on the panel board can be adjusted to control the air pressure to the pilot. One gauge on the panel board measures air line pressure to the panel board and the other gauge shows the air pressure being sent to the pilot. Steam pressure at the outlet of the regulator is controlled by the air pressure signal to the pilot. Depending on the air pilot model chosen (A1, A4, A6), there will be a 1:1, 4:1, or 6:1 ratio of outlet steam pressure to air pressure.
STEAM TRAP
428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134
www.watsonmcdaniel.com
129
PILOTS
PTL & PTR Controller
Pneumatic Temperature Controller (used with Air Pilot)
Pneumatic Temperature Controller
Max Inlet Pressure: 300 PSIG
Watson McDaniel reserves the
right to change the designs
and/or materials of its
products without notice.
©2010 Watson McDaniel Company
Temperature Range: PTR: 0-300F
PTL: 50-350 F
Minimum Inlet Pressures:
REGULATING VALVES
PILOT-OPERATED
Minimum Inlet Pressure:
15 PSIG when used with standard main valve
5 PSIG when used with low pressure main valve
TYPICAL APPLICATIONS
The PTL and PTR Pneumatic Temperature Controllers operate over a wider temperature
range than our standard “T” temperature pilot. These temperature controllers also react quicker to temperature change which make them an excellent choice for instantaneous hot water applications.
HOW IT WORKS
The PTL and PTR Pneumatic Temperature Controllers are used in conjunction with an “A” Air Pilot to control the operation of the HD
Regulator. The PTL uses a bimetallic element to sense temperature and the PTR uses a hydraulically filled bulb with a 4-ft. capillary to sense temperature. The air supply is connected to the inlet of the controller and the air output signal is fed directly to an Air Pilot, which controls the opening and closing of the steam regulating valve.
FEATURES
Accurate and rapid response to temperature
changes Covers control temperature range of 0-350 ˚F
MINIMUM OPERATING PRESSURES
15 PSIG (Standar
5 PSIG (Low Pr
d Main Valve)
essure Main Valve)
PTL
(mounts directly on
tank or vessel)
PTR
(mounts remotely
with 4-ft. Capillary)
Model PTL PTR Temperature Adjustment Range Maximum Air Supply Pressure Sensing Bulb Bi-Metallic Hydraulic Fill
Max. Pressure 250 Max. Temperature 400˚F 350˚F Material Copper Copper Optional Material Stainless Steel Stainless Steel Capillary Length N/A 4-ft.
50 - 350 ˚F 0 - 300 ˚F
35 PSIG 35 PSIG
PSIG
250
PSIG
HOW TO ORDER
PTL & PTR PNEUMATIC TEMPERATURE CONTROLLER Specify: PTL or PTR controller model (air pilot required for operation)
AIR PILOT Specify: A1, A4 or A6 Air Pilot model (refer to Air Pilot section)
REGULA Specify: HD regulator body
TOR BODY
• Regulator size or capacity
• End connections (threaded, 150/300# flanged)
130
428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134
www.watsonmcdaniel.com
SERIES HDA-PTL
PNEUMATIC
TEMPERATURE
REGULATOR
STEAM INLET
BYPASS LINE
PILOTS
PTL & PTR Controller
Pneumatic Temperature Controller (used with Air Pilot)
DESCRIPTION OF OPERATION
The PTL Pneumatic Temperature Controller senses outlet water
temperature on a semi­instantaneous hot water heater. When the outlet water temperature falls below the set point, the PTL pneumatic temperature controller sends an air signal to the A1 Air Pilot which opens the regulator, allowing steam to heat the tank. When the water reaches the desired set temperature, the PTL pneumatic temperature controller shuts off the air signal to the A1 Air Pilot and the regulator closes, cutting off steam to the heater.
VACUUM
BREAKER
SEMI-INSTANTANEOUS
AIR VENT
HEATER
COLD WATER INLET
AIR SIGNAL LINE
HOT WATER OUTLET
AIR REGULATOR
AIR INLET
“PTL” CONTROLLER
REGULATING VALVES
PILOT-OPERATED
Model PTL (direct mounted)
11/
35/
2
8
3/4” NPT
Model PTR (remote mounted)
2-1/4
5
/
3
16
111/
STEAM
TRAP
WELL
111/
2
3/4” NPT
8
COPPER
WELL
111/
TEMPERATURE SET POINT ADJUSTMENT KNOB
7/8
1/8” NPT
27/
8
Units: inches
TEMPERATURE SET POINT ADJUSTMENT KNOB
13/32
8
23/
4
WITH RELAY
61/
2
STAINLESS STEEL
1
/
5
4
428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134
www.watsonmcdaniel.com
1/8” NPT
21/
8
131
PILOTS
TRP”Pilot
Temperature Pilot for HD Regulating Valves
Temperature Pilot
Max Inlet Pressure: 300 PSIG
Temperature Control Range: 20-250 F
Min Inlet Pressures: 15 PSIG standard main valve
5 PSIG low pressure main valve
TYPICAL APPLICATIONS
PILOT-OPERATED
The “TRP” Temperature Pilot is used with the HD Regulator to control temperature in various processes and systems. Some examples are: Oil heaters, Ovens, Process Heaters, Vats, Dryers
REGULATING VALVES
and Jacketed Kettles.
FEATURES
Ductile Iron pilot body
Stainless steel valve and seat
Standard capillary is copper with 316 stainless steel
armor in 10 feet length
OPTIONS
Additional Capillary Length: Available up to 25-ft. in
5-ft. increments.
Special Materials: Sensing bulb, wells, and capillary are
available in special corrosion resistant materials.
- 316 stainless steel capillary
- 316 stainless steel armor with standard capillary
- Kynar-covered capillary
Finned Bulb: Special finned sensing bulb for improved
temperature sensitivity when controlling air temperature in heating ducts
Thermowell or Separable Socket: Available in
stainless steel or copper
Temperature Sensing Dial: Indicates temperature of
process being controlled
DIMENSIONS –
Std. Bulb Bulb Bulb Body Height
Range Length Diameter C
˚F A B w/Dial w/o Dial D E 40-65° 12 65-85° 12
85-110° 12 110-135° 12 135-160° 12 160-190° 12 190-210° 12 210-245° 12 245-275° 12 275-310° 12 305-365° 12 365-415° 12 415-435° 12
1
1
1
1
1
1
1
1
1
1
1
1
1
inches
Thermowell or
Separable Socket
/4 1.0 111/4 1611/64 13 1.1 /4 1.0 111/4 1611/64 13 1.1 /4 1.0 111/4 1611/64 13 1.1 /4 1.0 111/4 1611/64 13 1.1 /4 1.0 111/4 1611/64 13 1.1 /4 1.0 111/4 1611/64 13 1.1 /4 1.0 111/4 1611/64 13 1.1 /4 1.0 111/4 1611/64 13 1.1 /4 1.0 111/4 1611/64 13 1.1 /4 1.0 111/4 1611/64 13 1.1 /4 1.0 111/4 1611/64 13 1.1 /4 1.0 111/4 1611/64 13 1.1 /4 1.0 111/4 1611/64 13 1.1
“TRP” TEMPERATURE PILOT
Specify:
• Temperature range from the chart or indicate the temperature
• The length of capillary required
REGULA
Specify:
HD regulator body
• Regulator size or capacity of steam required
• End connections (threaded, 150/300# flanged)
The “TRP” will control lower temperatures than the standard “T” Pilot
MATERIALS
Pilot Body Ductile Iron Valve and Seat Stainless steel
Support Bracket Aluminum Bulb & Capillary Copper (optional stainless steel) All Other Parts Brass
HOW TO ORDER
of the process you wish to control
TOR BODY
4” minimum
length
C
Watson McDaniel reserves the
right to change the designs
and/or materials of its
products without notice.
