Pilot-Operated Regulating Valves
REGULATING VALVES
PILOT-OPERATED
428 Jones Boulevard • Limerick Airport Business Center • Pottstown PA • 19464 • Tel: 610-495-5131 • Fax: 610-495-5134
www.watsonmcdaniel.com
117
HD Series Pilot-Operated Regulators
PILOT-OPERATED REGULATORS
Pilot-Operated Regulators are more accurate and offer higher capacities than standard direct-operated regulators.
They will maintain constant set outlet pressure even when inlet pressure fluctuates or variations in flow occur. With the
proper selection of pilots, these regulators will accurately control temperature, pressure, or a combination of both.
PILOT-OPERATED
HD-Series
REGULATING VALVES
Steam Service
& temperature rating, a large full-port strainer with blow-down valve on pilot adapter which keeps dirt
from entering control pilots, and field reversible pilot-mounting for versatile and easy installation.
The HD-Series Regulator features Ductile Iron construction for increased pressure
Page No.
HD SeriesPilot-Operated Regulating Valve120-123
DUCTILE IRON BODY
HD Regulators are used in conjunction with the
appropriate Pilot(s) to control Steam Pressure
or Process Temperature
PILOTS for HD Regulators124-135
“P” & “P5”Pressure Pilots -
The “P5” is used for special applications requiring 0.5 PSI accuracy.
The “P” is the standard spring-loaded pressure pilot. 124
“BP”Back Pressure Pilot - Controls system back pressure.125
“T”Temperature Pilot - Used for controlling temperature.126-127
“A”Air Pilot -
“PTR” & “PTL”
“TRP” Temperature Pilot - Special purpose temperature pilot for controlling low temperatures132
“S” Solenoid Pilot - Used in conjunction with any of the above pilots for electrical on/off 133
“DP” DP Pilot - Differential Pressure pilot – used when trying to balance two different 134
Also used for temperature control when used in conjunction with the “PTR”
or “PTL” temperature controller.
Temperature Controllers
a wider temperature range than the standard “T” Pilot.
outside the range of the standard “T” Pilot. Also available with special sensing bulbs.
control of HD Regulators.
media sources that are being blended
Normally used for controlling steam pressure using an air signal.
(used with “A” Air Pilot) - The “PTR” or “PTL” will control
128-129
130-131
Over Pressure Protection Methods135
118
428 Jones Boulevard • Limerick Airport Business Center • Pottstown PA • 19464 • Tel: 610-495-5131 • Fax: 610-495-5134
www.watsonmcdaniel.com
HD Series Regulators (with commonly used Pilots) 136-143
HDPPressure Regulator136-137
(HD Regulator with “P” Pressure Pilot)
HDTTemperature Regulator138-139
(HD Regulator with “T” Temperature Pilot)
HDAAir Controlled Pressure Regulator140-141
(HD Regulator with “A” Air Pilot)
REGULATING VALVES
PILOT-OPERATED
HDP TPressure & Temperature Regulator
(HD Regulator with “P” Pressure & “T” Temperature Pilot)
142-143
HSP Series Pilot-Operated Pressure Regulating Valve
CAST STEEL BODY
The Watson McDaniel HSP Pilot-operated Regulating Valve
is constructed of Cast Carbon Steel for higher pressure &
Noise Attenuation - Reduces noise in pressure reducing applications148-151
Noise Attenuators for Pressure Regulators – Series A, H & S146-149
Capacities for Sizing of HD & HSP Series Regulators150-151
temperature ratings.
144-145
428 Jones Boulevard • Limerick Airport Business Center • Pottstown PA • 19464 • Tel: 610-495-5131 • Fax: 610-495-5134
Body MaterialDuctile Iron
PMO Max. Operating Pressure300 PSIG
Design Pressure/NPT 450 PSIG @ 650˚ F
Temperature Ratings 150# FLG 150 PSIG @ 566˚ F
REGULATING VALVES
PILOT-OPERATED
TMA/PMA300# FLG 450 PSIG @ 650˚ F
TYPICAL APPLICATIONS
The Watson McDaniel HD-Series pilot operated regulators were
designed for extremely accurate control of temperature and
pressure in steam service applications. The HD-Series is made of
Ductile-iron for extended pressure and temperature ratings. These
regulators use several different control pilots, which can be attached
to the valve to control pressure, temperature, or a combination of
both. The different control pilots can be added or removed from the
regulator body. This modular design adds to the versatility of this
product. The most common options include the P-Pilot for pressure
reducing, and the T-Pilot for temperature control.
Ductile Iron Body
Hardened
SST (55 Rc)
Seat & Disk
INLET
Self-cleaning
stem guide
Spring
protected
from steam
High Tensile
Diaphragm
• Ductile Iron body for higher pressures
• Full port strainer & blowdown
• Hardened stainless steel trim
• Pre-mounted tubing & field reversible
• Optional reduced port trim
• Low differential pressure option
• Low inlet pressure option
Right or Left
Pilot Mounting
Available
(Non-standard
left mounted
shown)*
Full Port Pilot
Strainer with
built-in
Blowdown
Valve
* Standard pilot mounting is
on the right side of the
regulator when looking
into the outlet port. Pilot
mounting on HD
regulators are field
reversible.
valve on pilot adapter for ultimate
protection from dirt & scale
for extended life
pilot adapter
FEATURES
No external power source is required.
•
This simplifies the valve and minimizes
installation and maintenance costs.
Pressure and temperature pilots can be used
•
in combination eliminating the need for a
separate pressure and temperature regulator
Ductile iron for higher pressure ranges and
•
increased safety. Ductile Iron is a better choice
than cast iron for steam applications.
Full port strainer and blowdown valve on
•
pilot adapter for ultimate protection against
dirt and scale
Hardened stainless steel trim (55 Rc) for
•
extended life even in the most demanding
applications
The innovative design allows the pilot to be
•
mounted on either side of the regulator and
is easily field reversible
Comes fully assembled with tubing and pilot
•
adapter. The control pilot requires only four
bolts to complete the installation.
120
428 Jones Boulevard • Limerick Airport Business Center • Pottstown PA • 19464 • Tel: 610-495-5131 • Fax: 610-495-5134
Standard pilot mounting is on the right side of the regulator
when looking into the outlet port (see diagrams on
next page which are all right mounted). For opposite
mounting, please specify when ordering. Pilot mounting
on HD regulators are field reversible.
Pressure
When controlling pressure there are several options you can use
for a pilot. The P-Pilot and the P5-Pilot are both spring adjusted
pressure pilots. The P-Pilot is used on typical general-purpose
pressure reducing applications. The P5-Pilot is used when higher
accuracy is required and is capable of maintaining a control
pressure window of less then 1 PSI. The A-Pilot is air controlled
and generally used when adjustment of the regulator and
pressure reducing station is done remotely.
Temperature
The T-Pilot is used to control temperature. The T-Pilot is filled
with a temperature sensitive liquid, which expands when heated.
The expansion of this liquid actuates a bellows that controls
the temperature-regulating valve. The T-Pilot is equipped with
an overheat bellows that protects the pilot in case of an over
temperature condition. The T-Pilot controls temperature through
a range of 60-260˚F. Spec: ANSI/FCI 70-2 Class IV shut-off.
TYPICAL APPLICATIONS
• Pressure Regulating
• Temperature Regulating
• Pressure-Temperature Control
• Back Pressure Control
• Differential Pressure Control
On-Off
On-off control of the regulator is possible by using the S-Solenoid
Pilot. The S-Pilot allows the regulator to be shut off or turned
on electrically. Normally the regulator is equipped with either
a P-Pressure Pilot or T-Temperature Pilot in addition to the
S-Solenoid Pilot.
Pressure-Temperature
The PT-Pilot combination is used when it is desirable to control both
the pressure and temperature of a system with only one regulating
valve. The unique features of this modular valve allow this to be
accomplished quite easily. When the PT-Pilot combination is used, the
downstream pressure is limited to a maximum setting by the pressure
pilot, while the temperature pilot maintains the correct temperature.
Back Pressure
When controlling the back pressure in a steam system, the BP-Pilot
is used in conjunction with the HD-Series Regulator. This controls
the pressure on the upstream side of the regulator.
Differential Pressure
The DP-Pilot is used when trying to balance two different media
sources that are being blended.
REGULATING VALVES
PILOT-OPERATED
COMBINATION PILOTS
One of the advantages of the HD-Series regulating valve is
that it can be used with many different variations of control pilots.
Up to three pilots can be used simultaneously to control the
operation of these valves. The most common is the “PT” PressureTemperature combination pilots. In addition to these pilots being
used together the S-Solenoid Pilot can be used for turning the
system on and off. (See next page for combination examples.)
428 Jones Boulevard • Limerick Airport Business Center • Pottstown PA • 19464 • Tel: 610-495-5131 • Fax: 610-495-5134
Option: Stainless diaphragms and external tubing - consult factory
MATERIALS
Body Ductile Iron
CoverDuctile Iron
GasketGrafoil
Cover ScrewsSteel
Pilot AdapterDuctile Iron/Cast Steel
ScreenStainless Steel
TubingCopper
Valve SeatHardened SST (55Rc)
Valve DiscHardened SST (55Rc)
DiaphragmPhosphor Bronze
MINIMUM OPERATING PRESSURES
Minimum Inlet Pressure (for Valve):
15 PSIG (Standar
5 PSIG (Low Pr
Minimum Differential Pressure
10 PSI (Standar
3 PSI (Low Pr
* Not required for Temperature Pilot applications
d Main Valve)
essure Main Valve)
(for Valve):*
d Main Valve)
essure Main Valve)
HOW TO ORDER
REGULATOR BODY
Specify: • HD regulator body
• Regulator size or capacity of steam required
• End connections
(threaded, 150/300# flanged)
PILOT REQUIRED TO OPERA
Note: See “How to Order” in specific Pilot Section
• T Temperature Pilot
• P Pressure Pilot
• A Air Pilot
• S Solenoid Pilot
• BP Back Pressure Pilot
• PD Differential Pressure
TE THIS VALVE
REGULATING VALVES
PILOT-OPERATED
FLOW
A
FLG
A
NPT
Pilot mounting
surface
C
OUT
B
D
428 Jones Boulevard • Limerick Airport Business Center • Pottstown PA • 19464 • Tel: 610-495-5131 • Fax: 610-495-5134
www.watsonmcdaniel.com
Standard pilot mounting is on
the right side of the regulator
when looking into the outlet
port (as shown). Pilot
mounting on HD regulators
are field reversible.
Pilot Body & CoverDuctile Iron or Cast Steel
GasketGrafoil
DiaphragmPhosphor Bronze
Head & Seat AssemblyHardened SST (55 Rc)
TYPICAL APPLICATIONS
The “P” & “P5” Pressure Pilots are used with the HD Regulator
to control steam pressure in steam mains or for process
equipment. Pilot operated regulators will maintain constant
downstream pressure even when the inlet pressure to the valve
fluctuates or steam usage varies.
FEATURES
The “P” Pilot can maintain downstream pressure to ±1 PSIG
•
“P5” Pilot can maintain downstream pressure to ±0.5 PSIG
•
Choic
es of three overlapping pressure ranges
•
Pressure control spring can be changed in line
•
Pilot is easily installed using only four bolts
•
Full port strainer and blowdown valve on pilot adapter for
•
ultimate protection from dirt and scale
Can be used with temperature and solenoid control pilot
•
Solid floating diaphragm is more failure resistant
•
Watson McDaniel's pilots can be used with other
•
manufacturers’ regulators
OPTIONS
Pressure pilot can be used with temperature pilot to eliminate
•
the need for two separate regulators
Solenoid pilot can be added for remote on/off control
•
of regulator
“P5” Pilot will maintain +0.5 PSIG accuracy
•
HOW TO ORDER
“P”, “P5” PRESSURE PILOT
Specify:• Reduced pressure range –
Example: “P” Pilot at 3-25 PSIG, yellow
REGULA
Specify:• HD regulator body
TOR BODY
• Regulator size or capacity
• End connections (threaded, 150/300# flanged)
Steam Sensing Line
Connection
1/4” NPT
91/2
12
MINIMUM OPERATING PRESSURES
Minimum Inlet Pressure:
15 PSIG(Standar
5 PSIG(Low Pr
Minimum Differential Pressure:
10 PSI(Standar
3 PSI (Low Pr
124
428 Jones Boulevard • Limerick Airport Business Center • Pottstown PA • 19464 • Tel: 610-495-5131 • Fax: 610-495-5134
d Main Valve)
essure Main Valve)
d Main Valve)
essure Main Valve)
Units: inches
5
8
www.watsonmcdaniel.com
“P”
“P5”
Back Pressure Pilot for HD Regulating Valves
Back Pressure
PILOTS
“
BP”Pilot
Pilot
• Max Inlet Pressure: 300 PSIG
• Back Pressure Range: 10-200 PSIG
• Minimum Inlet Pressures:
15 PSIG when used with standard main valve
5 PSIG when used with low pressure main valve
PRESSURE-ADJUSTING SPRING RANGES
Pressure RangeIdentifying Colors
10-25 PSIGyellow
20-100 PSIGblue
80-200 PSIGred
TYPICAL APPLICATIONS
The “BP” Back-Pressure Pilot used with the HD regulator,
maintains upstream pressure in steam systems. These regulators
are commonly used to supply flash steam to low pressure mains.
FEATURES
The “BP” Pilot can maintain upstream pressure to ±1 PSIG
•
Choices of three overlapping pressure ranges
•
Pressure adjusting spring can be changed with
•
regulator in line
Pilot is easily installed using only four bolts
•
Full port strainer and blowdown valve on pilot adapter for
•
ultimate protection from dirt and scale
Solid floating diaphragm is more failure resistant
•
Watson McDaniel's pilots can be used with other
•
manufacturers’ regulators
MATERIALS
Pilot Body & Cover Ductile Iron
GasketGrafoil
DiaphragmPhosphor Bronze
Head & Seat AssemblyHardened SST (55 Rc)
HOW TO ORDER
“BP” BACK PRESSURE PILOT
Specify:• Reduced pressure range –
Example:“BP” Pilot at 20-100 PSIG, blue
REGULA
Specify:• HD regulator body
TOR BODY
• Regulator size or capacity
• End connections (threaded, 150/300# flanged)
REGULATING VALVES
PILOT-OPERATED
OPTIONS
Can be used with solenoid pilot for on/off control
•
MINIMUM OPERATING PRESSURES
Minimum Inlet Pressure:
15 PSIG(Standar
5 PSIG(Low Pr
Minimum Differential Pressure:
10 PSI(Standar
3 PSI (Low Pr
d Main Valve)
essure Main Valve)
d Main Valve)
essure Main Valve)
428 Jones Boulevard • Limerick Airport Business Center • Pottstown PA • 19464 • Tel: 610-495-5131 • Fax: 610-495-5134
www.watsonmcdaniel.com
Steam Sensing Line
Connection
1/4” NPT
Units: inches
91/2
5
125
PILOTS
“
Temperature Pilot for HD Regulating Valves
T
”
Pilot
TemperaturePilot
• Max Inlet Pressure: 300 PSIG
• Temperature Control Range: 60-260 F
• Minimum Inlet Pressures:
15 PSIG when used with standard main valve
5 PSIG when low pressure temperature pilot is used
with low pressure main valve
Low Pressure Temperature Pilot must be used
PILOT-OPERATED
REGULATING VALVES
in conjunction with a low pressure main valve
for applications where inlet steam pressure is
less than 15 PSIG.