©2010 Watson McDaniel Company
THERMOWELL
1” NPT
Hub
A
B
D
1” NPT
E
132
428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134
www.watsonmcdaniel.com
PILOTS
Electric Pilot for On/Off Control of
Solenoid
Pilot
For Electrical On-Off Control
of Regulating Valves
Max Inlet Pressure: 250 PSIG
TYPICAL APPLICATIONS
Typically used for automatic operation, remote control, programmed cycling, sequential function interlocks with other equipment, and emergency shut-off in case of power failure.
HOW IT WORKS
The “S” Solenoid Pilot can be used in conjunction with Pressure, Temperature, or Air Pilots to electrically control on/off operation of the HD Regulator. When the solenoid pilot is used, the regulator can be turned on or off by electrically activating or de-activating the solenoid.
HD
S
Regulating Valves
Pilot
STANDARD SOLENOID PILOTS AVAILABLE
Steam Inlet Pressure 0-180 PSIG
180-250 PSIG
NEMA 1 – Standard
NEMA Ratings NEMA 4 – Waterproof (optional)
NEMA 7 – Explosion-proof (optional)
Voltage 110 Volts AC (standard)
24 Volts AC (optional) 220 Volts AC (optional) 240 Volts AC (optional)
REGULATING VALVES
REGULATING VALVES
PILOT-OPERATED
Normally Closed (nc) – Standard
The normally closed Solenoid Pilot remains closed in the non-activated state. The regulating valve will remain closed until an electrical signal is sent to the solenoid pilot. This is known as a fail-safe condition.
Normally Open (no) – Optional
The normally opened Solenoid Pilot remains open in the non-activated state. The regulating valve will function normally unless an electrical signal is used to shut-off the solenoid pilot.
FEATURES
Available normally opened (no) or normally closed (nc)
Full-port strainer and blow-down valve on pilot adapter to
eliminate failure caused by contaminated steam systems
OPTIONS
Normally open solenoid
NEMA Ratings: NEMA 4 and NEMA 7
Voltage: 24 VAC, 220 VAC, 240 VAC
MINIMUM OPERATING PRESSURES
Minimum Inlet Pressure:
15 PSIG (Standar
5 PSIG (Low Pr
Minimum Differential Pressure:
10 PSI (Standar
3 PSI (Low Pr
d Main Valve)
essure Main Valve)
d Main Valve)
essure Main Valve)
MATERIALS
Pilot Body & Cover Ductile Iron Gasket Grafoil Cover Screws Steel, GR5 Internals Stainless Steel
HOW TO ORDER
“S” SOLENOID PILOT
Specify: • Inlet Steam Pressure range:
0-180 PSIG or 180-250 PSIG
• NEMA rating: NEMA 1, NEMA 4 or NEMA 7 (if not specified NEMA 1 Standard will be supplied)
• Control Voltage: 24, 110, 220 or 240 VAC
REGULA Specify: HD regulator body
TOR BODY
• Regulator size or capacity of steam required
• End connections (threaded, 150/300# flanged)
428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134
www.watsonmcdaniel.com
133
PILOTS
DP”Pilot
Differential Pressure Pilot for HD Regulating Valves
Differential Pressure Pilot
Max Inlet Pressure: 300 PSIG
Reduced Outlet Pressure Range: 3-200 PSIG
Min Inlet Pressures: 15 PSIG standard main valve
5 PSIG low pressure main valve
DP-Pilot
PRESSURE-ADJUSTING SPRING RANGES
REGULATING VALVES
PILOT-OPERATED
“DP” Pressure Range Identifying Colors
TYPICAL APPLICATIONS
The “DP” Differential Pressure Pilot is used with the HD Regulator to maintain steam pressure at a balanced differential
pressure above another media source. This is typical on an oil burner where steam used for atomization is injected into the oil burner at a set pressure above the incoming oil supply. Therefore, as oil pressure fluctuates based on demand, the steam pressure will be maintained at a differential pressure above the oil pressure.
FEATURES
The “DP” Differential Pressure Pilot is used to maintain
downstream steam pressure to a set differential pressure above loading pressure
Accuracy to within ±2 PSIG
3 overlapping spring ranges to choose from
Pilot is installed using only four bolts
Full port strainer and blowdown valve on pilot adapter for
ultimate protection from dirt and scale
Solid floating diaphragm
Watson McDaniel's pilots can be used with other
manufacturers’ regulators
+
2 PSIG accuracy
3-25 PSIG yellow 20-100 PSIG blue 80-200 PSIG red
MATERIALS
Pilot Body & Cover Ductile Iron & Cast Steel Gasket Grafoil Diaphragm Phosphor Bronze Head & Seat Assembly Hardened SST (55 Rc)
HOW TO ORDER
“DP” DIFFERENTIAL PRESSURE PILOT
Specify: • Reduced pressure range – Example: “DP” Pilot at 3-25 PSIG, yellow
REGULA Specify: HD regulator body
TOR BODY
• Regulator size or capacity
• End connections (threaded, 150/300# flanged)
Watson McDaniel reserves the
right to change the designs
and/or materials of its
products without notice.
©2010 Watson McDaniel Company
OPTIONS
Solenoid pilot can be added for remote on/off control of
regulator
MINIMUM OPERATING PRESSURES
Minimum Inlet Pressure:
15 PSIG (Standar
5 PSIG (Low Pr
Minimum Differential Pressure:
10 PSI (Standar
3 PSI (Low Pr
134
428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134
d Main Valve)
essure Main Valve)
d Main Valve)
essure Main Valve)
9.27
Units: inches
www.watsonmcdaniel.com
5.00
PILOTS
Over Pressure Protection Methods
Using “P” and “BP” Pilots
Back Pressure Regulators for Boiler Overload Protection
In steam systems with several applications of varying importance, a back pressure regulator may be used to prevent overloading of the boiler by isolating non-essential loads from critical processes in the event steam demand exceeds boiler output. When steam demand is greater than the capacity the boiler can generate, pressure in the boiler will drop, possibly upsetting the control balance in the boiler resulting in the generation of wet steam. Using back pressure regulators on the non-essential application supply lines allows isolation of these applications at times of peak demand by shutting off steam flow to areas deemed non-essential. This ensures that boiler demand is not exceeded and steam flow is maintained to critical processes until demand subsides and the boiler is able to catch up.
STEAM TO ESSENTIAL SERVICES
SAFETY
VALVE
DRIP PAN ELBOW
REGULATING VALVES
PILOT-OPERATED
STEAM TO NON-ESSENTIAL SERVICES
BOILER STEAM SUPPLY
PILOT-OPERATED BACK PRESSURE REGULATOR
HEADER
PILOT-OPERATED PRESSURE REDUCING AND BACK PRESSURE
REGULATOR
FTT
TRAP
STEAM TO NON-ESSENTIAL SERVICES
Pressure Override Protection of Regulator Supply Lines
On multi-stage pressure reducing applications where a rise in control pressure due to failure of the final supply regulator could result in equipment damage and/or personnel injury, a secondary pressure pilot may be added to provide override protection of a steam supply line. During normal operation, the main pressure pilot on the 1st stage regulator provides intermediate pressure control while the additional “monitor” pilot senses final control pressure and remains open due to a slightly higher setting than the final control pressure setting. Should the 2nd stage regulator fail for any reason, increasing supply pressure will begin to close the monitor pressure pilot of the 1st stage regulator, thus overriding the main control pilot preventing final supply pressure from increasing. This overpressure protection can similarly be offered on single-stage reducing valves by protecting against failure of the main control pilot.