SPECIFY WHEN ORDERING.
TYPICAL APPLICATIONS
The “T” Temperature Pilot is used with the HD regulator
to control temperature in various processes and systems.
Some examples are:
• Oil heaters• Ovens
• Process heaters• Vats
• Dryers• Jacketed Kettles
FEATURES
Temperature adjustment made simple and easy by rotating
•
an adjustment knob to the desired temperature setting
Thermostatic sensing bulb comes with an 8-ft. or 15-ft.
•
length capillary
Capillary is armor-protected to resist damage
•
Overheat protection bellows is incorporated into sensing
•
bulb; 200˚F overheat protection up to 350˚F
Full port strainer and blowdown valve on pilot adapter for
•
ultimate protection from dirt and scale
OPTIONS
Temperature Pilot can be combined with Pressure and
•
Solenoid pilots
Additional capillary lengths can be ordered in 5-ft. increments;
•
up to 25-ft. maximum length
Wells* for isolating sensing bulb from process liquid are
•
available in 316 stainless steel or brass
Extended length wells are available
•
316 Stainless Steel Sensing Bulb
•
Other options available; consult factory
•
* Thermowells:
Wells isolate sensing bulb from the process liquid and are
available in Brass or Stainless Steel. When placed on the
side of a tank or vessel, the sensing bulb can be removed
without having to drain the process fluid.
428 Jones Boulevard • Limerick Airport Business Center • Pottstown PA • 19464 • Tel: 610-495-5131 • Fax: 610-495-5134
www.watsonmcdaniel.com
PILOTS
Temperature Pilot for HD Regulating Valves
SENSING BULBS AVAILABLE
81/2
T
TU
TUBW
TUSW
TBW
5/8
51/2
5/8
3/4” NPT
57/8
3/4
3/4” NPT
61/8
3/4
3/4” NPT
18
3/4
3/4” NPT
Units: inches
*Most common
“
TPlain copper bulb
TUUnion connected copper bulb that can be
screwed into the side of tank
* most common selection
TUBW Type TU bulb with a brass well. The well, which
isolates bulb from process fluid, can be placed
in the side of a tank allowing the sensing bulb to
be removed without having to drain the tank of
liquid
TUSW Type TU bulb with a corrosion resistant stainless
steel well. The well, which isolates bulb from
process fluid, can be placed in the side of a tank
allowing the sensing bulb to be removed without
having to drain the tank of liquid
TBWType T bulb with an extended length brass
well. The extended well allows deeper insertion
of sensing bulb into tanks.
TSWType T bulb with extended length stainless
steel well. The extended well allows deeper
insertion of sensing bulb into tanks.
Other options available; consult factory.
T
”
Pilot
REGULATING VALVES
PILOT-OPERATED
TSW
18
3/4
3/4” NPT
Diagram below shows “T” Pilot TU Option for Bulb
63/4
See bulb
chart above
Units: inches
Union
Nut
Union Hub
3/4” NPT
HOW TO ORDER
“T” TEMPERATURE PILOT
Specify:
• Temperature range from the chart or indicate the
temperature of the process you wish to control
• The length of capillary required; 8-ft. is standard
• Bulb type needed:
T, TU, TUBW, TUSW, TBW & TSW
Example: TU, 8 FT CAP, 60-120˚F, yellow
REGULA
Specify:
• HD regulator body
• Regulator size or capacity of steam required
• End connections (threaded, 150/300# flanged)
TOR BODY
MINIMUM OPERATING PRESSURES
Minimum Inlet Pressure:
15 PSIG(Standar
5 PSIG(Low Pr
Low Pressure Temperature Pilot must be used in
conjunction with a Low Pressure Main Valve for
applications where inlet steam pressure is below
15 PSIG. SPECIFY WHEN ORDERING.
d Main Valve)
essure Main Valve with
Low Pressure Temperature Pilot)
428 Jones Boulevard • Limerick Airport Business Center • Pottstown PA • 19464 • Tel: 610-495-5131 • Fax: 610-495-5134
The “A” Air Pilot is used with the HD Regulator to control
steam pressure on steam mains and process equipment.
The “A” Air Pilot can also be used in conjunction with the PTL or PTR pneumatic temperature controllers for controlling
temperature in process applications. The principal advantage
the “A” Air Pilot over standard spring loaded pilots is that
pressure adjustments to the regulator can be made from a
remote location. A regulator that is placed in a difficult to
reach or inaccessible location can be adjusted by a remote
control panel board placed in an accessible location.
HOW IT WORKS
When air pressure is applied to the upper chamber of the air
pilot it exerts a downward force on the air pilot’s diaphragm.
This force controls the outlet pressure of the steam through
the regulating valve. The control process is similar to a spring
loaded pressure pilot except that the air pressure takes the place
of the spring. There are three separate models of air pilots that
make up the complete range depending on the steam pressure
that needs to be controlled and the control air pressure available.
See Pressure Adjusting Ranges chart.
FEATURES
•
•
•
•
PTL & PTR temperature controllers
Pressure adjustments to the regulator can be done from
a remote location using an air signal
Air-operated pilot ensures instant response and extremely
accurate control
Full port strainer and blowdown valve on pilot adapter for
ultimate protection from dirt and scale
Controls pressure settings within ±1 PSIG
Controls Pressure & Temperature
MAXIMUM CONTROL AIR PRESSURE ON AIR PILOT IS 125 PSIG
PRESSURE ADJUSTING RANGES
Model
A13-125 PSIG1:1 ratio of steam pressure
A43-200 PSIG4:1 ratio of steam pressure
A620-200 PSIG6:1 ratio of steam pressure
The larger Diaphragm area of the “A4” & “A6” Air Pilots
allow the use of lower control air pressure to regulate higher
pressure steam.
MATERIALS
Pilot Body & CoverDuctile Iron
GasketGrafoil
Cover ScrewsSteel, GR5
Head & Seat AssemblyHardened SST (55 Rc)
Pressure
Ranges
Description
to control air pressure
to control air pressure
to control air pressure
Control Air Connection
1/4” NPT
B
DIMENSIONS –
ModelAB
A1 5
A45
A6 5
128
428 Jones Boulevard • Limerick Airport Business Center • Pottstown PA • 19464 • Tel: 610-495-5131 • Fax: 610-495-5134
inches
1
/45
1
/477/8
1
/491/2
Steam
Sensing Line
Connection
1/4” NPT
A
www.watsonmcdaniel.com
PILOTS
“
A”Pilot
Controls Pressure & Temperature
Air Pilot for HD Regulating Valves
REMOTE CONTROL PANEL BOARDS
Three different options of remote control panel boards can be used along
with the "A" Air Pilots. Supply air is fed directly through the control panel
board to the air pilot. You can choose one of the three options of control
panel boards when using the air piloted regulators. Minimum 5 PSIG air
supply pressure is required.
AIR SIGNAL
PL1
AIR SUPPLY
AIR SIGNAL
PL2
STEAM PRESSURE
AIR SUPPLY
AIR SIGNAL
PL1
The PL1 is made up of an air pressure regulator with adjustment knob
and pressure gauge that measures the amount of air pressure going to
the pilot (air signal). Steam pressure of the system is controlled by
adjusting the air pressure regulator.
PL3
HOW TO ORDER
“A” AIR PILOT
Specify:
• Air Pilot A1, A4 or A6
• Remote Control Panel Board
PL1, PL2 or PL3
REGULA
Specify:
• HD regulator body
• Regulator size or capacity and pressure range
• End connections (threaded, 150/300# flanged)
TOR BODY
of steam required
MINIMUM OPERATING PRESSURES
Minimum Inlet Pressure:
15 PSIG(Standar
5 PSIG(Low Pr
Minimum Differential Pressure:
10 PSI(Standar
3 PSI (Low Pr
d Main Valve)
essure Main Valve)
d Main Valve)
essure Main Valve)
REGULATING VALVES
REGULATING VALVES
PILOT-OPERATED
PL2
The PL2 is the same as the PL1 with the addition of an extra air pressure
gauge for measuring the air supply pressure to the control panel board.