MAIN PRESSURE PILOT
INLET
1st Stage HD REGULATOR
428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134
www.watsonmcdaniel.com
PRESSURE
PILOT
(Monitor)
PRESSURE PILOT
2nd Stage HD REGULATOR
OUTLET
135
REGULATOR & PILOT
HDP
Pilot-Operated Pressure Regulating Valve
HD Regulating Valve
with “P”Pressure Pilot
Max Inlet Pressure: 300 PSIG
Reduced Outlet Pressure Range: 3-200 PSIG
Min Inlet Pressures:
Watson McDaniel reserves the
right to change the designs
and/or materials of its
products without notice.
©2010 Watson McDaniel Company
PILOT-OPERATED
REGULATING VALVES
15 PSIG
standard main valve
5 PSIG low pressure main valve
TYPICAL APPLICATIONS
The HD Regulator with the “P” Pressure Pilot is used for reducing steam pressure in piping mains and process applications. Pilot-operated regulators will maintain constant downstream pressure even when the inlet pressure to the regulator fluctuates or steam usage varies.
FEATURES
The “P” Pilot can maintain downstream pressure
to ±1 PSIG
Optional “P5” pilot can maintain pressure
to ±0.5 PSIG
Choices of three overlapping pressure ranges
Pressure adjusting spring can be changed with
regulator in line Pilot is easily installed using only four bolts
Full port strainer and blowdown valve on pilot
adapter for ultimate protection from dirt and scale
Watson McDaniel’s pilots can be used with other
manufacturers’ regulators
OPTIONS
Pressure and temperature pilots can be combined
on the same regulator
Solenoid pilot can be added for electrical on/off
control of the regulator Can be used with solenoid and temperature pilots
MINIMUM OPERATING PRESSURES
Minimum Inlet Pressure:
15 PSIG (Standar
5 PSIG (Low Pr
Minimum Differential Pressure:
10 PSI (Standar
3 PSI (Low Pr
d Main Valve)
essure Main Valve)
d Main Valve)
essure Main Valve)
PRESSURE-ADJUSTING SPRING RANGES “P”
Pressure Ranges Identifying Colors
3-25 PSIG yellow 20-100 PSIG blue 80-200 PSIG red
PRESSURE-ADJUSTING SPRING RANGES “P5”
1-10 PSIG yellow
10-25 PSIG blue
MATERIALS
Body Ductile Iron Cover Ductile Iron Gasket Grafoil Cover Screws Steel Pilot Adapter Ductile Iron/Cast Steel Screen Stainless Steel Tubing Copper Valve Seat Hardened SST (55 Rc) Valve Disc Hardened SST (55 Rc) Diaphragm Phosphor Bronze
136
428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134
www.watsonmcdaniel.com
REGULATOR & PILOT
HDP
Pilot-Operated Pressure Regulating Valve
DIMENSIONS HD-Series
inches / pounds
Face-To-Face Weight (lbs) Size NPT 150# 300# B C* D E** NPT FLG 1/2” 4 3/4” 4
1” 5 11/4 6 11/2 7
2” 7 21/2 9
3
/8
3
/8
3
1
/8
5
/2
1
/2
1
7
/4
6
/8
7
1
1
/2
8
/2
3
/8
10 9 11
3” 10 10
4” 11
6” 15
For P5 Pilot:
* For sizes 1/2” to 11/2” add 21/2” to “C” dimension;
For sizes 2” to 6” add 5” to “C” dimension.
** Add 11/2” to “E” dimension for all sizes.
7
1
/8 /8
12
16 14
1
5
/2
1
5
/2
1
66
3
98
/4
3
7
/8
3
/8
7
/8
1
/4
3
7
/4
8
/8
1
7
/2
10
/8
1
/8
11 11 11 11 11 11
11 11 12
7
/8
7
/8
7
/8
7
/8
7
/8
7
/8
7
/8
7
/8
7
/8
1
/2
1
6 6
8
8 10 11 13 14 19
3
/2
7
/4
1
3
/2
7
/4
3
77
3
3
7
3
1
3
3
/4
1
/4
8
/4
1
/4
8
/4
1
/8
8
/2
1
/4
8
/2
1
/4
9
/2
1
/4
10
3
/4
11
18 18 23 35 43 43 60 65 85
/2 /4
105 145 235 470
Standard P-Pilot = 5”
P5-Pilot = 8”
C
B
E
D
HOW TO ORDER
P or P5 PRESSURE PILOT
Specify: • Reduced pressure range (P5 Pilot requires a special adapter block on 3” & 4” valves)
REGULATOR BODY
Specify: HD regulator body
• Regulator size or capacity and pressures of steam required
• End connections (threaded, 150/300# flanged)
REGULATING VALVES
PILOT-OPERATED
Adjusting Spring
Pilot
Diaphragm
Pilot Valve
Main Valve
Inlet
Pressure
Adjusting Screw
PRESSURE PILOT
Downstream Pressure Sensing LIne
Bleed Orifice
HOW IT WORKS
The purpose of the pressure pilot is to control the operation of the pressure regulating valve. A pressure sensing line connects the pressure pilot to the downstream side of the regulator. The pressure in the sensing line is directed under the diaphragm in the pressure pilot. When the pressure in the system
Control Pressure Line
reaches the adjusting spring set point it pushes the diaphragm upwards against the force of the adjusting spring and closes the pilot valve. When the pilot valve is shut, steam can no longer pass through to the
Outlet
underside of the regulator diaphragm and the main valve closes. When the steam pressure falls below its set point, the pilot valve opens allowing steam
Diaphragm Orifice with Clean-out Wire
Main Valve Diaphragm
428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134
www.watsonmcdaniel.com
to lift the main valve diaphragm which opens up the regulating valve.
137
REGULATOR & PILOT
HDT
Pilot-Operated Temperature Regulating Valve
HD Regulating Valve with
Watson McDaniel reserves the
right to change the designs
and/or materials of its
products without notice.
©2010 Watson McDaniel Company
“T”
Temperature Pilot
Inlet Pressure Max: 300 PSIG
Temperature Control Range: 60–260 F
Min Inlet Pressures:
PILOT-OPERATED
REGULATING VALVES
15 PSIG
5 PSIG
Low Pressure Temperature Pilot must be used in conjunction with a low pressure main valve for applications where inlet steam pressure is less than 15 PSIG.
TYPICAL APPLICATIONS
The HD Regulator with the “T” Temperature Pilot is used for controlling temperature in various processes and systems, such as Oil Heaters, Ovens, Process Heaters, Vats, Dryers and Jacketed Kettles.
FEATURES
Temperature adjustment made simple and easy
by rotating an adjustment knob to the desired temperature setting
Thermostatic sensing bulb comes with 8-ft. or
15-ft. capillary; optional lengths up
Capillary is armor-protected to resist damage
Optional stainless steel sensing bulb and capillary
Overheat protection bellows is incorporated into
sensing bulb; 200˚F overheat protection up to 350˚F Can be used with Pressure Pilot for simultaneous
control of pressure and temperature
Hardened stainless steel trim on regulator for
extended service life
Full port strainer and blowdown valve on pilot
adapter for ultimate protection from dirt and scale
OPTIONS
Temperature Pilot can be combined with Pressure
and Solenoid pilots
Additional capillary lengths can be ordered in 5-ft.
increments; up to 25-ft. maximum length Wells* are available in 316 stainless steel
Longer wells can be supplied
Low pressure (under 15 PSIG) temperature pilot
Consult factory for other options
standard main valve with standard temperature pilot low pressure main valve with low pressure temp. pilot
SPECIFY WHEN ORDERING.
to 25-ft. max
TEMPERATURE-ADJUSTING RANGES
Temperature Ranges * Identifying Colors
60 - 120 °F (16 - 49 °C) yellow 100 - 160 °F (38 - 71 °C) black 120 - 180 °F (49 - 82 °C) blue 160 - 220 °F (71 - 104 °C) red 200 - 260 °F (93 - 127 °C) green
* Other ranges available; consult Factory.
MATERIALS
Body Ductile Iron Cover Ductile Iron Gasket Grafoil Cover Screws Steel Pilot Adapter Ductile Iron/Cast Steel Screen Stainless Steel Tubing Copper Valve Seat Hardened SST (55 Rc) Valve Disc Hardened SST (55 Rc) Diaphragm Phosphor Bronze
* Thermowells:
Wells isolate sensing bulb from the process liquid and are available in Brass or Stainless Steel. When placed on the side of a tank or vessel, the sensing bulb can be removed without having to drain the process fluid.
138
428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134
www.watsonmcdaniel.com
REGULATOR & PILOT
HDT
Pilot-Operated Temperature Regulating Valve
DIMENSIONS HD-Series
inches / pounds
Face-To-Face Weight (lbs) Size NPT 150# 300# B C D E NPT FLG 1/2” 4 3/4” 4
1” 5 11/4 6 11/2 7
2” 7 21/2 9
3
/8
3
/8
3
1
/8
5
/2
1
/2
1
7
/4
6
/8
1
1
/2
8
/2
3
/8
3” 10 10
4” 11
6” 15
7
/8
1
/8
7
10 9 9
12
16 14
1
5
/2
1
5
/2
1
6 6
3
98
/4
3
7
/8
3
/8
7
/8
1
/4
3
7
/4
8
/8
1
7
/2
10
/8
1
/8
1
1
9
/4
6
1
9
/4
6
1
9
/4
1
9
/4
8
1
9
/4
8
1
9
/4
10
1
/4
11
1
9
/4
13
1
9
/4
14
3
9
/4
19
1
/2
6
/2
1
1
/2
6
/2
1
78
3
3
7
3
1
3
3
/4
1
/4
7
/4
1
/4
7
/4
1
/8
7
/2
3
/4
7
/4
1
/4
8
/2
1
/4
9
/2
3
/4
10
/4
18 18 23 35 43 43 60 65 85
HOW TO ORDER
“T” TEMPERATURE PILOT
Specify:
• Temperature range from the chart or indicate the set temperature of the process you wish to control
• The length of capillary required. 8-ft. or 15-ft. standard; Maximum length: 25-ft. in 5-ft. increments
• Bulb type needed: T, TU, TUBW, TUSW, TBW & TSW
REGULA
TOR BODY
Specify:
HD regulator body
• Regulator size or capacity
• End connections (threaded, 150/300# flanged)
MINIMUM OPERATING PRESSURES
Minimum Inlet Pressure:
15 PSIG (Standar
5 PSIG (Low Pr
Low Pressure Temperature Pilot must be used in conjunction with a
Low Pressure Main Valve for applications where inlet steam pressure is less than 15 PSIG. SPECIFY WHEN ORDERING.
d Main Valve with
Standard Temperature Pilot)
essure Main Valve with
Low Pressure Temperature Pilot)
105 145 235 470
C
B
E
D
HOW IT WORKS
The temperature pilot controls the operation of the temperature regulating valve. The temperature sensing bulb, which is filled with a temperature sensitive liquid, is placed in the process fluid that is being heated. When the temperature of the process fluid reaches its set point, the bellows expands and closes off the pilot valve. When the pilot valve is shut, steam can no longer pass thru to the underside of the regulator diaphragm, and the main valve closes. When the process fluid cools below the set temperature, the main valve reopens.
Temperature
Adjustment
Knob
Bellows
Pilot Valve
Inlet
Main Valve
TEMPERATURE PILOT
Temperature Sensing Bulb
Control Pressure Line
Bleed Orifice
Outlet
Diaphragm Orifice with Clean-out Wire
REGULATING VALVES
REGULATING VALVES
PILOT-OPERATED
Main Valve Diaphragm
428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134
www.watsonmcdaniel.com
139
REGULATOR & PILOT
HDA
Air-Operated Pilot Regulating Valve
HD Regulating Valve
with “A”Air Pilot
Max Inlet Pressure: 300 PSIG
Reduced Outlet Pressure Range: 3-200 PSIG
Min Inlet Pressures:
Watson McDaniel reserves the
right to change the designs
and/or materials of its
products without notice.
©2010 Watson McDaniel Company
PILOT-OPERATED
REGULATING VALVES
15 PSIG
standard main valve
5 PSIG low pressure main valve
Note: Temperature Range: 0-350F when used with
PTL & PTR temperature controllers
TYPICAL APPLICATIONS
The HD Regulator with the “A” Air Pilot is used for reducing steam pressure on steam mains and process equipment. The “A” Air Pilot can also be used in conjunction with the PTL and PTR Pneumatic Temperature Controllers for controlling temperature in process applications. The principal advantage of the “A” Air Pilot over standard spring-loaded pilots is that pressure adjustments to the regulator can be made from a remote location. A regulator placed in a difficult to reach or inaccessible location can be adjusted by a remote control panel board placed in an accessible location.
FEATURES
Air Pilot can be used with PTL or PTR Pneumatic
Temperature Controller Pressure adjustments of the regulator can be done
from a remote location Air-operated pilot insures instant response and
very accurate control
Full port strainer and blowdown valve on pilot
adapter for ultimate protection from dirt and scale
Controls pressure settings within ±1 PSIG
OPTIONS
Solenoid Pilot (S-Pilot) can be added for
Electrical On/Off Operation of the regulator
MAXIMUM CONTROL AIR PRESSURE ON AIR PILOT IS 125 PSIG
PRESSURE-ADJUSTING RANGES
Model Pressure Description
A1 3-125 PSIG 1:1 ratio of steam pressure to control air pressure
A4 3-200 PSIG 4:1 ratio of steam pressure to control air pressure
A6 20-200 PSIG 6:1 ratio of steam pressure to control air pressure
Ranges
Example:
With the A1 air pilot, 10 PSIG of air pressure maintains 10 PSIG of steam pressure
Example:
With the A4 air pilot, 10 PSIG of air pressure maintains 40 PSIG of steam pressure
Example:
With the A6 air pilot, 10 PSIG of air pressure maintains 60 PSIG of steam pressure
MINIMUM OPERATING PRESSURES
Minimum Inlet Pressure:
15 PSIG (Standar
5 PSIG (Low Pr
Minimum Differential Pressure:
10 PSI (Standar
3 PSI (Low Pr
d Main Valve)
essure Main Valve)
d Main Valve)
essure Main Valve)
140
CONTROL AIR PRESSURE RANGE
A-Pilot Control Pressure:
3-125 PSIG (depending on pilot selected and
desired outlet pressure)
428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134
www.watsonmcdaniel.com
REGULATOR & PILOT
HDA
Air-Operated Pilot Regulating Valve
DIMENSIONS HD-Series
inches / pounds
Face-To-Face Weight (lbs) Size NPT 150# 300# B C* D E** NPT FLG 1/2” 4 3/4” 4
1” 5 11/4 6 11/2 7
2” 7 21/2 9
3
/8
3
/8
3
1
/8
5
/2
1
/2
1
7
/4
6
/8
7
1
1
/2
8
/2
3
/8
10 9 7
3” 10 10
4” 11
6” 15
* Add 21/2” to “C” dimension for A4 or A6 Air Pilots on 2” thru 4” valves.