PL3
The PL3 is the same as the PL2 with the addition of a Steam
Pressure Gauge for measuring steam pressure on the outlet side
of the regulating valve.
Pressure Reducing Station Using HD Regulator with an Air Pilot
INLET
STEAM
AIR SIGNAL
(control air)
BYPASS
AIR PILOT
HD
REGULATOR
HDA
(REGULATOR
with AIR PILOT)
PL2
FLOW
CONTROL AIR PRESSURE RANGE
A-Pilot Control Pressure:
AIR SUPPLY
SENSING LINE
SLOPED DOWN
FROM PILOT
OUTLET
STEAM
3-125 PSIG(depending on pilot selected and
desired outlet pressure)
DESCRIPTION OF OPERATION
The “A” Air Pilot is being used in conjunction
with the PL2 Control Panel Board to regulate
steam pressure. A small air regulator on the
panel board can be adjusted to control the air
pressure to the pilot. One gauge on the panel
board measures air line pressure to the panel
board and the other gauge shows the air
pressure being sent to the pilot. Steam pressure
at the outlet of the regulator is controlled by the
air pressure signal to the pilot. Depending on
the air pilot model chosen (A1, A4, A6), there
will be a 1:1, 4:1, or 6:1 ratio of outlet steam
pressure to air pressure.
STEAM TRAP
428 Jones Boulevard • Limerick Airport Business Center • Pottstown PA • 19464 • Tel: 610-495-5131 • Fax: 610-495-5134
www.watsonmcdaniel.com
129
PILOTS
PTL & PTR Controller
Pneumatic Temperature Controller (used with Air Pilot)
The PTL and PTR Pneumatic Temperature
Controllers operate over a wider temperature
range than our standard “T” temperature pilot.
These temperature controllers also react quicker to
temperature change which make them an excellent
choice for instantaneous hot water applications.
HOW IT WORKS
The PTL and PTR Pneumatic Temperature
Controllers are used in conjunction with an
“A” Air Pilot to control the operation of the HD
Regulator. The PTL uses a bimetallic element to
sense temperature and the PTR uses a hydraulically
filled bulb with a 4-ft. capillary to sense temperature.
The air supply is connected to the inlet of the controller
and the air output signal is fed directly to an Air Pilot,
which controls the opening and closing of the steam
regulating valve.
FEATURES
Accurate and rapid response to temperature
•
changes
Covers control temperature range of 0-350 ˚F
•
MINIMUM OPERATING PRESSURES
15 PSIG(Standar
5 PSIG(Low Pr
d Main Valve)
essure Main Valve)
PTL
(mounts directly on
tank or vessel)
PTR
(mounts remotely
with 4-ft. Capillary)
ModelPTLPTR
Temperature Adjustment Range
Maximum Air Supply Pressure
Sensing BulbBi-MetallicHydraulic Fill
PTL & PTR PNEUMATIC TEMPERATURE CONTROLLER
Specify:• PTL or PTR controller model (air pilot required for operation)
AIR PILOT
Specify:• A1, A4 or A6 Air Pilot model (refer to Air Pilot section)
REGULA
Specify:• HD regulator body
TOR BODY
• Regulator size or capacity
• End connections (threaded, 150/300# flanged)
130
428 Jones Boulevard • Limerick Airport Business Center • Pottstown PA • 19464 • Tel: 610-495-5131 • Fax: 610-495-5134
www.watsonmcdaniel.com
SERIES HDA-PTL
PNEUMATIC
TEMPERATURE
REGULATOR
STEAM
INLET
BYPASS LINE
PILOTS
PTL & PTR Controller
Pneumatic Temperature Controller (used with Air Pilot)
DESCRIPTION OF
OPERATION
The PTL Pneumatic Temperature
Controller senses outlet water
temperature on a semiinstantaneous hot water heater.
When the outlet water temperature
falls below the set point, the PTL
pneumatic temperature controller
sends an air signal to the A1 AirPilot which opens the regulator,
allowing steam to heat the tank.
When the water reaches the
desired set temperature, the PTL
pneumatic temperature controller
shuts off the air signal to the A1Air Pilot and the regulator closes,
cutting off steam to the heater.
VACUUM
BREAKER
SEMI-INSTANTANEOUS
AIR
VENT
HEATER
COLD
WATER
INLET
AIR
SIGNAL
LINE
HOT
WATER
OUTLET
AIR
REGULATOR
AIR
INLET
“PTL”
CONTROLLER
REGULATING VALVES
PILOT-OPERATED
Model PTL (direct mounted)
11/
35/
2
8
3/4” NPT
Model PTR (remote mounted)
2-1/4
5
/
3
16
111/
STEAM
TRAP
WELL
111/
2
3/4” NPT
8
COPPER
WELL
111/
TEMPERATURE SET POINT ADJUSTMENT KNOB
7/8
1/8”
NPT
27/
8
Units: inches
TEMPERATURE SET POINT ADJUSTMENT KNOB
13/32
8
23/
4
WITH RELAY
61/
2
STAINLESS STEEL
1
/
5
4
428 Jones Boulevard • Limerick Airport Business Center • Pottstown PA • 19464 • Tel: 610-495-5131 • Fax: 610-495-5134
www.watsonmcdaniel.com
1/8”
NPT
21/
8
131
PILOTS
“
TRP”Pilot
Temperature Pilot for HD Regulating Valves
TemperaturePilot
• Max Inlet Pressure: 300 PSIG
• Temperature Control Range: 20-250 F
• Min Inlet Pressures:15 PSIG standard main valve
5 PSIG low pressure main valve
TYPICAL APPLICATIONS
PILOT-OPERATED
The “TRP” Temperature Pilot is used with the HD Regulator to
control temperature in various processes and systems. Some
examples are: Oil heaters, Ovens, Process Heaters, Vats, Dryers
REGULATING VALVES
and Jacketed Kettles.
FEATURES
Ductile Iron pilot body
•
Stainless steel valve and seat
•
Standard capillary is copper with 316 stainless steel
•
armor in 10 feet length
OPTIONS
Additional Capillary Length: Available up to 25-ft. in
•
5-ft. increments.
Special Materials: Sensing bulb, wells, and capillary are
•
available in special corrosion resistant materials.
- 316 stainless steel capillary
- 316 stainless steel armor with standard capillary
- Kynar-covered capillary
Finned Bulb: Special finned sensing bulb for improved
•
temperature sensitivity when controlling air temperature in
heating ducts
Thermowell or Separable Socket: Available in
•
stainless steel or copper
Temperature Sensing Dial: Indicates temperature of
428 Jones Boulevard • Limerick Airport Business Center • Pottstown PA • 19464 • Tel: 610-495-5131 • Fax: 610-495-5134
www.watsonmcdaniel.com
PILOTS
Electric Pilot for On/Off Control of
Solenoid
Pilot
•For Electrical On-Off Control
of Regulating Valves
•Max Inlet Pressure: 250 PSIG
TYPICAL APPLICATIONS
Typically used for automatic operation, remote control,
programmed cycling, sequential function interlocks with other
equipment, and emergency shut-off in case of power failure.
HOW IT WORKS
The “S” Solenoid Pilot can be used in conjunction with
Pressure, Temperature, or Air Pilots to electrically control on/off
operation of the HD Regulator. When the solenoid pilot is used,
the regulator can be turned on or off by electrically activating
or de-activating the solenoid.
“
HD
”
S
Regulating Valves
Pilot
STANDARD SOLENOID PILOTS AVAILABLE
Steam Inlet Pressure0-180 PSIG
180-250 PSIG
NEMA 1 – Standard
NEMA RatingsNEMA 4 – Waterproof (optional)
NEMA 7 – Explosion-proof (optional)
Voltage110 Volts AC (standard)
24 Volts AC (optional)
220 Volts AC (optional)
240 Volts AC (optional)
REGULATING VALVES
REGULATING VALVES
PILOT-OPERATED
Normally Closed (nc) – Standard
The normally closed Solenoid Pilot remains closed in the
non-activated state. The regulating valve will remain closed
until an electrical signal is sent to the solenoid pilot. This is
known as a fail-safe condition.
Normally Open (no) – Optional
The normally opened Solenoid Pilot remains open in the
non-activated state. The regulating valve will function normally
unless an electrical signal is used to shut-off the solenoid pilot.
FEATURES
Available normally opened (no) or normally closed (nc)
•
Full-port strainer and blow-down valve on pilot adapter to
•
eliminate failure caused by contaminated steam systems
OPTIONS
Normally open solenoid
•
NEMA Ratings: NEMA 4 and NEMA 7
•
Voltage: 24 VAC, 220 VAC, 240 VAC
•
MINIMUM OPERATING PRESSURES
Minimum Inlet Pressure:
15 PSIG(Standar
5 PSIG(Low Pr
Minimum Differential Pressure:
10 PSI(Standar
3 PSI (Low Pr
d Main Valve)
essure Main Valve)
d Main Valve)
essure Main Valve)
MATERIALS
Pilot Body & CoverDuctile Iron
GasketGrafoil
Cover ScrewsSteel, GR5
InternalsStainless Steel
HOW TO ORDER
“S” SOLENOID PILOT
Specify:• Inlet Steam Pressure range:
0-180 PSIG or 180-250 PSIG
• NEMA rating: NEMA 1, NEMA 4 or NEMA 7
(if not specified NEMA 1 Standard will be supplied)
• Control Voltage: 24, 110, 220 or 240 VAC
REGULA
Specify:• HD regulator body
TOR BODY
• Regulator size or capacity of steam required
• End connections (threaded, 150/300# flanged)
428 Jones Boulevard • Limerick Airport Business Center • Pottstown PA • 19464 • Tel: 610-495-5131 • Fax: 610-495-5134
www.watsonmcdaniel.com
133
PILOTS
“
DP”Pilot
Differential Pressure Pilot for HD Regulating Valves
Differential Pressure Pilot
• Max Inlet Pressure: 300 PSIG
• Reduced Outlet Pressure Range: 3-200 PSIG
• Min Inlet Pressures:15 PSIG standard main valve
5 PSIG low pressure main valve
• DP-Pilot
PRESSURE-ADJUSTING SPRING RANGES
REGULATING VALVES
PILOT-OPERATED
“DP” Pressure RangeIdentifying Colors
TYPICAL APPLICATIONS
The “DP” Differential Pressure Pilot is used with the HD
Regulator to maintain steam pressure at a balanced differential
pressure above another media source. This is typical on an oil
burner where steam used for atomization is injected into the oil
burner at a set pressure above the incoming oil supply. Therefore,
as oil pressure fluctuates based on demand, the steam pressure
will be maintained at a differential pressure above the oil pressure.
FEATURES
The “DP” Differential Pressure Pilot is used to maintain
•
downstream steam pressure to a set differential pressure
above loading pressure
Accuracy to within ±2 PSIG
•
3 overlapping spring ranges to choose from
•
Pilot is installed using only four bolts
•
Full port strainer and blowdown valve on pilot adapter for
•
ultimate protection from dirt and scale
Solid floating diaphragm
•
Watson McDaniel's pilots can be used with other
•
manufacturers’ regulators
+
2 PSIG accuracy
3-25 PSIGyellow
20-100 PSIGblue
80-200 PSIGred
MATERIALS
Pilot Body & CoverDuctile Iron & Cast Steel
GasketGrafoil
DiaphragmPhosphor Bronze
Head & Seat AssemblyHardened SST (55 Rc)
HOW TO ORDER
“DP” DIFFERENTIAL PRESSURE PILOT
Specify:• Reduced pressure range –
Example:“DP” Pilot at 3-25 PSIG, yellow
Solenoid pilot can be added for remote on/off control of
•
regulator
MINIMUM OPERATING PRESSURES
Minimum Inlet Pressure:
15 PSIG(Standar
5 PSIG(Low Pr
Minimum Differential Pressure:
10 PSI(Standar
3 PSI (Low Pr
134
428 Jones Boulevard • Limerick Airport Business Center • Pottstown PA • 19464 • Tel: 610-495-5131 • Fax: 610-495-5134
d Main Valve)
essure Main Valve)
d Main Valve)
essure Main Valve)
9.27
Units: inches
www.watsonmcdaniel.com
5.00
PILOTS
Over Pressure Protection Methods
Using “P” and “BP” Pilots
Back Pressure Regulators for Boiler Overload Protection
In steam systems with several applications of varying importance, a back pressure regulator may be used to prevent overloading of the
boiler by isolating non-essential loads from critical processes in the event steam demand exceeds boiler output. When steam demand
is greater than the capacity the boiler can generate, pressure in the boiler will drop, possibly upsetting the control balance in the boiler
resulting in the generation of wet steam. Using back pressure regulators on the non-essential application supply lines allows isolation
of these applications at times of peak demand by shutting off steam flow to areas deemed non-essential. This ensures that boiler
demand is not exceeded and steam flow is maintained to critical processes until demand subsides and the boiler is able to catch up.
STEAM TO ESSENTIAL SERVICES
SAFETY
VALVE
DRIP PAN
ELBOW
REGULATING VALVES
PILOT-OPERATED
STEAM TO
NON-ESSENTIAL
SERVICES
BOILER
STEAM
SUPPLY
PILOT-OPERATED
BACK PRESSURE
REGULATOR
HEADER
PILOT-OPERATED
PRESSURE REDUCING
AND BACK PRESSURE
REGULATOR
FTT
TRAP
STEAM TO
NON-ESSENTIAL
SERVICES
Pressure Override Protection of Regulator Supply Lines
On multi-stage pressure reducing applications where a rise in control pressure due to failure of the final supply regulator could result in
equipment damage and/or personnel injury, a secondary pressure pilot may be added to provide override protection of a steam supply
line. During normal operation, the main pressure pilot on the 1st stage regulator provides intermediate pressure control while the
additional “monitor” pilot senses final control pressure and remains open due to a slightly higher setting than the final control pressure
setting. Should the 2nd stage regulator fail for any reason, increasing supply pressure will begin to close the monitor pressure pilot of
the 1st stage regulator, thus overriding the main control pilot preventing final supply pressure from increasing. This overpressure
protection can similarly be offered on single-stage reducing valves by protecting against failure of the main control pilot.
MAIN
PRESSURE
PILOT
INLET
1st Stage HD REGULATOR
428 Jones Boulevard • Limerick Airport Business Center • Pottstown PA • 19464 • Tel: 610-495-5131 • Fax: 610-495-5134
The HD Regulator with the “P” Pressure Pilot is used
for reducing steam pressure in piping mains and
process applications. Pilot-operated regulators will
maintain constant downstream pressure even when the
inlet pressure to the regulator fluctuates or steam usage
varies.