1
** Add 1
/2” to “E” dimension for A4, and 21/4”” for A6.
7
1
/8 /8
12
16 14
1
5
/2
1
5
/2
1
66
3
98
/4
3
7
/8
3
/8
7
/8
1
/4
3
7
/4
8
/8
1
7
/2
10
/8
1
/8
1
1
7
/2
6
1
7
/2
6
1
7
/2
1
7
/2
8
1
7
/2
8
1
7
/2
10
1
/2
11
1
7
/2
13
1
7
/2
14
1
8
/4
19
3
/2
7
/4
1
3
/2
7
/4
3
77
3
3
7
3
1
3
3
/4
3
/4
8
/8
3
/4
8
/8
3
/8
8
/4
3
/4
8
/4
1
/4
9
/2
1
/4
10
/2
3
/4
11
/4
18 18 23 35 43 43 60 65 85
MATERIALS
Body Ductile Iron Cover Ductile Iron Gasket Grafoil Cover Screws Steel Pilot Adapter Ductile Iron/Cast Steel Screen Stainless Steel Tubing Copper Valve Seat Hardened SST (55 Rc) Valve Disc Hardened SST (55 Rc) Diaphragm Phosphor Bronze
105 145 235 470
C
B
E
D
HOW IT WORKS
When air pressure is applied to the upper chamber of the air pilot it exerts a downward force on the air pilot’s diaphragm. The lower chamber of the air pilot is connected to the outlet side of the regulator using a sensing line. The purpose of the sensing line is to sense the pressure on the outlet side of the regulator. When the intended set pressure is reached, the pilot valve closes which then closes off the flow path of steam to the underside of the diaphragm chamber in the regulator body. The regulator modulates maintaining the desired downstream pressure regardless of the amount of steam being used.
REGULATING VALVES
PILOT-OPERATED
HOW TO ORDER
“A” AIR PILOT
Specify: • Air Pilot A1, A4 or A6
• Remote Control Panel Board: PL1, PL2 or PL3
REGULA Specify: HD regulator body
TOR BODY
• Regulator size or capacity and pressures of steam required
• End connections (threaded, 150/300# flanged)
428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134
www.watsonmcdaniel.com
Air Control
Line
Pilot
Diaphragm
Pilot Valve
Main Valve
Inlet
AIR PILOT
Downstream Pressure Sensing LIne
Control Pressure Line
Bleed Orifice
Outlet
Diaphragm Orifice with Clean-out Wire
Main Valve Diaphragm
141
REGULATOR & PILOT
Watson McDaniel reserves the
right to change the designs
and/or materials of its
products without notice.
HDPT
©2010 Watson McDaniel Company
Pilot-Operated Pressure & Temperature Regulating Valve
HD Regulating Valve
with
“T”
Temperature Pilots
“P”
Pressure &
Max Inlet Pressure: 300 PSIG
Reduced Outlet Pressure Range: 3-200 PSIG
REGULATING VALVES
PILOT-OPERATED
Temperature Control Range: 60-260 F
Min Inlet Pressures:
15 PSIG
standard main valve with standard temperature pilot
5 PSIG low pressure main valve with low pressure temp. pilot
Low Pressure Temperature Pilot must be used in conjunction with a low pressure main valve for applications where inlet steam pressure is less than 15 PSIG.
SPECIFY WHEN ORDERING
TYPICAL APPLICATIONS
The HD Regulator with both the “P” Pressure Pilot and “T” Temperature Pilot is used to simultaneously control
both pressure and temperature in process applications.
Using both the temperature and pressure pilot on the same regulator eliminates the need for two separate regulators to control temperature and pressure.
FEATURES
Pressure and temperature pilot combination
eliminates the need for two separate regulators
Choice of three overlapping pressure ranges
Pilot is installed using only four bolts
Full port strainer and blowdown valve on pilot
adapter for ultimate protection from dirt and scale
Watson McDaniel's pilots can be used with other
manufacturers’ valves
OPTIONS
Solenoid Pilot can be added for electrical On/Off
control of the regulator
* Other ranges available; consult Factory.
PRESSURE-ADJUSTING SPRING RANGES
TEMPERATURE-ADJUSTING RANGES
Temperature Ranges * Identifying Colors
60 - 120 °F (16 - 49 °C) yellow 100 - 160 °F (38 - 71 °C) black 120 - 180 °F (49 - 82 °C) blue
160 - 220 °F (71 - 104 °C) red 200 - 260 °F (93 - 127 °C) green
Pressure Ranges Identifying Colors
3-25 PSIG yellow 20-100 PSIG blue 80-200 PSIG red
MINIMUM OPERATING PRESSURES
Minimum Inlet Pressure:
15 PSIG (Standar
5 PSIG (Low Pr
Minimum Differential Pressure:
10 PSI (Standar
3 PSI (Low Pr
d Main Valve with
Standard Temperature Pilot)
essure Main Valve with
Low Pressure Temperature Pilot)
d Main Valve)
essure Main Valve)
142
428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134
www.watsonmcdaniel.com
REGULATOR & PILOT
HDPT
Pilot-Operated Pressure & Temperature Regulating Valve
DIMENSIONS HD-Series
inches / pounds
Face-To-Face Weight (lbs) Size NPT 150# 300# B C D E NPT FLG 1/2” 4 3/4” 4
1” 5 11/4 6 11/2 7
2” 7 21/2 9
3
/8
3
/8
3
1
/8
5
/2
1
/2
1
7
/4
6
/8
1
1
/2
8
/2
3
/8
3” 10 10
4” 11
6” 15
7
/8
1
/8
7
10 9 14
12
16 14
1
5
/2
1
5
/2
1
66
3
98
/4
3
7
/8
3
/8
7
/8
1
/4
3
7
/4
8
/8
1
7
/2
10
/8
1
/8
1
14
/2
1
14
/2
1
14
/2
1
14
/2
1
14
/2
1
14
/2
1
/2
1
14
/2
1
14
/2
15 19
1
6
/2
10
1
6
/2
10
710
3
8
/4
10
3
8
/4
10
7
10
/8
11
3
11
/4
11
1
13
/4
12 145
3
14
/4
13 235
3
/4
14
1
/4
1
/4
1
/4
3
/4
3
/4
1
/4
1
/4
1
/4
18 18 23 35 43 43 60 65 85
MATERIALS
Body Ductile Iron Cover Ductile Iron Gasket Grafoil Cover Screws Steel Pilot Adapter Ductile Iron/Cast Steel Screen Stainless Steel Tubing Copper Valve Seat Hardened SST (55 Rc) Valve Disc Hardened SST (55 Rc) Diaphragm Phosphor Bronze
HOW TO ORDER
“T” TEMPERATURE PILOT
Specify: • Temperature range from the chart or indicate the set
temperature of the process you wish to control
• The length of capillary required; 8-ft. is standard
• Bulb type needed: T, TU, TUBW, TUSW, TBW & TSW
“P” PRESSURE PILOT
Specify: • Pressure range from the chart
105
470
C
B
E
D
HOW IT WORKS
A pressure pilot and temperature pilot can be used together to control the operation of the regulator. The pressure pilot limits the outlet pressure of the regulator when the temperature pilot calls for steam. The temperature pilot senses the temperature of the process that is being controlled and opens or closes the regulator accordingly. Using a pressure­temperature pilot combination eliminates having to use two separate valves.