FEATURES
The “P” Pilot can maintain downstream pressure
•
to ±1 PSIG
Optional “P5” pilot can maintain pressure
•
to ±0.5 PSIG
Choices of three overlapping pressure ranges
•
Pressure adjusting spring can be changed with
•
regulator in line
Pilot is easily installed using only four bolts
•
Full port strainer and blowdown valve on pilot
•
adapter for ultimate protection from dirt and scale
Watson McDaniel’s pilots can be used with other
•
manufacturers’ regulators
OPTIONS
Pressure and temperature pilots can be combined
•
on the same regulator
Solenoid pilot can be added for electrical on/off
•
control of the regulator
Can be used with solenoid and temperature pilots
•
MINIMUM OPERATING PRESSURES
Minimum Inlet Pressure:
15 PSIG(Standar
5 PSIG(Low Pr
Minimum Differential Pressure:
10 PSI(Standar
3 PSI (Low Pr
d Main Valve)
essure Main Valve)
d Main Valve)
essure Main Valve)
PRESSURE-ADJUSTING SPRING RANGES “P”
Pressure RangesIdentifying Colors
3-25 PSIGyellow
20-100 PSIGblue
80-200 PSIGred
PRESSURE-ADJUSTING SPRING RANGES “P5”
1-10 PSIGyellow
10-25 PSIGblue
MATERIALS
Body Ductile Iron
CoverDuctile Iron
GasketGrafoil
Cover ScrewsSteel
Pilot AdapterDuctile Iron/Cast Steel
ScreenStainless Steel
TubingCopper
Valve SeatHardened SST (55 Rc)
Valve DiscHardened SST (55 Rc)
DiaphragmPhosphor Bronze
136
428 Jones Boulevard • Limerick Airport Business Center • Pottstown PA • 19464 • Tel: 610-495-5131 • Fax: 610-495-5134
* For sizes 1/2” to 11/2” add 21/2” to “C” dimension;
For sizes 2” to 6” add 5” to “C” dimension.
** Add 11/2” to “E” dimension for all sizes.
7
1
/8
/8
12
1614
1
5
/2
1
5
/2
1
66
3
98
/4
3
7
/8
3
/8
7
/8
1
/4
3
7
/4
8
/8
1
7
/2
10
/8
1
/8
11
11
11
11
11
11
11
11
12
7
/8
7
/8
7
/8
7
/8
7
/8
7
/8
7
/8
7
/8
7
/8
1
/2
1
6
6
8
8
10
11
13
14
19
3
/2
7
/4
1
3
/2
7
/4
3
77
3
3
7
3
1
3
3
/4
1
/4
8
/4
1
/4
8
/4
1
/8
8
/2
1
/4
8
/2
1
/4
9
/2
1
/4
10
3
/4
11
18
18
2335
43
4360
6585
/2
/4
105
145
235
470
Standard P-Pilot = 5”
P5-Pilot = 8”
C
B
E
D
HOW TO ORDER
P or P5 PRESSURE PILOT
Specify:• Reduced pressure range
(P5 Pilot requires a special adapter block on 3” & 4” valves)
REGULATOR BODY
Specify:• HD regulator body
• Regulator size or capacity and pressures
of steam required
• End connections
(threaded, 150/300# flanged)
REGULATING VALVES
PILOT-OPERATED
Adjusting Spring
Pilot
Diaphragm
Pilot Valve
Main Valve
Inlet
Pressure
Adjusting Screw
PRESSURE PILOT
Downstream
Pressure
Sensing LIne
Bleed
Orifice
HOW IT WORKS
The purpose of the pressure pilot is to control the
operation of the pressure regulating valve. A pressure
sensing line connects the pressure pilot to the
downstream side of the regulator. The pressure in the
sensing line is directed under the diaphragm in the
pressure pilot. When the pressure in the system
Control
Pressure
Line
reaches the adjusting spring set point it pushes the
diaphragm upwards against the force of the adjusting
spring and closes the pilot valve. When the pilot valve
is shut, steam can no longer pass through to the
Outlet
underside of the regulator diaphragm and the main
valve closes. When the steam pressure falls below
its set point, the pilot valve opens allowing steam
Diaphragm
Orifice with
Clean-out Wire
Main Valve Diaphragm
428 Jones Boulevard • Limerick Airport Business Center • Pottstown PA • 19464 • Tel: 610-495-5131 • Fax: 610-495-5134
www.watsonmcdaniel.com
to lift the main valve diaphragm which opens up
the regulating valve.
Low Pressure Temperature Pilot must be used
in conjunction with a low pressure main valve
for applications where inlet steam pressure is
less than 15 PSIG.
TYPICAL APPLICATIONS
The HD Regulator with the “T” Temperature Pilot is
used for controlling temperature in various processes
and systems, such as Oil Heaters, Ovens, Process
Heaters, Vats, Dryers and Jacketed Kettles.
FEATURES
Temperature adjustment made simple and easy
•
by rotating an adjustment knob to the desired
temperature setting
Thermostatic sensing bulb comes with 8-ft. or
•
15-ft. capillary; optional lengths up
Capillary is armor-protected to resist damage
•
Optional stainless steel sensing bulb and capillary
•
Overheat protection bellows is incorporated into
•
sensing bulb; 200˚F overheat protection up to 350˚F
Can be used with Pressure Pilot for simultaneous
•
control of pressure and temperature
Hardened stainless steel trim on regulator for
•
extended service life
Full port strainer and blowdown valve on pilot
•
adapter for ultimate protection from dirt and scale
OPTIONS
Temperature Pilot can be combined with Pressure
•
and Solenoid pilots
Additional capillary lengths can be ordered in 5-ft.
•
increments; up to 25-ft. maximum length
Wells* are available in 316 stainless steel
•
Longer wells can be supplied
•
Low pressure (under 15 PSIG) temperature pilot
•
Consult factory for other options
•
standard main valve with standard temperature pilot
low pressure main valve with low pressure temp. pilot
Body Ductile Iron
CoverDuctile Iron
GasketGrafoil
Cover ScrewsSteel
Pilot AdapterDuctile Iron/Cast Steel
ScreenStainless Steel
TubingCopper
Valve SeatHardened SST (55 Rc)
Valve DiscHardened SST (55 Rc)
DiaphragmPhosphor Bronze
* Thermowells:
Wells isolate sensing bulb from the process liquid and
are available in Brass or Stainless Steel. When placed
on the side of a tank or vessel, the sensing bulb can
be removed without having to drain the process fluid.
138
428 Jones Boulevard • Limerick Airport Business Center • Pottstown PA • 19464 • Tel: 610-495-5131 • Fax: 610-495-5134
• Temperature range from the chart or indicate the set temperature
of the process you wish to control
• The length of capillary required. 8-ft. or 15-ft. standard;
Maximum length: 25-ft. in 5-ft. increments
• Bulb type needed:
T, TU, TUBW, TUSW, TBW & TSW
REGULA
TOR BODY
Specify:
• HD regulator body
• Regulator size or capacity
• End connections (threaded, 150/300# flanged)
MINIMUM OPERATING PRESSURES
Minimum Inlet Pressure:
15 PSIG(Standar
5 PSIG(Low Pr
Low Pressure Temperature Pilot must be used in conjunction with a
Low Pressure Main Valve for applications where inlet steam pressure
is less than 15 PSIG. SPECIFY WHEN ORDERING.
d Main Valve with
Standard Temperature Pilot)
essure Main Valve with
Low Pressure Temperature Pilot)
105
145
235
470
C
B
E
D
HOW IT WORKS
The temperature pilot controls the operation of
the temperature regulating valve. The temperature
sensing bulb, which is filled with a temperature
sensitive liquid, is placed in the process fluid that is
being heated. When the temperature of the process
fluid reaches its set point, the bellows expands and
closes off the pilot valve. When the pilot valve is shut,
steam can no longer pass thru to the underside of the
regulator diaphragm, and the main valve closes.
When the process fluid cools below the set
temperature, the main valve reopens.
Temperature
Adjustment
Knob
Bellows
Pilot Valve
Inlet
Main Valve
TEMPERATURE PILOT
Temperature
Sensing Bulb
Control
Pressure
Line
Bleed
Orifice
Outlet
Diaphragm
Orifice with
Clean-out Wire
REGULATING VALVES
REGULATING VALVES
PILOT-OPERATED
Main Valve Diaphragm
428 Jones Boulevard • Limerick Airport Business Center • Pottstown PA • 19464 • Tel: 610-495-5131 • Fax: 610-495-5134
The HD Regulator with the “A” Air Pilot is used
for reducing steam pressure on steam mains and
process equipment. The “A” Air Pilot can also be
used in conjunction with the PTL and PTR Pneumatic
Temperature Controllers for controlling temperature in
process applications. The principal advantage of the
“A” Air Pilot over standard spring-loaded pilots is that
pressure adjustments to the regulator can be made from
a remote location. A regulator placed in a difficult to
reach or inaccessible location can be adjusted by a
remote control panel board placed in an accessible
location.
FEATURES
Air Pilot can be used with PTL or PTR Pneumatic
•
Temperature Controller
Pressure adjustments of the regulator can be done
•
from a remote location
Air-operated pilot insures instant response and
•
very accurate control
Full port strainer and blowdown valve on pilot
•
adapter for ultimate protection from dirt and scale
Controls pressure settings within ±1 PSIG
•
OPTIONS
Solenoid Pilot (S-Pilot) can be added for
•
Electrical On/Off Operation of the regulator
MAXIMUM CONTROL AIR PRESSURE ON AIR PILOT IS 125 PSIG
PRESSURE-ADJUSTING RANGES
ModelPressureDescription
A13-125 PSIG1:1 ratio of steam pressure to control air pressure
A43-200 PSIG4:1 ratio of steam pressure to control air pressure
A620-200 PSIG6:1 ratio of steam pressure to control air pressure
Ranges
Example:
With the A1 air pilot, 10 PSIG of air pressure
maintains 10 PSIG of steam pressure
Example:
With the A4 air pilot, 10 PSIG of air pressure
maintains 40 PSIG of steam pressure
Example:
With the A6 air pilot, 10 PSIG of air pressure
maintains 60 PSIG of steam pressure
MINIMUM OPERATING PRESSURES
Minimum Inlet Pressure:
15 PSIG(Standar
5 PSIG(Low Pr
Minimum Differential Pressure:
10 PSI(Standar
3 PSI (Low Pr
d Main Valve)
essure Main Valve)
d Main Valve)
essure Main Valve)
140
CONTROL AIR PRESSURE RANGE
A-Pilot Control Pressure:
3-125 PSIG (depending on pilot selected and
desired outlet pressure)
428 Jones Boulevard • Limerick Airport Business Center • Pottstown PA • 19464 • Tel: 610-495-5131 • Fax: 610-495-5134
* Add 21/2” to “C” dimension for A4 or A6 Air Pilots on 2” thru 4” valves.
1
** Add 1
/2” to “E” dimension for A4, and 21/4”” for A6.
7
1
/8
/8
12
1614
1
5
/2
1
5
/2
1
66
3
98
/4
3
7
/8
3
/8
7
/8
1
/4
3
7
/4
8
/8
1
7
/2
10
/8
1
/8
1
1
7
/2
6
1
7
/2
6
1
7
/2
1
7
/2
8
1
7
/2
8
1
7
/2
10
1
/2
11
1
7
/2
13
1
7
/2
14
1
8
/4
19
3
/2
7
/4
1
3
/2
7
/4
3
77
3
3
7
3
1
3
3
/4
3
/4
8
/8
3
/4
8
/8
3
/8
8
/4
3
/4
8
/4
1
/4
9
/2
1
/4
10
/2
3
/4
11
/4
18
18
2335
43
4360
6585
MATERIALS
Body Ductile Iron
CoverDuctile Iron
GasketGrafoil
Cover ScrewsSteel
Pilot AdapterDuctile Iron/Cast Steel
ScreenStainless Steel
TubingCopper
Valve SeatHardened SST (55 Rc)
Valve DiscHardened SST (55 Rc)
DiaphragmPhosphor Bronze
105
145
235
470
C
B
E
D
HOW IT WORKS
When air pressure is applied to the upper chamber
of the air pilot it exerts a downward force on the
air pilot’s diaphragm. The lower chamber of the air
pilot is connected to the outlet side of the regulator
using a sensing line. The purpose of the sensing
line is to sense the pressure on the outlet side of
the regulator. When the intended set pressure is
reached, the pilot valve closes which then closes
off the flow path of steam to the underside of the
diaphragm chamber in the regulator body. The
regulator modulates maintaining the desired
downstream pressure regardless of the amount
of steam being used.
REGULATING VALVES
PILOT-OPERATED
HOW TO ORDER
“A” AIR PILOT
Specify:• Air Pilot A1, A4 or A6
• Remote Control Panel Board: PL1, PL2 or PL3
REGULA
Specify:• HD regulator body
TOR BODY
• Regulator size or capacity and pressures of steam required
• End connections (threaded, 150/300# flanged)
428 Jones Boulevard • Limerick Airport Business Center • Pottstown PA • 19464 • Tel: 610-495-5131 • Fax: 610-495-5134
Pilot-Operated Pressure & Temperature Regulating Valve
HDRegulating Valve
with
“T”
TemperaturePilots
“P”
Pressure&
• Max Inlet Pressure: 300 PSIG
• Reduced Outlet Pressure Range: 3-200 PSIG
REGULATING VALVES
PILOT-OPERATED
• Temperature Control Range: 60-260 F
• Min Inlet Pressures:
15 PSIG
standard main valve with standard temperature pilot
5 PSIG low pressure main valve with low pressure temp. pilot
Low Pressure Temperature Pilot must be
used in conjunction with a low pressure
main valve for applications where inlet
steam pressure is less than 15 PSIG.
SPECIFY WHEN ORDERING
TYPICAL APPLICATIONS
The HD Regulator with both the “P” Pressure Pilot and
“T” Temperature Pilot is used to simultaneously control
both pressure and temperature in process applications.
Using both the temperature and pressure pilot on the
same regulator eliminates the need for two separate
regulators to control temperature and pressure.
FEATURES
Pressure and temperature pilot combination
•
eliminates the need for two separate regulators
Choice of three overlapping pressure ranges
•
Pilot is installed using only four bolts
•
Full port strainer and blowdown valve on pilot
•
adapter for ultimate protection from dirt and scale
Body Ductile Iron
CoverDuctile Iron
GasketGrafoil
Cover ScrewsSteel
Pilot AdapterDuctile Iron/Cast Steel
ScreenStainless Steel
TubingCopper
Valve SeatHardened SST (55 Rc)
Valve DiscHardened SST (55 Rc)
DiaphragmPhosphor Bronze
HOW TO ORDER
“T” TEMPERATURE PILOT
Specify:• Temperature range from the chart or indicate the set
temperature of the process you wish to control
• The length of capillary required; 8-ft. is standard
• Bulb type needed: T, TU, TUBW, TUSW, TBW & TSW
“P” PRESSURE PILOT
Specify:• Pressure range from the chart
105
470
C
B
E
D
HOW IT WORKS
A pressure pilot and temperature pilot can be used
together to control the operation of the regulator.
The pressure pilot limits the outlet pressure of the
regulator when the temperature pilot calls for steam.
The temperature pilot senses the temperature of the
process that is being controlled and opens or closes
the regulator accordingly. Using a pressuretemperature pilot combination eliminates having
to use two separate valves.