Temperature Sensing Bulb
TEMPERATURE
PILOT
Temperature
Pilot Valve
Inlet
Temperature Adjustment Knob
PRESSURE
PILOT
Pressure Adjusting Screw
Pressure Pilot Diaphragm
Pilot Valve
Bleed Orifice
Outlet
REGULATING VALVES
PILOT-OPERATED
REGULA
TOR BODY
Specify: HD regulator body
• Regulator size or capacity and pressures of steam required
• End connections (threaded, 150/300# flanged)
428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134
www.watsonmcdaniel.com
Main Valve
Main Valve Diaphragm
Control Pressure Line
Diaphragm Orifice with Clean-out Wire
143
REGULATORS
HSP Series
Pilot-Operated Pressure Regulating Valve
Model HSP Series Sizes 1”, 11/2”, 2”, 3”, 4” Connections 150#/300# Flange Body Material Cast Steel PMO Max. Operating Pressure 450 PSIG
TMO Max. Operating Temperature 650˚F
PMA Max. Allowable Pressure 550 PSIG @ 650˚F
TMA
PILOT-OPERATED
REGULATING VALVES
Max. Allowable Temperature 650˚F @ 550 PSIG
PRESSURE-ADJUSTING SPRING RANGES
Pressure Ranges Identifying Colors
10-40 PSIG yellow 25-100 PSIG blue 75-300 PSIG red
CAST STEEL
Watson McDaniel reserves the
right to change the designs
and/or materials of its
products without notice.
©2010 Watson McDaniel Company
TYPICAL APPLICATIONS
The HSP-Series Main Valve with integral Pressure Pilot reduces steam pressure in steam system piping mains and process applications. This pilot-operated regulator is specifically used in applications where the properties and benefits of Cast Steel are desired and/or specified. Using steel as the material of construction for the main valve body extends the temperature ranges of the regulator. A unique two-bolt pilot adapter design and field-reversible tubing offer even greater versatility to this type of regulator, further reducing maintenance downtime. These valves share the same design and proven reliability of the Watson McDaniel HD-Series Regulators, providing extremely accurate control of downstream system pressure even when inlet pressure to the regulator fluctuates or steam usage varies.
FEATURES
Cast Steel body for higher pressure and temperature ratings
New, convenient bolt-on pilot design simplifies installation
New diaphragm design improves performance and
extends life
Hardened stainless steel trim for extended life
Optional Stellite trim available
Full port strainer and blowdown valve on pilot adapter
for ultimate protection from dirt and scale Maintains downstream pressure+1.0 PSIG
Choice of three overlapping spring ranges
Pre-mounted pilot & tubing simplifies installation
LOTS
CONTROL PILOTS
Pilot Mounting
Standard pilot mounting is on the right side of the regulator when looking into the outlet port (see diagram on opposite page which is right mounted). For opposite mounting, please specify when ordering. Pilot mounting on HSP regulators are field reversible.
Pressure
The spring-adjusted Pilot is used for general purpose pressure reducing applications.
MATERIALS
Body ASTM A-216 GR WCB Cover ASTM A-216 GR WCB Diaphragm Cover ASTM A-216 GR WCB Pilot ASTM A-216 GR WCB Gaskets Garlock 3400/grafoil SLS Seat 420F SS
(optional Stellite seat, consult factory)
Disc 420F SS Diaphragm 300 SS Mfg. Bolts SA-193 GR B7 Spring 302 SS Stem 416 SS
144
428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134
www.watsonmcdaniel.com
REGULATORS
HSP Series CAST STEEL
Pilot-Operated Pressure Regulating Valve
DIMENSIONS HSP Series
(A) Face-To-Face Weight (lbs)
Size NPT 150# 300# B C D NPT 150# 300#
1” x5
11/2 x 6
2” x 8 3” x1010 4” x11
1
/2
7
/8
7
1
/2
7
/8
12
1
66
3
98
/4
3
/8
7
/8
1
/4
3
7
/4
8
/8
1
7
/2
10
/8
inches / pounds
1
3
/2
7 x 40 45
7
4 5 6 7
3
/8
8
/4
3
3
1
7
/8
10
/8
1
/4
13
/4
3
/2
14
/4
x 55 60 x 75 85 x 130 145 x 215 235
MINIMUM OPERATING PRESSURES
Minimum Inlet Pressure:
15 PSIG (standard Main Valve) 5 PSIG (low pressure Main Valve)
Minimum Differential Pressure:
10 PSIG (standard Main Valve) 3 PSIG (low pressure Main Valve)
HOW TO ORDER
REGULATOR BODY
Specify: • HSP regulator body
• Regulator size or capacity of steam required
• End connections (150#/300# flanged)
PILOT REQUIRED TO OPERA
• Pressure Pilot (Specify Range)
Specify: 10-40 PSIG - Yellow
25-100 PSIG - Blue 75-300 PSIG - Red
Example: 2” HSP, 150# FLG, 10-40 PSIG (yellow)
TE THIS VALVE
REGULATING VALVES
PILOT-OPERATED
FLOW
A
OUT
B
C
D
428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134
www.watsonmcdaniel.com
Standard pilot mounting is on the right side of the regulator when looking into the outlet port (as shown). Pilot mounting on HD regulators are field reversible.
145
NOISE ATTENUATORS
Series-A
for Pressure Regulating Valves
Noise Attenuation Equipment is used to reduce unwanted or excessive noise that
Series-A ORIFICE PLATE
Noise Reduction Capability: 5-10 dBA
REGULATING VALVES
PILOT-OPERATED
ORIFICE PLATE
commonly occurs in pressure reducing stations.
Watson McDaniel reserves the
Watson McDaniel reserves the
right to change the designs
right to change the designs
and/or materials of its
and/or materials of its
products without notice.
products without notice.
©2010 Watson McDaniel Company
©2002 Watson McDaniel Company
HOW IT WORKS
The Series-A Orifice Plate with its drilled orifice pattern is installed after the pressure regulating valve to smooth out turbulence caused by the pressure drop across the regulator. Noise reduction levels of 5-10 dBA can typically be achieved.
INSTALLATION
The Series-A Orifice Plate is installed between ANSI flanges immediately after the regulator. If the regulator is a flanged unit, the orifice plate is placed at the flange outlet connection.
Series-A Orifice Plate
Series-A Typical Hook-up
Sensing Line
For Regulator
FLOW
Pressure
Reducing
Valve
SERIES-A
ORIFICE
PLATE
Series A Dimensions
Orifice Plate installed
between flanges
FLOW
.75
Series-A DIMENSION (A) –
Pipe Size 125# Flange 250# Flange
2” 64
21/2 74
3” 71/2 511/16 4” 96 6” 11 911/16
Note: Other sizes available. Consult factory.
inches
3
/16
15
/16
15
/16
A DIa.
146
428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134
www.watsonmcdaniel.com
NOISE ATTENUATORS
ACOUSTIC SILENCER
Noise Attenuation Equipment is used to reduce unwanted or excessive noise that
commonly occurs in pressure reducing stations.
Series-H ACOUSTIC SILENCER
Noise Reduction Capability: 20-30 dBA
Series-H Acoustic Silencer
Series-H
for Pressure Regulating Valves
Series-H Dimensions
BA1
Inlet
C
A
REGULATING VALVES
PILOT-OPERATED
HOW IT WORKS
The Series-H Acoustic Silencer incorporates a Dual Diffuser tube design. The inner tube has a drilled orifice pattern and the outer tube contains an integral layer of sound absorbing insulation. Noise reduction levels of 20-30 dBA can typically be achieved.
INSTALLATION
The Series-H Diffuser Tube should be installed immediately downstream of the regulator, as shown below.
Series-H Typical Hook-up
Gate
Valve
Separator
FLOW
To Trap
Strainer
PRV
Series-H DIMENSIONS –
Model A1 A B C
LCV-8 4 8 14 57 145 LCV-10 6 10 16 71 210 LCV-12 6 12 18 81 295
Note: Other sizes available. Consult factory.
Pressure
Sensing Line
SERIES-H
ACOUSTIC
SILENCER
Gate
Valve
inches
Weight
(lbs)
428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134
www.watsonmcdaniel.com
147
NOISE ATTENUATORS
Series-S
for Pressure Regulating Valves
Series-S ACOUSTIC DIFFUSER
Noise Reduction Capability: 10-15 dBA
REGULATING VALVES
PILOT-OPERATED
Series-S Acoustic Diffuser
ACOUSTIC DIFFUSER
Watson McDaniel reserves the
right to change the designs
and/or materials of its
products without notice.
©2010 Watson McDaniel Company
HOW IT WORKS
The Series-S Acoustic Diffuser incorporates a single tube with a drilled orifice pattern which reduces downstream turbulence. Noise reduction levels of 10-15 dBA can typically be achieved.
INSTALLATION
The Series-S Diffuser Tube should be installed immediately downstream of the regulator, as shown below.
Series-S Typical Hook-up
Gate
Valve
Separator
FLOW
Strainer
PRV
ACOUSTIC
To Trap
Pressure
Sensing Line
SERIES-S
DIFFUSER
Gate Valve
Model Selection Chart for Series-S Diffuser
Steam Capacity (lbs/hr)
1000 S-3 S-3 S-3 S-3 S-3 S-3 S-3 S-3 S-3 S-3 S-3 S-3 S-3 S-3 S-3 S-3 1500 S-3 S-3 S-3 S-3 S-3 S-3 S-3 S-3 S-3 S-3 S-3 S-3 S-3 S-3 S-3 S-3 2000 S-4 S-4 S-4 S-4 S-4 S-4 S-4 S-4 S-4 S-4 S-4 S-4 S-4 S-4 S-4 S-4 3000 S-4 S-4 S-4 S-4 S-4 S-5 S-5 S-5 S-5 S-5 S-5 S-5 S-5 S-5 S-5 S-5 4000 S-5 S-5 S-5 S-5 S-5 S-5 S-5 S-5 S-5 S-5 S-5 S-5 S-5 S-5 S-5 S-5 6000 S-6 S-6 S-6 S-6 S-6 S-6 S-6 S-6 S-6 S-6 S-6 S-6 S-6 S-6 S-6 S-6 8000 S-8 S-8 S-8 S-8 S-8 S-8 S-8 S-8 S-8 S-8 S-8 S-8 S-8 S-8 S-8 S-8
10000 S-8 S-8 S-8 S-8 S-8 S-8 S-8 S-8 S-8 S-8 S-8 S-8 S-8 S-8 S-8 S-8
Note: For higher capacity models, S-10 & S-12, consult factory.
15 20 25 30 40 50 60 75 90 100 125 150 175 200 225 250
Valve Inlet Pressure
(PSIG)
148
428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134
www.watsonmcdaniel.com
NOISE ATTENUATORS
ACOUSTIC DIFFUSER
for Pressure Regulating Valves
Series-S Dimensions –
Inlet (A) Outlet NPT x Weld Dimensions
Model
S-3
S-4 11/4 4 61/2 131/2 41/2
S-5
S-6 268145
S-8 21/2 21/2 8 10 17 85/8
S-10 3 3 12 12 14 123/4
S-12
NPT FLG FLG/BW B C D
3/4 2 5
125
3/4 4 61/2 131/2 41/2
146
11/2 4 61/2 131/2 41/2
246
3/4 4 61/2 161/2 41/2
146
1
1
/4 46
11/2 46
246 21/2 21/2 46 11/4 68145 11/2 68145
21/2 21/2 68145
3368145 11/2 8 10 17 85/8
2 8 10 17 85/8
3 3 8 10 17 85/8
4 4 8 10 17 85/8
212121412 21/2 21/2 12 12 14 123/4
4 4 12 12 14 123/4
6 6 12 12 14 123/4 21/2 21/2 12 12 21 123/4
3 3 12 12 21 12
4 4 12 12 21 123/4
6 6 12 12 21 123/4
inches
1
/2 131/2 23/8
1
/2 131/2 23/8
1
/2 131/2 41/2
1
/2 131/2 41/2
1
/2 161/2 41/2
1
/2 161/2 41/2
1
/2 161/2 41/2
1
/2 161/2 41/2
1
/2 161/2 41/2
5
/8
5
/8
5
/8
5
/8
5
/8
3
/4
3
/4
Series-S
NPT x Weld
C
B
A
NPT
Flanged x Weld
A
Flanged
NPT x Flanged
A
NPT
PILOT-OPERATED
REGULATING VALVES
D
Notes: 1)150# & 300# flanges available.
2) Other sizes available; consult factory.
428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134
www.watsonmcdaniel.com
Flanged x Flanged
A
Flanged
149
REGULATORS
HD & HSP Series
Watson McDaniel reserves the
right to change the designs
and/or materials of its
products without notice.
©2010 Watson McDaniel Company
Full Port
CAPACITIES –
Inlet
Pressure
(PSIG)
REGULATING VALVES
PILOT-OPERATED
100 60 700 1200 2000 2700 3800 6700 10000 12900 20500 43800
125 75 825 1475 2400 3300 4600 8200 12200 15700 25000 53500
150 100 925 1600 2700 3600 5100 9000 13400 17400 27700 59000
175 125 1000 1800 2900 4000 5600 9900 14700 18900 30100 64300
200 125 1300 2300 3700 5100 7100 12600 18700 24100 38400 81900
225 150 1450 2500 4200 5700 8000 14100 21000 27200 43300 92300
250 150 1650 2900 4700 6500 9100 16000 23800 30800 49000 104600
300 175 1945 3425 5625 7670 10740 18925 28130 36320 57800 123270
Note: For inlet pressures in shaded area, use low pressure main valve and low pressure temperature pilot.