Temperature
Sensing Bulb
TEMPERATURE
PILOT
Temperature
Pilot Valve
Inlet
Temperature Adjustment Knob
PRESSURE
PILOT
Pressure
Adjusting Screw
Pressure
Pilot
Diaphragm
Pilot Valve
Bleed
Orifice
Outlet
REGULATING VALVES
PILOT-OPERATED
REGULA
TOR BODY
Specify:• HD regulator body
• Regulator size or capacity and pressures of steam required
• End connections (threaded, 150/300# flanged)
428 Jones Boulevard • Limerick Airport Business Center • Pottstown PA • 19464 • Tel: 610-495-5131 • Fax: 610-495-5134
www.watsonmcdaniel.com
Main Valve
Main Valve Diaphragm
Control
Pressure
Line
Diaphragm
Orifice with
Clean-out Wire
143
REGULATORS
HSP Series
Pilot-Operated Pressure Regulating Valve
ModelHSP Series
Sizes1”, 11/2”, 2”, 3”, 4”
Connections150#/300# Flange
Body MaterialCast Steel
PMO Max. Operating Pressure450 PSIG
The HSP-Series Main Valve with integral Pressure Pilot reduces
steam pressure in steam system piping mains and process
applications. This pilot-operated regulator is specifically used
in applications where the properties and benefits of Cast Steel
are desired and/or specified. Using steel as the material of
construction for the main valve body extends the temperature
ranges of the regulator. A unique two-bolt pilot adapter design
and field-reversible tubing offer even greater versatility to this
type of regulator, further reducing maintenance downtime.
These valves share the same design and proven reliability of
the Watson McDaniel HD-Series Regulators, providing extremely
accurate control of downstream system pressure even when
inlet pressure to the regulator fluctuates or steam usage varies.
FEATURES
Cast Steel body for higher pressure and temperature ratings
•
New, convenient bolt-on pilot design simplifies installation
•
New diaphragm design improves performance and
•
extends life
Hardened stainless steel trim for extended life
•
Optional Stellite trim available
•
Full port strainer and blowdown valve on pilot adapter
•
for ultimate protection from dirt and scale
Maintains downstream pressure+1.0 PSIG
•
Choice of three overlapping spring ranges
•
Pre-mounted pilot & tubing simplifies installation
•
LOTS
CONTROL PILOTS
Pilot Mounting
Standard pilot mounting is on the right side of the regulator
when looking into the outlet port (see diagram on opposite
page which is right mounted). For opposite mounting, please
specify when ordering. Pilot mounting on HSP regulators are
field reversible.
Pressure
The spring-adjusted Pilot is used for general purpose pressure
reducing applications.
MATERIALS
Body ASTM A-216 GR WCB
CoverASTM A-216 GR WCB
Diaphragm CoverASTM A-216 GR WCB
PilotASTM A-216 GR WCB
GasketsGarlock 3400/grafoil SLS
Seat420F SS
(optional Stellite seat, consult factory)
Disc420F SS
Diaphragm300 SS
Mfg. BoltsSA-193 GR B7
Spring302 SS
Stem416 SS
144
428 Jones Boulevard • Limerick Airport Business Center • Pottstown PA • 19464 • Tel: 610-495-5131 • Fax: 610-495-5134
www.watsonmcdaniel.com
REGULATORS
HSP Series CAST STEEL
Pilot-Operated Pressure Regulating Valve
DIMENSIONS HSP Series –
(A) Face-To-FaceWeight (lbs)
SizeNPT150# 300#BCDNPT150# 300#
1”x5
11/2”x 6
2”x 8
3”x1010
4”x11
1
/2
7
/8
7
1
/2
7
/8
12
1
66
3
98
/4
3
/8
7
/8
1
/4
3
7
/4
8
/8
1
7
/2
10
/8
inches / pounds
1
3
/2
7x40 45
7
4
5
6
7
3
/8
8
/4
3
3
1
7
/8
10
/8
1
/4
13
/4
3
/2
14
/4
x55 60
x 7585
x130145
x215235
MINIMUM OPERATING PRESSURES
Minimum Inlet Pressure:
15 PSIG (standard Main Valve)
5 PSIG (low pressure Main Valve)
Minimum Differential Pressure:
10 PSIG (standard Main Valve)
3 PSIG (low pressure Main Valve)
HOW TO ORDER
REGULATOR BODY
Specify: • HSP regulator body
• Regulator size or capacity of steam required
• End connections (150#/300# flanged)
PILOT REQUIRED TO OPERA
• Pressure Pilot (Specify Range)
Specify:10-40 PSIG - Yellow
25-100 PSIG - Blue
75-300 PSIG - Red
Example: 2” HSP, 150# FLG, 10-40 PSIG (yellow)
TE THIS VALVE
REGULATING VALVES
PILOT-OPERATED
FLOW
A
OUT
B
C
D
428 Jones Boulevard • Limerick Airport Business Center • Pottstown PA • 19464 • Tel: 610-495-5131 • Fax: 610-495-5134
www.watsonmcdaniel.com
Standard pilot mounting
is on the right side of the
regulator when looking
into the outlet port (as
shown). Pilot mounting
on HD regulators are
field reversible.
145
NOISE ATTENUATORS
Series-A
for Pressure Regulating Valves
Noise Attenuation Equipment is used to reduce unwanted or excessive noise that
The Series-A Orifice Plate with its drilled orifice pattern is
installed after the pressure regulating valve to smooth out
turbulence caused by the pressure drop across the regulator.
Noise reduction levels of 5-10 dBA can typically be achieved.
INSTALLATION
The Series-A Orifice Plate is installed between ANSI flanges
immediately after the regulator. If the regulator is a flanged unit,
the orifice plate is placed at the flange outlet connection.
Series-A
Orifice Plate
Series-A Typical Hook-up
Sensing Line
For Regulator
FLOW
Pressure
Reducing
Valve
SERIES-A
ORIFICE
PLATE
Series A Dimensions
Orifice Plate installed
between flanges
FLOW
.75
Series-A DIMENSION (A) –
Pipe Size125# Flange250# Flange
2”64
21/2”74
3”71/2511/16
4”96
6”11911/16
Note: Other sizes available. Consult factory.
inches
3
/16
15
/16
15
/16
A DIa.
146
428 Jones Boulevard • Limerick Airport Business Center • Pottstown PA • 19464 • Tel: 610-495-5131 • Fax: 610-495-5134
www.watsonmcdaniel.com
NOISE ATTENUATORS
ACOUSTIC SILENCER
Noise Attenuation Equipment is used to reduce unwanted or excessive noise that
commonly occurs in pressure reducing stations.
Series-H ACOUSTIC SILENCER
Noise Reduction Capability: 20-30 dBA
Series-H
Acoustic Silencer
Series-H
for Pressure Regulating Valves
Series-H Dimensions
BA1
Inlet
C
A
REGULATING VALVES
PILOT-OPERATED
HOW IT WORKS
The Series-H Acoustic Silencer incorporates a Dual Diffuser
tube design. The inner tube has a drilled orifice pattern and
the outer tube contains an integral layer of sound absorbing
insulation. Noise reduction levels of 20-30 dBA can typically
be achieved.
INSTALLATION
The Series-H Diffuser Tube should be installed immediately
downstream of the regulator, as shown below.
Series-H Typical Hook-up
Gate
Valve
Separator
FLOW
To Trap
Strainer
PRV
Series-H DIMENSIONS –
ModelA1ABC
LCV-8481457145
LCV-106101671210
LCV-126121881295
Note: Other sizes available. Consult factory.
Pressure
Sensing Line
SERIES-H
ACOUSTIC
SILENCER
Gate
Valve
inches
Weight
(lbs)
428 Jones Boulevard • Limerick Airport Business Center • Pottstown PA • 19464 • Tel: 610-495-5131 • Fax: 610-495-5134
The Series-S Acoustic Diffuser incorporates a single tube with
a drilled orifice pattern which reduces downstream turbulence.
Noise reduction levels of 10-15 dBA can typically be achieved.
INSTALLATION
The Series-S Diffuser Tube should be installed immediately
downstream of the regulator, as shown below.