Regulating Valves – Capacities
Steam (lbs/hr)
Outlet
Pressure
1/2" 3/4" 1" 1
1
/4"11/2"2" 2
1
/2"3" 4" 6"
(PSIG)
CvFactors
5 0 85 150 250 350 500 800 1200 1600 2600 5500
2 80 140 230 310 440 770 1100 1500 2400 5100 0 115 200 325 450 600 1100 1650 2100 3600 7800
7 2 105 180 300 400 575 1000 1500 2000 3100 6700
3 90 160 275 375 525 900 1300 1800 2800 6000 0 150 260 425 575 850 1500 2200 2800 4600 9900
10 2 140 240 400 550 800 1400 2100 2700 4300 9100
5 100 175 300 400 600 1000 1600 2000 3200 6900 0 160 280 475 600 900 1600 2400 3100 4900 10300
12 4 140 240 400 550 800 1400 2100 2700 4300 9100
7 125 200 375 500 700 1200 1900 2400 3800 8200
0-3 190 325 550 750 1000 1800 2700 3500 5600 12000
15 5 175 300 500 700 900 1700 2500 3200 5200 11100
8 140 250 400 500 800 1300 2000 2600 4200 8900
0-5 210 375 625 850 1200 2100 3100 4000 6400 13700
20 10 190 325 550 750 1000 1800 2700 3500 5600 12000
12 170 300 500 675 950 1600 2500 3200 5100 10800
0-7 250 450 775 1050 1500 2600 3800 5000 7900 16900
25 10 225 425 700 975 1300 2400 3600 4600 7300 15600
15 200 350 600 800 1100 2000 3000 3900 6200 13200
0-12 275 500 800 1100 1500 2700 4100 5200 8300 17800
30 15 250 450 750 1000 1400 2500 3800 4900 7800 16600
20 225 375 650 850 1200 2100 3200 4100 6500 14000
0-18 350 600 1000 1350 1900 3300 5000 6400 10300 21900
40 25 300 500 850 1150 1600 2800 4200 5400 8700 18500
30 250 425 700 1000 1400 2500 3700 4700 7600 16100
0-20 400 700 1200 1650 2300 4100 6000 7800 12400 26500
50 30 350 650 1100 1500 2000 3600 5400 6900 11000 23600
40 275 500 800 1100 1500 2700 4100 5200 8300 17800
0-30 475 850 1350 1900 2600 4600 6900 8900 14200 30300
60 35 425 775 1250 1700 2400 4300 6400 8200 13100 27900
50 300 525 850 1200 1600 2900 4300 5600 8900 19000
0-35 575 1000 1650 2300 3200 5600 8300 10800 17200 36600
75 50 475 825 1350 1900 2600 4600 6900 8900 14100 30100
60 400 700 1150 1600 2200 3900 5800 7400 11800 25200
0-45 675 1200 1950 2700 3700 6600 9800 12700 20200 43100
90 60 575 1000 1700 2300 3200 5700 8500 10900 17400 37100
75 425 750 1200 1700 2300 4100 6100 7900 12600 27000
0-50 750 1300 2100 3000 4100 7300 10800 14000 22200 47500
80 500 875 1400 1900 2700 4800 7100 9200 14700 31300
0-60 925 1650 2700 3700 5200 9100 14000 17500 28000 59500
100 625 1100 1800 2500 3500 6200 9200 11900 19000 40400
0-75 1100 1900 3100 4300 6000 10600 15800 20400 32400 69100
125 650 1150 1900 2600 3600 6400 9500 12300 19600 41900
0-85 1275 2250 3700 5000 7100 12500 18600 24000 38200 81400
150 750 1300 2100 2900 4100 7300 10800 14000 22200 47500
0-100 1450 2500 4200 5700 8000 14100 21000 27100 43100 92000
150 1075 1900 3100 4300 6000 10600 15700 20300 32300 68900
0-120 1575 2800 4600 6200 8700 15400 22900 29500 47000 100200
175 1350 2400 3900 5300 7400 13100 19500 25200 40100 85500
0-130 1750 3100 5100 6900 9700 17100 25500 32900 53400 111800
200 1200 2100 3500 4800 6700 11900 17600 22800 36200 77300
0-160 2045 3605 5920 8075 11310 19220 29610 38230 60840 129750
200 1780 3140 5155 7030 9840 17340 25780 33275 52960 112950
3.8 6.7 11 15 21 37 55 71 113 241
FULL PORT
150
REGULATORS
HD & HSP Series
Reduced Port Regulating Valves
CAPACITIES –
Inlet
Pressure
(PSIG)
CvFactors
5 0 15 35 59 82 140 197 272 438 777 1712
7 2 20 46 79 110 187 265 365 587 1042 2296
10 2 28 68 115 160 274 387 533 858 1523 3354
12 4 33 78 133 185 316 446 615 990 1758 3873
15 5 41 98 166 232 395 558 769 1238 2198 4841
20 10 51 120 204 284 483 684 942 1517 2692 5929
25 10 67 158 269 375 640 905 1246 2006 3561 7843
30 15 76 180 305 426 726 1025 1413 2275 4037 8892
40 25 99 199 367 511 872 1232 1698 2734 4852 10688
50 30 118 277 470 655 1117 1579 2175 3502 6216 13692
60 35 143 338 573 798 1361 1924 2651 4268 7573 16682
75 50 164 387 657 916 1561 2207 3040 4895 8687 19135
90 60 197 465 789 1100 1874 2648 3649 5874 10425 22962
100 60 235 554 940 1310 2234 3158 4351 7006 12432 27384
125 75 294 693 1176 1638 2793 3948 5439 8757 15540 34230
150 100 329 775 1315 1831 3123 4414 6081 9791 17374 38270
175 125 360 849 1440 2006 3421 4835 6661 10725 19032 41923
200 125 459 1082 1836 2557 4360 6164 8492 13672 24262 53442
225 150 493 1162 1972 2747 4684 6621 9121 14686 26061 57405
250 150 588 1386 2352 3276 5586 7896 10878 17514 31080 68460
300 175 715 1690 2865 3990 6800 9615 13250 21330 37850 83370
Note: For inlet pressures in shaded area, use low pressure main valve and low pressure temperature pilot.
Outlet
Pressure
(PSIG)
0-12 81 190 323 450 768 1085 1495 2408 4273 9411
0-18 105 248 420 585 998 1410 1943 3128 5551 12227
0-20 135 318 539 751 1280 1809 2492 4013 7121 15686
0-30 153 360 611 851 1451 2051 2826 4550 8074 17786
0-35 195 460 780 1086 1853 2619 3608 5809 10308 22706
0-45 229 540 916 1277 2177 3077 4239 6825 12112 26680
0-50 255 600 1018 1419 2419 3419 4710 7584 13458 29644
0-60 322 760 1290 1796 3063 4329 5964 9603 17041 37536
0-75 381 900 1527 2128 3628 5128 7065 11376 20187 44467
0-85 449 1060 1800 2505 4272 6939 8320 13396 23771 52362
0-100 509 1200 2037 2837 4838 6838 9420 15168 26916 59288
0-120 560 1319 2238 3117 5360 7514 10351 16667 29577 65150
0-130 628 1480 2511 3498 5964 8431 11614 18700 33184 73095
0-160 755 1775 3015 4200 7160 10120 13945 22450 39840 87760
Steam (lbs/hr)
1/2" 3/4" 1" 1
1.4 3.3 5.6 7.8 13.3 18.8 25.9 41.7 74 163
2 13 32 53 75 128 181 249 401 712 1569 0 21 48 82 115 195 276 381 613 1088 2396
3 19 44 74 104 177 250 344 554 983 2165 0 29 70 117 164 279 395 544 876 1554 3423
5 25 60 102 142 242 342 471 758 1346 2964 0 35 83 141 197 335 473 653 1051 1865 4108
7 29 68 115 160 272 385 530 854 1515 3336
0-3 43 102 173 241 410 580 800 1287 2284 5031
8 37 88 149 208 354 500 690 1111 1972 4343
0-5 57 134 227 317 541 764 1053 1696 3009 6629
12 47 111 188 262 447 632 870 1401 2486 5477
0-7 70 166 282 393 670 948 1305 2102 3730 8215
15 59 139 235 328 559 790 1088 1751 3108 6846
20 66 155 263 366 625 883 1216 1958 3475 7654
30 78 183 311 433 739 1044 1439 2317 4111 9056
40 88 208 353 491 838 1184 1632 2627 4662 10269
50 98 230 390 543 926 1309 1804 2904 5154 11353
60 132 312 529 737 1257 1777 2448 3941 6993 15404
75 146 345 585 815 1389 1964 2705 4357 7731 17029
80 176 416 706 983 1676 2367 3263 5254 9324 20538
100 221 518 882 1229 2095 2961 4079 6568 11655 25672
125 243 575 975 1385 2316 3274 4510 7261 12885 28382
150 265 625 1060 1476 2518 3558 5606 7893 14008 30855
150 389 917 1556 2167 3695 5223 7195 11584 20557 45232
175 416 980 1663 2316 3950 5583 7692 12384 21976 48409
200 441 1040 1764 2457 4190 5922 8159 13136 23310 51345
200 655 1550 2625 3655 6235 8810 12140 19545 34680 76400
1
/4"1
1
/2"2" 2
1
/2"3" 4" 6"
– Capacities
REDUCED PORT
REGULATING VALVES
PILOT-OPERATED
151